46
Electrical installation
Type 8745 Ethernet, 8745 Analogue
Tab. 33:
Default assignment of the relay output of the D-sub DE-9 male
connector
product variant analogue
default assignment
MFM
No assignment
MFC
The set-point value cannot be
reached
→
To choose the events that are assigned to the relay output, use
the Bürkert Communicator software. To connect the product to
the Bürkert Communicator software, refer to chpt. 10.4
. Several
events can be associated to the digital input.
8.6
Wire a product variant Analogue
with 6 terminal connections
NOTICE
requirements for the proper function of the product.
▶
Use shielded cables only.
▶
Connect each cable end to the functional earth.
▶
Use a power supply with sufficient power.
▶
For an MFC pay attention to the maximum permissible resid
-
ual ripple on the operating voltage (residual ripple < 2 %).
NOTICE
risk of faulty operation of the product if the
GND signals are
bridged
on the product
.
▶
Individually connect the GND or earth connections of all the
signals to the product.
→
Loosen the screws of the removable terminal connections.
→
If your product is an MFM, wire the removable terminal con
-
nections according to the pin assignment in
Terminal connections
assignment
1
2
3
4
5
6
V+
V-
AI+
AI-
AO+
AO-
1
+24 V DC
2
GND for the power supply
3
Not used
4
Not used
5
Analogue output for the
measured value
6
GND for the analogue output
Fig. 27:
MFM Analogue: Pin assignment of the terminal connections
→
If your product is an MFC, wire the removable terminal con
-
nections according to the pin assignment in
Terminal connections
assignment
1
2
3
4
5
6
V+
V-
AI+
AI-
AO+
AO-
1
+24 V DC
2
GND for the power supply
3
Set-point input
4
GND for the set-point input
5
Analogue output for the
measured value
6
GND for the analogue output
Fig. 28: MFC Analogue: Pin assignment of the terminal connections