Installation / Service / User Manual

                                                                          BURNERTECH 

 
 

 

2.4

 

Burner operation 

 

2.4.1 

Control operation 

 

The microprocessor-based burner controller is made for fan assisted, direct burner ignition 
applications.   
The control powers the gas valve and DC-fan. Normal heat demand is given by a 230 VAC switch 
input (depending on the model) 
After heat demand and successful ignition, modulation can be controlled by external 0 - 10V or        
4 - 20mA signal. 
  

2.4.2 

Basic sequence of operation 

 
The Normal Heating mode is started when the High Voltage Heat Demand input is closed. When 
ignition is successful, the fan can be controlled in a number of ways depending on parameter 
setting: 
 

 

 

 

0-10 V control

, a DC voltage between zero and ten volts can be applied to connector (X3 

Pins 8 & 16). At zero volt the fan will run on Minimum Fan speed. At ten volt the fan will run 
on Maximum Fan speed. 

 

4-20 mA control

, with an external resistor of 500 

Ώ 1 % placed between connector (X3 

Pins 8 & 16), the fan speed can be controlled with a current in the range of 4 to 20 mA. 

             At 4 mA the fan will run on Minimum Fan speed. At 20 mA the fan will run at Maximum Fan   
             Speed. 

 

On/Off control

, when the option On/Off control is selected, the fan speed depends on the 

fan Slope control parameter:  When slope control is off (parameter set to zero), the fan 
speed will immediately go to maximum. Otherwise the fan speed will rise from Ignition Fan 
speed to Maximum Fan speed with(value)*50 RPM/sec. Slope control works for both 
increasing and decreasing of fan speed. 

 

2.4.2.1

 

Burner Program 

 

 

 

NOTE:

 The Control can be reset by depressing the internal/external reset button 

 

 

Содержание INVERTERJET 30M/L

Страница 1: ...bject to Modifications MODEL PRODUCT CODE CLASS INVERTERJET 30M L 91353 MODULATING PRE MIX BURNER INVERTERJET 30M N 91354 MODULATING PRE MIX BURNER INVERTERJET 50M L 91320 MODULATING PRE MIX BURNER IN...

Страница 2: ...4 Commissioning 12 4 1 Commissioning procedure 12 4 1 1 Turning on the Burner 13 4 1 2 Commissioning operation 13 4 1 2 1 Maximum rate CO2 13 4 1 2 2 Minimum rate CO2 13 4 1 2 3 Burner Heat Input 13 4...

Страница 3: ...ility we advise and request that a Burnertech Approved Engineer who has attended our product course conducts the 1st burner commissioning For Training Service or Commissioning information please conta...

Страница 4: ...Installation Service User Manual BURNERTECH 3...

Страница 5: ...Max A 0 3 1 9 1 9 Gas Connection Flange Size 1 2 BSP 1 2 BSP 1 2 BSP Gas Inlet Pressure Min mbar 10 10 10 Max mbar 60 60 60 2 2 Technical Description of the Burner Parts The Burners in the Inverterje...

Страница 6: ...ght mm mm mm mm mm mm mm mm mm kg Inverterjet 30M L 89 71 91 101 6 170 133 218 361 225 5 2 Inverterjet 30M N 89 71 91 101 6 170 133 218 361 225 5 2 Inverterjet 50M L 92 71 91 101 6 170 164 244 365 238...

Страница 7: ...d ten volts can be applied to connector X3 Pins 8 16 At zero volt the fan will run on Minimum Fan speed At ten volt the fan will run on Maximum Fan speed 4 20 mA control with an external resistor of 5...

Страница 8: ...Installation Service User Manual BURNERTECH 7 3 Installation 3 1 General Installation Information...

Страница 9: ...sealing and insulating between the Mounting Plate and the bearing wall of the appliance 3 2 1 Standard Burner Mounting Detail 1 Burner Head 2 Burner Mounting Gasket 3 Boiler Door MODEL C D1 D2 G PCD...

Страница 10: ...front of the Gas connection flange at the rear of the burner 2 Check the thread on the flange and ensure that there is no debris in the threads 3 Connect the corresponding gas pipe fittings to the Gas...

Страница 11: ...Installation Service User Manual BURNERTECH 10 3 4 Electrical Installation The electrical wiring diagram for the Burners are shown in the following page 3 5 Basic Electrical Safety...

Страница 12: ...fit connector is used for communication via a dedicated Windows based PC software and USB lead Please contact Burnertech for more information An Earth must be connected to the 6 3mm spade connector on...

Страница 13: ...g procedure follow the steps bellow 1 Connect a Manometer to the gas inlet pressure test nipple on the burner gas inlet connection 2 Locate CO CO2 combustion analyser into flue pipe as close as possib...

Страница 14: ...5 CAUTION Generally the CO2 should not normally exceed 9 5 on NG or 11 on LPG We recommend that the operating CO2 is between 0 to 0 5 higher at maximum fan speed than at minimum 4 1 2 2 Minimum rate...

Страница 15: ...during a complete burner sequence The basic states are Stand by fan is off or at Continuous Fan speed when this option is selected Pre purge Ignition Run state fan speed is controlled by modulation i...

Страница 16: ...mmunication 4 1 3 1 PC USB Interface If required a windows based software along with a dedicated USB cable and driver is available to enable programming of certain parameters in the control and also t...

Страница 17: ...Installation Service User Manual BURNERTECH 16 5 User Instructions 5 1 Limitations on use of Burner...

Страница 18: ...uous Fan speed option is switched off 5 2 3 Heating Mode The normal heating mode is started when a high voltage heat demand input is closed When ignition is successful the fan can be controlled betwee...

Страница 19: ...m the chamber 6 1 1 The condition of the burner head some discolouration of the burner material is normal but the material should not be cracked or open Under no circumstances should any of the perfor...

Страница 20: ...ion The fan case has gas tight seals and the fan casing must never be opened Due to the 1 1 gas air ratio operating principle of the burner a reduction in fan performance i e dust build up will not re...

Страница 21: ...alse Flame Indication Error is created if flame current is detected in illegal situations no heat demand currently present gas valve closed safety time passed This error condition requires manual rese...

Страница 22: ...Installation Service User Manual BURNERTECH 21 6 3 2 Maintenance Notes...

Страница 23: ...Installation Service User Manual BURNERTECH 22...