![Bürkert 8695 Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/burkert/8695/8695_operating-instructions-manual_2831914051.webp)
51
DeviceNetinstallation
Procedure
:
noTe!
Breakage of the pneumatic connection pieces due to rotational impact.
▶
When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the
connection housing.
→
Open the control head: turning the transparent cap anti-clockwise.
Body casing
Connection housing
Actuator
Transparent cap
Figure 43:
Open control head
→
Set the DIP switches according to the following tables.
noTe!
Damage or malfunction due to penetration of dirt and humidity.
▶
To observe degree of protection IP65 / IP67, screw the transparent cap in all the way.
→
Close the device (assembly tool: 674078
9)
).
Settings of the Devicenet address
MAC ID - Medium Access Control Identifier:
[DIP 1=off=0 / DIP 1=on=1 / MAC ID=DIP 1*2
0
+DIP 2*2
1
+...+DIP 6*2
5
]
Dip 1
[20=1]
Dip 2
[21=2]
Dip 3
[22=4]
Dip 4
[23=8]
Dip 5
[24=16]
Dip 6
[25=32]
mac iD
off
off
off
off
off
off
0
on
off
off
off
off
off
1
off
on
off
off
off
off
2
...
...
...
...
...
...
...
off
on
on
on
on
on
62
on
on
on
on
on
on
63
Table 15:
Settings of the DeviceNet address
9)
The assembly tool (674078) is available from your Bürkert sales office.
english
Type 8695
Содержание 8695
Страница 190: ...190 Type 8695 français ...
Страница 191: ......
Страница 192: ...www burkert com ...