11.1 Definition
• The DeviceNet is a field bus system which is based on the CAN protocol (Controller Area Network). It enables
actuators and sensors (slaves) to be networked with higher-level controllers (master).
• The control head in the DeviceNet is a slave device according to the Predefined Master/Slave Connection Set
stipulated in the DeviceNet specification. Polled I/O, Bit Strobed I/O and Change of State (COS) are supported
as an I/O connection variant.
• With DeviceNet it is necessary to differentiate between cyclical or event-driven high-priority process messages
(I/O Messages) and acyclical low-priority management messages (Explicit Messages).
• The protocol process conforms to the
Devicenet specification release 2.0.
11.2 Technical data
EDS file BUE8695.EDS
Icons
BUE8695.ICO
Baudrate 125 kbit/s, 250 kbit/s, 500 kbit/s (via DIP switches);
Factory setting: 125 kbit/s
Address 0
–
63 (via DIP switches);
Factory setting: 63
Process data 1 static input assembly (input: from the control head 8695 to the DeviceNet Master/Scanner)
1 static output assembly
11.3 maximum line lengths
The maximum total line length (sum of trunk lines and drop lines) of a network depends on the baudrate.
11.3.1 Total line length according to Devicenet specification
Baudrate
maximum total line length
8)
thick cable
thin cable
125 kbaud
500 m
100 m for all baudrates
250 kbaud
250 m
500 kbaud
100 m
Table 12:
Total line length
8)
According to DeviceNet specification.
If a different cable type is used, lower maximum values apply.