29
Configuringthenetwork
The bits of the bit string are assigned to the following alarms:
Bit
Alarm
0
Discrete alarm (LSB)
1
HI_HI_Alarm
2
HI_Alarm
3
LO_LO_Alarm
4
LO_Alarm
5
reserved
6
reserved
7
Block Alarm (e.g. increase of St_Rev)
8-15
reserved
8.2.1.4. Parameter description of the physical block
Parameter
Parameter description
DEVICE_ID
Identification of the field device
DEVICE_MAN_ID
Identification code of the field device manufacturer (Bürkert = 120)
DEVICE_SER_NUM
Serial number of the manufacturer
DIANOSIS
Precise information on the device, coded bit by bit.
DIANOSIS_MASK
Definition of supported DIAGNOSIS information bits
0 = not supported
1 = supported
DIA_MEM_CHKSUM
Storage error
DIA_CONF_INVAL
Invalid configuration
DIA_WARMSTART
Warm start
DIA_COLDSTART
Cold start
HARDWARE_REVISION
Version number of the hardware for the field device
SOFTWARE_REVISION
Version number of the software for the field device
DIANOSIS_EXTENSION
Additional diagnosis for device manufacturer
DIANOSIS_MASK_
EXTENSION
Definition of supported information
FACTORY_RESET
1
Reset to standard values
2506
Warm start
2712
Reset the bus address, IDENT_NUMBER_SELECTOR is not reset
Parameter
Parameter description
DESCRIPTOR
User-definable text to describe the device within the application