Parameter Description | 7
0870208958_INVEOR_VFD_-0002_PCI_en
31 / 44
4.050 AI2 input type
Function of analogue input 2:
2 = current input
4.051 AI2 standard Low (%)
Specifies the minimum value of the analogue inputs as a percentage of the range:
Example:
0 … 20 mA
►
0% … 100%
2 … 40 mA
►
20% … 100%
0
►
0 mA
►
0% = default value to be adapt to your process
4.052 AI2 standard High (%)
Specifies the maximum value of the analogue inputs as a percentage of the range:
Example:
0 … 20 mA
►
0% … 100%
2 … 40 mA
►
20% … 100%
100
►
20 mA
►
100% = default value to be adapt to your process
4.053 AI2 dead time (%)
Dead time as percentage of the range of the analogue input:
0 = no dead time default value, to be adapted to your process
4.054 AI2 filter time (second)
Filter time of analogue inputs in seconds:
0.02 = default value to be adapt to your process
4.060 AI2 function
Function of analogue input 2:
0 = analogue input
4.063 AI2 physical unit
Selection of different physical values to be displayed:
4.063 =
0
%
4.063 =
1
bar
4.063 =
2
mbar
4.063 =
3
psi
4.063 =
4
Pa
4.063 =
5
m
3
/h
4.063 =
6
l/min
4.063 =
7
°C
4.063 =
8
°F
4.063 =
9
m
4.063 =
10
mm
4.064 AI2 physical minimum
Selection of the lower limit of a physical value to be displayed:
0 = default value to be adapt to your process