SF-2001
August 8, 2017
Fireye Surefire II
High Energy Igniters
DESCRIPTION
The Surefire II High-Energy Ignition System is used for direct spark ignition of most gas or liquid
fuels used in oil or gas igniters or main burners. The High-Energy Ignition System is available in
various versions. To ensure optimal operation, the first part of the ignition tip should always be in an
ignitable fuel-air mixture, during all modes of operation.
After successful ignition, the ignition tip should be disconnected from the power supply and taken
out of the flame. Optionally, when an automated process is required, a pneumatic retraction unit and
systems for hazardous areas are available.
The Surefire II range includes:
Integrated power pack with spark rod.
Split Power pack and separate spark rod.
Portable battery powered Integrated power pack and spark rod.
ATEX, Power pack, and spark rods.
Co-axial Retractors, with / without integrated solenoid valve.
ATEX Solenoid.
Features
Selectable voltage ( 115/230 vac ).
Visual indication of spark operation
Proof of spark relay
Choice of system, Integrated or Kit or Kit with Quick Disconnect
Thermal cutout protection integrated in transformer
ATEX options
Compact "co-axial" retractors
Safety bleed resistor discharges capacitors in 120 seconds.
1