BCM-MS, BCM-LS
4.2.2.6 "CANopen Object Dictionary" Details
The following tables show the full object directory for the sensor. The first table shows the communication portion of the object
directory. Apart from a few exceptions, these settings correspond to the CANopen standard as described in DS 301. There are
some communication limitations based on the hardware platform used. The configuration steps for "heartbeat time" (Index
1017h), "TPDO1 event timer" (Index 1800h, Subindex 5), "TPDO2 event timer" (Index 1801h, Subindex 5), "TPDO3 event timer" (In-
dex 1802h, Subindex 5) are limited to 50 ms in place of the 1 ms envisaged. This means that these objects can be configured to
0 ms, 50 ms, 250 ms, but not 35 ms, 125 ms, etc.
Communication Profile Area
ldx (hex) Sub Name
Type
Attr. Default
Notes
1000
0
Device type
U32
ro
194h
Sensor, see DS 404
1001
0
Error register
U8
ro
00h
mandatory, see DS 301
100A
0
Manufacturer Software Ver-
sion
string ro
depends current firm-
ware
e.g.: "1.01"
1017
0
Producer heartbeat time
U16
rw
3E8h
heartbeat time in ms, granularity of
50ms (instead of 1ms, e.g. can be set to
0, 50, 150, but not to 20)
range: 0..10000
1018
identity object
record ro
0
Number of entries
U8
ro
04h
largest sub index
1
Vendor ID
U32
ro
000000E6h
2
Product code
U32
ro
Device dependant
3
Revision number
U32
ro
Device dependant
4
Serial number
U32
ro
Device dependant
lower 3 bytes contain the serial number,
the top byte is reserved for future use
1800
Transmit PDOs Parameter
record
0
Number of entries
U8
ro
05h
largest sub index
1
COB-ID
U32
rw
180h + NodeID
COB-ID used by PDO, range: 181h..1FFh,
can be changed while not operational
2
Transmission type
U8
rw
FFh
synchronous, asynchronous
values: 1-240, 254, 255
5
Event timer
U16
rw
1388h
event timer in ms for asynchronous
TPDO1, value has to be a multiple of 50
and max 12700
1801
Transmit PDO2 Parameter
record
0
Number on entries
U8
ro
05h
largest sub index
1
COB-ID
U32
rw
280h + NodeID
COB-ID used by PDO, range: 281h..2FFh,
can be changed while not operational
2
Transmission type
U8
re
FFh
synchronous, asynchronous
values: 1-240, 254, 255
5
Event timer
U16
rw
1388h
event timer in ms for asynchronous
TPDO2, value has to be a multiple of 50
and max 12700
1802
Transmit PDO3 Parameter
record
0
Number on entries
U8
ro
05h
largest sub index
1
COB-ID
U32
ro
380h + NodeID
COB-ID used by PDO, cannot be changed
2
Transmission type
U8
ro
Copy of TPDO2 Transmis-
sion Type
synchronous, asynchronous,
copy TPDO2 Transmission Type
5
Event timer
U16
ro
copy of TPDO2 event
timer
event timer in ms for asynchronous
TPDO3, copy of TPDO2 event timer
1803
Transmit PDO4 Parameter
record
only for level sensors
0
Number of entries
U8
ro
05h
largest sub index
1
COB-ID
U32
ro
480h + NodeID
COB-ID used by PDO, cannot be changed
2
Transmission type
U8
ro
Copy of TPDO2 Transmis-
sion Type
synchronous, asynchronous,
copy TPDO2 Transmission Type
31