27
Installation
Auf
Zu
N
-
Ph
+
1
2
3
T/E
Auf
N
-
Ph
+
3
2
1
T/E
Fig. 16: Three points mode
Fig. 17: Open / Closed mode / Emergency current
model
If voltage is applied simultaneously to terminals 2 and 3, terminal 2 is the leading one and the actuator
moves to the OPEN position.
procedure:
Loosen left cable gland 15 (see Figs.
→
1 and 2) and feed through the cable to be connected.
Connect cable according to the required control type (see Figs.
→
16 and 17) to the terminal strip Pos. B of the
power supply card (see Figs. 14 and 15).
operating principle for open / Closed mode
:
Switch open = actuator closes
•
Switch closed = actuator opens
•
Connecting feedback
The limit switches for the feedback are suitable for a maximum voltage of 250 V AC/DC – 5 A.
The rotary actuator features two additional limit switch contacts which are supplied by the factory in an open position.
These can be used for the feedback of the rotary actuator.
2
3
1
FC2
FC1
FCF
FC0
4-6
5
7
=
C
C
A
B
D
D
T/E
Motor
Feedback
Power supply and control
Fig. 18: Internal wiring of actuator
English
Type 3004
Содержание 3004
Страница 19: ...19 Technical Data Motor 100 300 Nm Dimensions Type 3004 at torque 100 300 Nm Fig 6 English Type 3004 ...
Страница 42: ...42 English Type 3004 ...
Страница 59: ...59 Technische Daten Motor 100 300 Nm Abmessungen Typ 3004 mit Drehmoment 100 300 Nm Bild 6 deutsch Typ 3004 ...
Страница 82: ...82 deutsch Typ 3004 ...
Страница 122: ...122 français Type 3004 ...
Страница 124: ...124 Certificat d essai de modèle Ce Baumusterprüfbescheinigung Type 3004 deutsch français ...
Страница 125: ...125 Type 3004 deutsch français ...
Страница 126: ...126 Certificat d essai de modèle Ce EC Design Text Certificate english Type 3004 français ...
Страница 127: ...127 english Type 3004 français ...
Страница 128: ...128 english Type 3004 deutsch français ...
Страница 129: ......
Страница 130: ...www burkert com ...