3010 - 7
englisch
Electrical
connections
ATTENTION!
The operating voltage and frequency of the electrical supply must
be the same as quoted on the rating plate of the drive.
The voltages and currants must not lie outside the permitted ope-
rating range.
For models with rated voltages of 220 V and 110 V, the regulations
for heavy current must be complied with.
Ensure the electrical earthing (PE) of the adapters and fitting th-
rough the piping installation.
The switching diagram for the connection of the rotary actuator is located inthe cover of the
drive. The electrical fusing is carried out on the network side. When using a stepper motor,
(Ident. = S), a pulsed control is required. The cable head insert can be rotated by 3 x 90°,
tightening torque 1 Nm.
NOTE
For rotary actuators with a.c. motors, every rotary drive must be
driven via its own switch or is own relay. If several drives are con-
nected in parallel via a common control switch or relay contact, fault
currents may occur that could lead to the destruction of the drive.
Circuit diagram for Type 3010
Standard model AC
Standard model DC
S2
right
(OPEN)
left
(OPEN)
left
(CLOSED)
right
(OPEN)
S1
L1
N
PE
1
2
3
1
2
3
S2
right
(OPEN)
left
(CLOSED)
left
(CLOSED)
right
(OPEN)
S1
+
-
PE
1
2
3
1
2
3
M