Burnham 101602-01 Скачать руководство пользователя страница 3

Boiler 

Model

Boiler 

Supply 

Connection, 

Inch, FPT

Boiler 

Return 

Connection, 

Inch, FPT

Minimum 

Required Flow 

(GPM)

@ 35°F

 

DT

Boiler 

Head Loss, 

Ft.

@ 35°F 

DT

Required

Flow, 

(GPM)

@ 30°F 

DT

Boiler 

Head Loss,

Ft.

@ 30°F 

DT

Required 

Flow, 

(GPM)

@ 25°F 

DT

Boiler 

Head Loss, 

Ft. @ 25°F 

DT

Maximum 

Required 

Flow (GPM)

@ 20°F

 

D

T

Boiler

Head Loss, 

Ft. 

@ 20°F

 

DT

ALP080

1

1

4.2

4.8

4.9

6.4

5.8

8.9

7.3

13.4

ALP105

1

1

5.5

7.0

6.4

9.3

7.7

12.8

9.6

19.1

ALP150

1

1

7.9

5.2

9.2

6.6

11.0

8.9

13.8

12.7

ALP210

1

1

11.1

5.4

12.9

7.1

15.5

9.8

19.4

14.4

ALP285

15.1

5.9

17.7

7.8

21.2

10.7

26.5

16.0

ALP399

21.5

6.1

25.1

7.9

30.2

10.8

37.7

15.9

Notes:  Required Flow (GPM) = ** Output (MBH) * 1000 / 500 * 

DT

** Output (MBH) - Select Value for specific Boiler Model from Tables 2A or 2B
Using boiler antifreeze will result in higher fluid density and may require larger circulators.

Table 0:  Flow Range Requirement Through Boiler

Alpine Boiler Head Loss vs. Flow

80

105

150

210

285

399

0

2

4

6

8

10

12

14

16

18

20

0

5

10

15

20

25

30

35

40

Flow Rate (GPM)

Boiler Head Loss (Feet)