Introduction 

The  BTU‐4  Burk  Temperature  unit  supports  up  to  four  independent 

temperature  sensors,  and  provides  a  low  voltage  output  that  tracks 
linearly with the AC line voltage.  

Each  temperature  output  supplies  10mV  per  degree  Fahrenheit  or 
Centigrade, based on the type of sensor installed.  

The BTU‐4 is supplied with: 

 

 

One AC power adapter  

 

One BTO Fahrenheit temperature sensor  

 

One 6‐terminal plug for connection to monitoring equipment 

 

 

Sensors  

BTO 

 Outdoor Sensor  

The  BTO  is  included  with  the  BTU‐4  system,  and 

is  intended  for  general  purpose 

monitoring of equipment or ambient temperatures.  

The BTO is attached to 15’ of shielded cable with a stereo phone type connector. 

 

The sensor has a mounting ring and gasket to accommodate #6 or #8 hardware. The 

sensing elements are sealed for added protection from dirt and moisture. 

BTI 

 Indoor Sensor  

The  BTI  is  tailored  for  monitoring  ambient  temperatures  within  a  room,  while 
maintaining a polished appearance.  

The BTI is ho

used in a 2 5/8” x 5” enclosure with air vents to facilitate sensing of the 

environment.  

15’ of shielded cable is provided with a stereo phone type connector on one end. The BTI has a large, easy 

to connect barrier strip that accommodates flat or Phillips type screwdrivers.

  

BTS 

 Stack Sensor  

The BTS is designed for sensing heat within the air ducting of your equipment.  

The BTS is attached to 15’ of shielded cable with a stereo phone type connector.

 

 

The sensor is mounted in the tip of a 3/8” diameter chrome tube. The supplied 

mounting hardware consists of a base and a compression fitting to allow the sensor to 
be secured at variable depths. This allows the installer to locate the sensor up to 9 1/2

” 

from the equipment wall, well within the airflow being monitored. 

Содержание BTU-4

Страница 1: ...BTU 4 Sensors Installation and Operation Manual ...

Страница 2: ...llation 2 BTU 4 Burk Temperature Unit 2 BTO Outdoor Sensor 2 BTI Indoor Sensor 3 BTS Stack Sensor 3 Remote Control Setup 4 ARC Plus 4 ARC Solo 4 ARC 16 4 GSC3000 VRC2500 4 Specifications 5 Dimensions 5 Power 5 Inputs 5 Outputs 5 Sensor Temperature 5 Cable Length 5 BTO Outdoor Sensor 5 BTI Indoor Sensor 5 BTS Stack Sensor 5 Getting Help 6 Warranty 6 ...

Страница 3: ...ardware The sensing elements are sealed for added protection from dirt and moisture BTI Indoor Sensor The BTI is tailored for monitoring ambient temperatures within a room while maintaining a polished appearance The BTI is housed in a 2 5 8 x 5 enclosure with air vents to facilitate sensing of the environment 15 of shielded cable is provided with a stereo phone type connector on one end The BTI ha...

Страница 4: ...perature sensor 3 4 Sample from temperature sensor 4 5 Sample from AC line monitor 6 Ground connection for all samples The BTU 4 is powered by an external AC power adapter The supplied adapter accepts 120VAC input and provides 12VAC to the power input jack of the BTU 4 BTO Outdoor Sensor 1 Attach the ring of the BTO with the supplied 6 sheet metal screw or use any existing post hook or machine scr...

Страница 5: ...e AC adapter from the BTU 4 11 Plug the connector of the BTI into one of the four available input jacks on the BTU 4 12 Connect the output sample pin associated with the appropriate input jack from the BTU 4 to the remote control equipment 13 Plug the AC adapter into the BTU 4 BTS Stack Sensor 1 Select a location on the equipment ducting that is flat and able to support the weight of the BTS and i...

Страница 6: ...e The meter type must be set to MV pre 5 x firmware of DEG 5 x or later firmware Configure the ARC 16 to show the decimal point one digit to the left if true input valve 700 MV DEG displayed value 70 0 MV DEG No calibration is necessary Please refer to your ARC 16 manual for detailed instructions on moving the decimal point display location GSC3000 VRC2500 Note The meter type should be set to 5 to...

Страница 7: ...erminal plug providing four temperature samples and one AC line sample Sensor Temperature LM34 Fahrenheit maximum temperature 300oF LM35 Celsius maximum temperature 149oC Cable Length Maximum recommended cable length is 50 BTO Outdoor Sensor 15 shielded 1 4 phono cable Mount with 6 or 8 hardware BTI Indoor Sensor 2 5 8 x 5 enclosure BTS Stack Sensor 15 shielded 1 4 phono cable 3 8 chrome tube Moun...

Страница 8: ...ire or flood or harsh environment is not to be covered by this warranty Damage in shipping is not the responsibility of Burk Technology A return authorization must be obtained before returning any equipment Materials returned under this warranty must be shipped freight prepaid and insured in the original shipping carton or suitable substitute to Burk Technology Inc 7 Beaver Brook Road Littleton MA...

Отзывы: