Configuringthenetwork

Abs. index Variable

Data type

Storage

Length

Access

40

IDENT_NUMBER

Unsigned8

S

1

r/w

Table 6:  Assignments of the standard parameters

All parameters of the physical block are acyclic!

Parameter structure of the bit string DIAGNOSIS

Bit

Notation

Description

*

4

DIA_MEM_CHKSUM

Storage checksum error

R

10

DIA_CONF_INVAL

Configuration not valid

R

11

DIA_WARMSTART

Repeated start request 
(warm start request)

A

12

DIA_COLDSTART

Restart request (cold start 
request)

A

Table 7:  Diagnosis of the parameter coding of the Physical Block

Coding of the diagnosis parameters

Values of the diagnosis bits:

0

 = not set

1

 = set

* = 

display class:

R

 = display is active for as long as the reason of the message is available.

A

 = display is automatically reset after the read process.

The standard parameter View Object

Rel. Index

Variable

View_1

View_2

View_3

View_4

1

ST_REV

2

2

TAG_DESCRIPTION

3

STRATEGY

4

ALERT_KEY

5

TARGET_MODUS

6

MODUS _BLK

3

7

ALARM_SUM

8

Table 8:  View Object of the standard parameters

english

Type 8643 PA

Содержание 8643 PA

Страница 1: ...Operating Instructions Bedienungsanleitung Instructions de Service Type 8643 PA Power I O Box with PROFIBUS PA profile 3 0 mit PROFIBUS PA Profil 3 0 avec PROFIBUS PA profil 3 0...

Страница 2: ...he right to make technical changes without notice Technische nderungen vorbehalten Sous r serve de modifications techniques B rkert Werke GmbH Co KG 200 2017 Operating Instructions 1706 0 _EU EN_0080...

Страница 3: ...N 10 5 1 General Description 10 5 1 1 Advantages and technical features 10 5 1 2 Application area 11 5 1 3 Identification 11 5 1 4 Cable connections on the body 12 5 1 5 LED display 13 5 2 Technical D...

Страница 4: ...THE STATION ADDRESSES 23 7 1 LED display 23 7 2 Watchdog 23 8 CONFIGURING THE NETWORK 24 8 1 Storage allocation for user data transfer 24 8 2 System parameters 24 8 2 1 Physical block 24 8 2 2 Transd...

Страница 5: ...Symbols DANGER Warns of an immediate danger Failure to observe the warning may result in a fatal or serious injury WARNING Warns of a potentially dangerous situation Failure to observe the warning may...

Страница 6: ...on Certificate The device may be used only in conjunction with third party devices and components recommended and authorized by B rkert Correct transportation correct storage and installation and care...

Страница 7: ...wer supply for longer than 4 minutes Danger of explosion if the allowable ambient temperature ranges are exceeded Observe the respective ambient temperature range which is based on the type designatio...

Страница 8: ...ectronic components when the power supply voltage is present The Power I O Box Type 8643 was developed with due consideration given to the accepted safety rules and is state of the art Nevertheless da...

Страница 9: ...se printed operating instructions And also on the internet at www burkert com 4 2 Warranty The warranty is only valid if the Power I O Box Type 8643 is used as intended in accordance with the specifie...

Страница 10: ...e usable energy from the bus line is severely restricted However the connection to an Ex e bus is also possible 5 1 1 Advantages and technical features Advantages of the Power I O Box Simple and safe...

Страница 11: ...intrinsically safe circuits of the Power I O Box Type 8643 always switch off the oper ating voltage of the system If using the Power I O Box Type 8643 in a control cabinet ensure that the control cab...

Страница 12: ...device 1 2 3 P r o f i b u s P A I n t e r f a c e D i g i t a l I O No Designation 1 Cable glands for intrinsically safe circuits 8 screw joints blue 2 Cable glands for bus and power supply 4 screw j...

Страница 13: ...lit check power supply 5 2 Technical Data Designation Values Body material Polyester aluminium Colour black Ambient temperature 20 60 C Cable entry Polyamide cable glands Protection class IP 65 DIN E...

Страница 14: ...rdance with IEC 1158 2 in accordance with FISCO EEx i 4 screw terminals bus up to 2 5 mm 3 screw terminals shield 1x directly and 2x capacitively earthed Auxiliary supply Ignition protection type Elec...

Страница 15: ...15 System Description 5 3 Dimensions 260 160 188 110 240 92 Fig 5 Dimensions Type 8643 english Type 8643 PA...

Страница 16: ...exceeded Observe the respective ambient temperature range which is based on the type designation e g 8643 4 AL KS F I O according to the table in the EC Type Examination Certificate Danger of explosio...

Страница 17: ...ly voltage is on Function restriction The function of the device may be restricted without potential equalisation Connect the earth terminal point on the body to the potential equalisation PA 6 2 Inst...

Страница 18: ...4 black M20 x 1 5 cable glands bus and power supply 8 blue M20 x 1 5 cable glands for intrinsically safe circuits sensor actuator outputs Fig 6 Cable glands The body features eight blue cable glands f...

Страница 19: ...erse polarity Pay attention to the polarity of the terminals The device is protected against polarity reversal 6 4 2 Overview of the terminals and outputs LED module Address BUS Power supply 24 V DC B...

Страница 20: ...plosion due to unauthorized combination of the ignition protection types Unauthorized combination of the ignition protection types may cause hazardous situations If the bus supply of the device was op...

Страница 21: ...m authorized bus voltage must be taken into consideration Connection of the cable shield Connect cable shield to the left 2 terminals Connect the shield in a continuous manner Earth the shield at a po...

Страница 22: ...3 14 Output 4 19 20 6 4 6 Sensor terminals The Power I O Box Type 8643 has eight NAMUR sensor inputs two sensors are always assigned to one actuator output The sensors signal back the end positions of...

Страница 23: ...ON OFF ON OFF ON OFF OFF ON OFF ON ON ON OFF ON ON ON OFF ON ON ON OFF ON ON ON OFF ON ON ON 3 124 125 126 Delivery status Address 126 If switch 8 is in the ON position the internal address is used T...

Страница 24: ...e allocation can be found in the handbook 8 2 System parameters All profile data refers to the profile version 3 0 class B This is where you will also find detailed documentation on the parameters Whe...

Страница 25: ...le 24 16 C SOFTWARE_REVISION 25 16 C HARDWARE_REVISION 26 2 C DEVICE_MAN_ID 27 2 C DEVICE_ID 28 16 N Serial number 29 4 D DIANOSIS 30 6 D DIANOSIS_EXTENSION 31 4 C DIANOSIS_MASK 32 6 C DIANOSIS_MASK_E...

Страница 26: ...se by 1 whenever a static block parameter is changed As a result the parameter revision can be checked STRATEGY Arrangement of the function module The STRATEGY field can be used to group blocks TAG_DE...

Страница 27: ...e access The standard parameter View Object Rel Index Variable View_1 View_2 View_3 View_4 1 ST REV 2 2 TAG_DESCRIPTION 3 STRATEGY 4 ALERT_KEY 5 TARGET_MODUS 6 MODUS_BLK 3 7 ALARM_SUM 8 Table 3 View O...

Страница 28: ...rs of the permitted mode are limited for target The modes are specified by the bit string in the following manner Bit Mode 7 Out of service O S MSB 4 Manual Man 3 Automatic Auto 1 Remote Cascade RCas...

Страница 29: ...ce coded bit by bit DIANOSIS_MASK Definition of supported DIAGNOSIS information bits 0 not supported 1 supported DIA_MEM_CHKSUM Storage error DIA_CONF_INVAL Invalid configuration DIA_WARMSTART Warm st...

Страница 30: ...from another block Cst constant The parameter does not change S Static non volatile the version counter ST_REV is increased during the write process Access r read access w write access Abs index Vari...

Страница 31: ...arm start request A 12 DIA_COLDSTART Restart request cold start request A Table 7 Diagnosis of the parameter coding of the Physical Block Coding of the diagnosis parameters Values of the diagnosis bit...

Страница 32: ...NOSIS_MASK_ EXTENSION Table 9 Display objects of the physical block 8 2 2 Transducer Block Abbreviations Storage N Non volatile parameter which must be observed in the operating cycle However it does...

Страница 33: ...edString S 16 r w 91 ACTUATOR_SER_NUM OctedString S 16 r w 92 VALVE_ID OctedString S 16 r w 93 ACTUATOR_ID OctedString S 16 r w 94 ACTUATOR_ACTION Unsigned8 S 1 r w 95 TRAVEL_COUNT Unsigned16 N 2 r w...

Страница 34: ...edString S 16 r w 91 ACTUATOR_SER_NUM OctedString S 16 r w 92 VALVE_ID OctedString S 16 r w 93 ACTUATOR_ID OctedString S 16 r w 94 ACTUATOR_ACTION Unsigned8 S 1 r w 95 TRAVEL_COUNT Unsigned16 N 2 r w...

Страница 35: ...edString S 16 r w 91 ACTUATOR_SER_NUM OctedString S 16 r w 92 VALVE_ID OctedString S 16 r w 93 ACTUATOR_ID OctedString S 16 r w 94 ACTUATOR_ACTION Unsigned8 S 1 r w 95 TRAVEL_COUNT Unsigned16 N 2 r w...

Страница 36: ...edString S 16 r w 91 ACTUATOR_SER_NUM OctedString S 16 r w 92 VALVE_ID OctedString S 16 r w 93 ACTUATOR_ID OctedString S 16 r w 94 ACTUATOR_ACTION Unsigned8 S 1 r w 95 TRAVEL_COUNT Unsigned16 N 2 r w...

Страница 37: ...IT values are exceeded the corresponding bit in the parameter CHECK_BACK is set TRAVEL_TIME_CLOSE_ OPEN Set point value for the time in seconds between the change of status from CLOSED to OPEN if 0 th...

Страница 38: ...n activated Short circuit detection not activated 2 Line break detection not activated Short circuit detection activated 3 Line break or short circuit detection not activated The standard parameter Vi...

Страница 39: ...0 LSB valve position DS 34 D 2 r w a cyc 26 OUT_D value bit 0 LSB valve position DS 34 D 2 r 28 READ_BACK_D cyclic possible DS 34 D 2 r a cyc 30 RCAS_IN_D cyclic possible value bit 0 LSB valve positi...

Страница 40: ...e position DS 34 D 2 r w a cyc 26 OUT_D value bit 0 LSB valve position DS 34 D 2 r a 28 READ_BACK_D cyclic possible DS 34 D 2 r a cyc 30 RCAS_IN_D cyclic possible value bit 0 LSB valve position DS 34...

Страница 41: ...e position DS 34 D 2 r w a cyc 26 OUT_D value bit 0 LSB valve position DS 34 D 2 r a 28 READ_BACK_D cyclic possible DS 34 D 2 r a cyc 30 RCAS_IN_D cyclic possible value bit 0 LSB valve position DS 34...

Страница 42: ...a 28 READ_BACK_D cyclic possible DS 34 D 2 r a cyc 30 RCAS_IN_D cyclic possible value bit 0 LSB valve position DS 34 D 2 r w a cyc 17 ST_REV Unsigned16 N 2 r w a 18 TAG_DESC OctedString S 32 r w a 19...

Страница 43: ...e RCAS status Remote Cascade Bit 0 in the value specifies the valve position The transferred status must be a good status e g 0x80 RCAS_OUT_D Process value of the valve position in the RCAS status Bit...

Страница 44: ...ta in the GSD file are indicated below The device operates with the GSD for 8643 as well as with the GSD for 8642 Module EMPTY 0x00 EndModule Module SP_D 0xA1 EndModule Module SP_D_READBACK_D 0xC1 0x8...

Страница 45: ...blow off at the deaeration connections Inadequate or no pressure supply Design the pressure supply with the largest possible volume even for upstream devices such as pressure controllers maintenance...

Страница 46: ...erfaces of the coil and the pneumatic connections from damage by placing protective caps on them 11 STORAGE NOTE Incorrect storage may damage the device Store the device in a dry and dust free locatio...

Страница 47: ......

Страница 48: ...www burkert com...

Отзывы: