Table 11: Gas Flow Rate in Cubic Feet per Hour
Seconds
for One
Revolution
Size of Gas Meter Dial
One-Half
Cu. Ft.
One
Cu. Ft.
Two
Cu. Ft.
30
60
120
240
32
56
113
225
34
53
106
212
36
50
100
200
38
47
95
189
40
45
90
180
42
43
86
172
44
41
82
164
46
39
78
157
48
37
75
150
50
36
72
144
52
35
69
138
54
33
67
133
56
32
64
129
58
31
62
124
60
30
60
120
J
. Ignition system safety device test.
Disconnect ignitor/
sensor cable from Terminal 9 (SPARK). Gas valve
should close and pilot and main burners should
extinguish.
K.
Check water pressure switch.
1. Adjust thermostat to highest setting.
2. Connect hose to drain valve and run to bucket or
floor drain. With boiler operating, partially open
drain valve and slowly drain boiler.
3. Main burners and pilot burner will extinguish and
blower stop when water pressure drops below 10
psi. Verify limit, thermostat or other controls have
not shut off boiler.
4. Close drain valve.
5. Adjust thermostat to lowest setting. Refill boiler.
L.
Check Boiler High Limit.
1. Adjust thermostat to highest setting.
2. Observe temperature gauge. When temperature is
indicated, adjust limit to setting below observed
temperature. Main burners and pilot burner should
extinguish, and blower stop.
3. Adjust limit to setting above observed temperature.
Ignition sequence should begin.
4. Adjust thermostat to lowest setting. Adjust limit to
desired setting, at least 20°F above the tank aquastat
setting.
M.
Adjust gas input rate to boiler.
1. Adjust thermostat to highest setting.
2. Check manifold gas pressure. Pressure should be
stamped on the rating label located in the boiler's
vestibule compartment. Adjust gas valve pressure
regulator as necessary (turn adjustment screw
counterclockwise to decrease manifold pressure, or
clockwise to increase manifold pressure). If pressure
cannot be attained, check gas valve inlet pressure. If
less than minimum indicated on the boiler's rating
label, contact gas supplier for assistance.
3. Clock gas meter for at least 30 seconds. Use Table
11 to determine gas flow rate in Cubic Feet per
Hour.
4. Determine Input Rate. Multiply gas flow rate by gas
heating value.
5. Compare measured input rate to input rate stated on
rating plate.
a. Boiler must not be overfired. Reduce input rate
by decreasing manifold pressure. Do not reduce
more than 0.2 inch w.c. If boiler is still overfired,
contact your U.S. Boiler distributor or Regional
Office for replacement Gas Orifices.
b. Increase input rate if less than 98% of rating
plate input. Increase manifold gas pressure no
more than 0.2 inch w.c. If measured input rate is
still less than 98% of rated input:
i.
Remove Main Burners per procedure in
Section IX: Service.
ii.
Remove gas orifices. Drill one (1) drill size
larger (drill size is stamped on orifice, or see
Key No. 4C in Section X: Repair Parts).
iii.
Reinstall gas orifices and main burners.
Measure input rate.
6. Recheck Main Burner Flame.
7. Return other gas fired appliances to previous
conditions of use.
N
. Review User's Information Manual
and system
operation with owner or operator.
Содержание Minuteman II
Страница 6: ... Figure 4 Recommended Boiler Piping For Circulator Zoned Heating Systems ...
Страница 7: ... Figure 5 Recommended Water Piping for Zone Valve Zoned Heating Systems ...
Страница 22: ...22 Figure 21 Operating Instructions ...
Страница 25: ...25 Figure 23 Troubleshooting Guide ...
Страница 30: ...30 Figure 27 Burner and Flueway Cleaning ...
Страница 33: ...33 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 34: ...34 ...
Страница 35: ...35 ...
Страница 37: ...37 ...
Страница 38: ...38 ...
Страница 40: ...40 ...
Страница 46: ...46 SERVICE RECORD DATE SERVICE PERFORMED ...