Model 9163
Digital indicator
Page 72
¾
Use the following codes to set the position of the decimal point.
Only positions "0" and "1" are available for thermocouples.
Code Format
0
0 0 0 0 0
1
0 0 0 0
.
0
2
0 0 0
.
0 0
3
0 0
.
0 0 0
4
0
.
0 0 0 0
Add-on functions:
If it is a linear input:
•
+8 disables the message
Lo
and
Hi
(linear inputs only).
•
+16 disables the message
Ebr
(only for sensors type 0 to 15 and for Sensors type 28 and 29)
•
+32 for linear differential inputs (16...25)
Once you have set the position of the decimal point for this input:
¾
Continue by setting the upper and lower scale values.
To do this, press the [F] button.
The display now shows the parameter
LoS
.
PV
¾
Set the lower scale value.
Once you have set the lower scale value:
¾
Press the [F] button briefly.
¾
Repeat the procedure for the upper scale value.
The display shows the parameter
HiS
.
PV
¾
Confirm the upper scale value with the [F] button.
The display now shows the parameter
OFS
.
PV
¾
Specify the correction offset for this input.
The correction offset can lie between –999 and +999 scale divisions.
¾
Confirm with the [F] button.
Содержание 9163
Страница 4: ...Model 9163 Digital indicator Page 4...
Страница 5: ...Digital indicator Model 9163 Page 5 9163 as panel mount unit 9163 as bench top unit...
Страница 6: ...Model 9163 Digital indicator Page 6...
Страница 8: ...Model 9163 Digital indicator Page 8...
Страница 12: ...Model 9163 Digital indicator Page 12...
Страница 56: ...Model 9163 Digital indicator Page 56...
Страница 68: ...Model 9163 Digital indicator Page 68...
Страница 138: ...Model 9163 Digital indicator Page 138...