19
Adjustment
9.6.3
Out (Output)
– setting the output signal
In this parameter, define whether the device is to work as a flow transmitter or a pulse divider.
setting as flow transmitter
(4 - 20 mA)
:
When changing the unit (e.g. from liters to gallons) the limit values for the current output are not con-
verted automatically
→
Set the lower and upper limit values for the flow rate range associated to the 4-20 mA output, in the unit set
within the UNIT parameter.
The lower limit value is marked by an L (low) on the display and the upper limit value by an H (high).
setting as pulse divider
(Freq)
:
→
Set the volume, in the displayed unit, for each pulse emitted on the NPN and PNP outputs.
Setting in the parameter:
* Order of value input:
1. Select the decimal point place
(each time the key is pressed: one position to
the left)
2. Set numerical values
Status display changes to "active"
set the flow rate range *
set the volume pro pulse, in the displayed unit *
Lower limit value
Upper limit value
select
flow
transmitter
select
pulse divider
mA
l
L = low
H = high
Fig. 13 : Out – Setting the output; operation as flow transmitter or pulse divider
English
Type 8022