TABLE 3: TANKLESS HEATER DATA:  Rear

Mounted Heater on Steam and Water
Boilers

TABLE 3A: TANKLESS HEATER DATA:  Front

Mounted Heater on Water Boilers

WARNING

Install an automatic mixing valve at the tankless
heater outlet to avoid risk of burns or scalding
due to excessively hot water at the fixtures.
Adjust and maintain the mixing valve in
accordance with the manufacturer's instructions.

3. FLUSHING OF HEATER — All water contains

some sediment which settles on the inside of the
coil. Consequently, the heater should be
periodically backwashed. This is accomplished by
installing hose bibs as illustrated and allowing
water at city pressure to run into hose bib A,
through the heater, and out hose bib B until the
discharge is clear. The tees in which the hose bibs
are located should be the same size as heater
connections to minimize pressure drop.

4. HARD WATER  — A water analysis is necessary

to determine the hardness of your potable water.
This is applicable to some city water and
particularly to well water. An appropriate water
softener should be installed based on the analysis
and dealer’s recommendation. This is not only
beneficial to the tankless heater but to piping and
fixtures plus the many other benefits derived from
soft water.

NOTE:  STEAM BOILERS

a. During summertime operation, the normal water

line should be raised 1”, from 22-5/8” to
23-5/8” (see Figure 1C) for improved tankless
heater performance.

G. INSTALL SMOKEPIPE — The V7 should be vented

into a fireclay tile-lined masonry chimney or chimney
constructed from type L vent or a factory built chimney
that complies with the type HT requirements of
UL103.   The chimney and vent pipe shall have a
sufficient draft at all times, to assure safe proper
operation of the boiler. See Figure 13 for recommended
installation.

1. Install a draft regulator (supplied with boiler)

following the instructions furnished with the
regulator. See Figure 14 for alternate draft regulator
locations.

2. Consider the chimney overall. Chimneys that have

a high heat loss may become less suitable as the
heat loss of the home goes down and the efficiency
of the boiler installed goes up. Most homes have a
chimney appropriate for the fuel and the era in
which the home was built. That may have been a
coal fired or an inefficient oil fired boiler built into
a home without insulation or storm windows. With
increasing fuel prices that home probably has been
insulated and fitted with storm windows so that the
heat loss of the home has been reduced. This

cold water with the hot. This prevents excessive
and possibly scalding hot water at the fixtures. In
addition, savings of hot water will be achieved
since the user will not waste as much hot water
while seeking water temperature to his liking.
Higher temperature hot water required by
dishwashers and automatic washers is possible by
piping the hot water from the heater prior to
entering the mixing valve. The mixing valve should
be “trapped” by installing it below the cold water
inlet to heater to prevent lime formation in the
valve.

Boiler

Model

Heater

No.

Heater Rating

(GPM)

Pressure Drop

Thru Heater (PSI)

V73

222

3

22

V74

222

3.5

22

V75

222

4

30.5

V76

222

4.5

33

V77

222

4.6

33

A54

5.5

36

V78

222

4.75

40

A54

6

39.5

V79

222

4.75

40

A54

6

39.5

Boiler

Model

Heater

No.

Heater Rating

(GPM)

Pressure Drop

thru Heater

(PSI)

Steam

Water

Steam

Water

V713

V1-2

---

3.25

---

5.6

V73

V1-2

2.75

3

3.9

4.7

V714

V1-1

---

3.5

---

4.4

V1-2

---

4

---

8

V74

V1-2

3

3.25

4.7

5.6

V75

V1-2

3.25

3.5

5.6

6.4

V76

V1-2

3.75

3.75

7.2

7.2

V77

V1-2

3.75

4

7.2

8

V78

V1-2

4

4.5

8

9.8

V79

V1-2

4

4.5

8

9.8

Содержание V7 SERIES

Страница 1: ...he installationofULClabeled V 7 Series Boilers As an ENERGY STAR Partner Burnham Corporation has determined that the V73WR 0 60 GPH V74WR 0 80 GPH V75WR 0 90 GPH and V76WR 1 15 GPH meet the ENERGY STA...

Страница 2: ...ASON FOR ANY OBSTRUCTIONS A CLEAN AND UNOBSTRUCTED CHIMNEY FLUE IS NECESSARY TO ALLOW NOXIOUS FUMES THAT COULD CAUSE INJURY OR LOSS OF LIFE TO VENT SAFELY AND WILL CONTRIBUTE TOWARD MAINTAINING THE BO...

Страница 3: ...Size Water Content Gallons Heat Transfer Surface Area Sq Ft Approximate Shipping Weight LB A B C Steam Boiler Water Boiler Steam Boiler V72 11 3 8 6 3 8 5 8 x 8 x 15 10 6 381 V713 16 8 3 4 6 8 x 8 x...

Страница 4: ...4 Figure 1B V73 thru V79 Water Boiler with Tankless Heater WBT Figure 1C V73 thru V79 Steam Boiler with or without Tankless Heater SBT or SB...

Страница 5: ...5 Figure 1E V713 and V714 Packaged Water Boiler with Tankless Heater WBT Figure 1D V713 and V714 Packaged Water Boiler Less Tankless Heater WB Burnham...

Страница 6: ...de at least 24 clearance from front jacket panel for servicing and removal of front tankless heater increase to 30 for A54 heater Provide at least 24 clearance from right side of boiler or top of boil...

Страница 7: ...If loose retighten mounting hardware If flue plate or sealing insulation is damaged repair or replace as needed G INSTALL AND SECURE CANOPY with cerafelt gasket and hardware provided to ensure gas ti...

Страница 8: ...ss Probe LW CO Water G aug e G lass Pre ssuretrol a nd LW CO Flo at Flush Plu g F L4 006 A Op era tin g C on trol Disre gard L81 24 C Op era tin g C on trol G 1 Bushe d to for Draincock O ptiona l Re...

Страница 9: ...Fold panel at perforation keeping insulation inward Align left side panel mounting holes with the front and rear panel holes Secure with 8 x long sheet metal screws 5 Install jacket top panel Place ja...

Страница 10: ...e slot with vertical set of bolts engage hex head of bolts and rotate burner to the left Install two remaining 5 16 x long bolts in horizontal sets of holes Level burner and fully tighten all bolts K...

Страница 11: ...eturn on water boilers 5 If CIRCULATOR not supplied with boiler is to be mounted directly to 1 boiler return tapping G use the piping arrangements outlined in steps a thru e as follows a Thread 1 x 3...

Страница 12: ...ded in trim bag See Figure on previous page Connect wiring harness from Low Water Cutoff See Figure below TS 39 126 A 5 If this boiler is used in connection with refrigeration systems the boiler must...

Страница 13: ...13 Fig 8 V73 Thru V79 Recommended Boiler Piping For Gravity Return Steam Boiler Fig 9 V72 thru V79 V713 and V714 Recommended Boiler Piping for Series Loop Forced Hot Water System TS 39 17 D TS 39 4 C...

Страница 14: ...he distribution system 5 Isolating the boiler from the system water by installing a heat exchanger F CONNECT TANKLESS HEATER PIPING AS SHOWN IN Figure 12 See Tables 3 and 3A for Tankless Heater Rating...

Страница 15: ...raft at all times to assure safe proper operation of the boiler See Figure 13 for recommended installation 1 Install a draft regulator supplied with boiler following the instructions furnished with th...

Страница 16: ...nto a container Continue to bleed for 15 seconds after oil is free of air bubbles Stop burner and close valve requires less fuel to be burned and sends less heat up the chimney A new boiler probably h...

Страница 17: ...S Figure 15 TABLE 4 SINGLE STAGE UNITS 3450 RPM TWO PIPE SYSTEMS Lift H See Fig 16 Manimum Length of Tubing H R See Figure 16 3 8 OD Tubing 3 GPH 1 2 OD Tubing 3 GPH 0 84 100 1 78 100 2 73 100 3 68 10...

Страница 18: ...be low water cutoffs will shut down the burner after a 10 15 second delay if the water level in the boiler drops too low The Hydrolevel CG 450 and the McDonnell Miller PS 804 120 low water cutoffs wil...

Страница 19: ...er cut off will shut down the burner if the water level in the boiler drops too low The control resets and restarts the burner with a call for heat a few seconds after the water is returned to its nor...

Страница 20: ...t by the thermostat energizes the L8124C control which in turn energizes the R4184D primary control to turn on the burner If burner ignites within approximately 45 seconds and the cad cell sees flame...

Страница 21: ...WITHOUT TANKLESS HEATERS set high limit dial on L8148 at 210 F This temperature may be varied to suit requirements of installation 6 On WATER BOILERS WITH TANKLESS HEATERS set operating control dial...

Страница 22: ...the ability to control air by moving the head either forward or back Loosen the adjusting plate assembly hold down screw Slide the head and plate to the required firing rate setting as shown in Figure...

Страница 23: ...service is complete be sure to fasten down the ignitor 7 FLAME FAILURE The V7 boiler controls operate the burner automatically If for unknown reasons the burner ceases to fire and the reset button on...

Страница 24: ...at cell is securely in socket Reconnect leads Reset safety switch h Close line switch If burner starts and runs beyond safety switch cut out time cell is good If not install new cell 3 WARNING Check H...

Страница 25: ...tion of mud scale etc and clean as required Examine all visible wiring for brittle or worn insulation and make sure electrical contacts are clean and that they function properly Give special attention...

Страница 26: ...manner i Remove safety relief valve using extreme care to avoid damaging it ii Add an appropriate amount of Continue this slow boiling and trickle of overflow for several hours until the water coming...

Страница 27: ...ceman to have 2 FLAME SHAPE Looking into the combustion chamber through the observation door the flame should appear straight with no sparklers rolling up toward the crown of the chamber If the flame...

Страница 28: ...N This boiler contains controls which may cause the boiler to shut down and not restart without service If damage due to frozen pipes is a possibility the heating system should not be left unattended...

Страница 29: ...ture fall R B will make and R W will break at 130 F Set low limit indicator at the minimum temperature recommended for domestic hot water supply This setting must be at least 20 F below high limit set...

Страница 30: ...s necessary to allow removal of the jacket top panel and canopy smokebox c Remove the jacket top panel d Remove the canopy being careful not to damage the ceramic fiber gasket 5 Using a 1 diameter wir...

Страница 31: ...er Illinois A Albany Fulton Montgomery B Loudoun Northampton and Indiana A Rensselaer Saratoga Prince William Counties Iowa A Schenectady Schoharie All other Counties A Kansas A Warren Washington Coun...

Страница 32: ...32 BARE BOILER ASSEMBLY...

Страница 33: ...ning Machined 71727036 1 1 1 1 1 1 1 6 5 Cast Iron Slip Nipple 7066003 1 2 3 4 5 6 7 8 7 2 Cast Iron Slip Nipple 7066001 1 4 2 6 3 4 5 6 7 8 8 Rear Target Wall Insulation 8202701 1 1 1 1 1 1 1 1 1 1 8...

Страница 34: ...34 BARE BOILER ASSEMBLY CONTINUED...

Страница 35: ...wing Door Mounting Plate 7172705 1 1 1 1 1 1 1 1 1 1 14A Burner Swing Door Mounting Plate Insulation 82027021 1 1 1 1 1 1 1 1 1 1 15 Rope Gasket Burner Mounting Plate 53 Lg 72027014 1 1 1 1 1 1 1 1 1...

Страница 36: ...36 TS 39 112 D V713 and V714 FLUSH JACKET...

Страница 37: ...de Top Panel Assembly 604270314 1 604270414 1 4 Jacket Top Panel Assembly 604270322 1 604270422 1 5 Jacket Lower Right Side Panel Assembly 604270337 1 604270437 1 6 Jacket Upper Right Side Access Pane...

Страница 38: ...38 V72 Thru V79 FLUSH JACKET TS 39 109 D...

Страница 39: ...acket Left Side Top Panel Assembly 604270241 1 604270341 1 604270441 1 604270541 1 604270641 1 604270741 1 604270841 1 604270941 1 5 Jacket Top Panel Assembly 604270221 1 604270321 1 604270421 1 60427...

Страница 40: ...40 V73 Thru V79 STEAM BOILERS TRIM AND CONTROLS...

Страница 41: ...Syphon NPT x 4 x 180 806603030 1 1 1 1 1 1 1 3D1 Bushing NPT x NPT 806600508 1 1 1 1 1 1 1 3D2 Elbow NPT 806601520 1 1 1 1 1 1 1 3D3 Nipple NPT x 2 806600003 1 1 1 1 1 1 1 3E Gage Glass Set 6 ConBraC...

Страница 42: ...42 V72 Thru V79 V713 and V714 WATER BOILERS TRIM AND CONTROLS...

Страница 43: ...1 1 1 1 1 1 1 1 3C Honeywell R4184D 1027 1001 Protectorelay 80160473 1 1 1 1 1 1 1 1 1 1 4 CIRCULATOR PIPING Packaged Boiler Only 4A Circulator Taco 007F position 2 8056007 1 1 1 1 1 1 1 1 1 1 4B Gas...

Страница 44: ...44 Beckett AFG Burner...

Страница 45: ...3 5503 5503 5503 5503 5503 5503 5503 5503 5503 Escutcheon Plate 3493 3493 3493 3493 3493 3493 3493 3493 Adjusting Plate Assembly 5941 5941 Head 5912 360003 4 360004 360006 5 360004 6 360006 7 360012 3...

Страница 46: ...46 Print word document...

Страница 47: ...47...

Отзывы: