Troubleshooting | 8
0870208958_INVEOR_VFD_-0002_PCI_en
39 / 44
No. Error name
Description of error
Possible causes/remedy
22
Acknowledgement error
The number of maximum automatic
acknowledgements (1.182) was ex-
ceeded
Check error history and remedy error
23
External fault 1
The parameterised fault input is active.
5.010
Correct the external fault
24
External fault 2
The parameterised fault input is active.
5.011
Correct the external fault
25
Motor detection
Motor identification error
Check variable-frequency drive/motor
and PC / remote control / variable-
frequency drive connections / restart
motor identification
26
STO inputs plausibility
The statuses of the two STO inputs
have not been identical for more than
2 sec.
Incorrect activation of the STO inputs
Check corresponding external wiring
32
Trip IGBT
Protection of the IGBT module against
overcurrent has been triggered
Short circuit in the motor or motor
feed line / controller settings
33
Overvoltage of intermediate
circuit
The maximum intermediate circuit
voltage has been exceeded
Feedback by motor in generator
mode / mains voltage too high /
faulty setting for rotation speed con-
troller / brake resistor not connected
or defective / ramp times too short
34
Undervoltage of intermediate
circuit
The minimum intermediate circuit
voltage has not been reached
Mains voltage too low, mains connec-
tion defective / check wiring
35
Excess motor temperature
Motor PTC has been triggered
Overload of the motor (e.g. high
torque at low motor speed) / ambient
temperature too high
36
Power failure
The grid voltage has dropped briefly
Grid fluctuation / grid voltage inter-
rupted
38
Excess IGBT module temper-
ature
Excess IGBT module temperature
Insufficient cooling, low motor speed
and high torque, switching frequency
too high
39
Overcurrent
Maximum output current of variable-
frequency drive exceeded
Motor stalled / check motor connec-
tion / incorrect speed controller set-
ting / check motor parameters / ramp
times too short / brake not open
40
Excess frequency converter
temperature
Inner temperature too high
Insufficient cooling / low motor speed
and high torque / switching frequency
too high permanent overload / reduce
ambient temperature / check fan
42
I2t motor protection shutoff
The internal I2t motor protection (can
be parameterised) has been triggered
Permanent overload
43
Ground leak
Ground leak during a motor phase
Insulation fault
45
Motor connection disrupted
No motor current in spite of control
through frequency converter
No motor connected or not com-
pletely connected
Check phases or motor connections
and connect correctly when necessary
46
Motor parameters
Plausibility check for motor parameters
failed
Parameter set not OK
47
Variable-frequency drive
parameters
Plausibility check for variable-fre-
quency drive parameters failed
Parameter set not OK, motor type
33.001 and control method 34.010
not plausible
48
Type plate data
No motor data entered
Please enter the motor data according
to the motor nameplate