37
büS/CANopen-Design
6.13.4 Central configuration management (Configuration client)
As of firmware B.01.00.00 the central configuration management (e.g. with gateway ME43, as of firmware A.03.02)
is supported. This means that defective Bürkert devices can be exchanged easily, almost without configuration effort.
To do this, the configuration management for the configuration provider (gateway) in the Bürkert Communicator must
be set to “Active”
and
the “
Configuration client
” parameter for the configuration device (control head) must be set
to mode “Automatically switch on” (= factory setting) or “Active” (Bürkert Communicator: Control Head / General
settings / Parameters / Configuration client / Mode).
Via a memory card in the ME43 gateway, the last stored device parameters and configurations are retained and can
be transferred to the new Bürkert device.
When replacing a defective control head, however, the
hardware settings (all DIP switches)
must be set on the
new device
before
connecting to the network, as they have been set on the device which is to be replaced. In this
way, all relevant software parameters (during the communication process lasting several minutes to integrate the
new control head into the network) can be transferred automatically. The new device must then be taught-in.
Details and operating conditions are described in the software manual “Central configuration management of
Bürkert devices” (see chapter “5.6”).
For this configuration the Bürkert Communicator version 4.x or higher is required.
(During a device reset / factory reset of the configuration device (control head, as of firmware B.01.00.00), the
“configuration client”
parameter mode is reset to the factory setting “Automatically switch on”.)
6.14 Changing the gateway IP address
Each gateway requires a unique IP address to distinguish several gateways from each other.
If required, the gateway IP address can be changed directly at the gateway itself using its menu and arrow keys or
in four other ways:
using
web server
Bürkert Communicator
(“6.14.2”) or
Logix Designer
LogixDesigner manual for this) or
RS Linx
.
After changing the gateway IP address, register and install the gateway using Logix Designer (“6.15”) (see
“6.16”).
The gateway must always be connected to the same network as the PC!
6.14.1 Changing the gateway IP address using web server
→
Call the gateway’s web server with a
browser (enter only the current IP address
number:
“http://192.168.1.100”
)
(the window which opens for this IP
address shows the default
“Static IP address” of all gateways ME43
(factory setting):
192.168.1.100
)
→