2
Product information
SM290/2 5 | SM300/5 | SM400/5 | SM290/5E | SM400/5E – 6 720 800 023 (2013/01)
30
2.4
Specification
Unit
SM290/5(E)
SM300/5
SM400/5(E)
General data
Dimensions
Height when tilted
mm
1945
1655
1965
Minimum room height for anode replacement
mm
2000
1850
2100
Connections
Connection size, DHW
DN
R1"
R1"
R1"
Connection size, cold water
DN
R1"
R1"
R1"
Connection size, DHW circulation
DN
R¾ "
R¾ "
R¾ "
Internal diameter, test port, solar cylinder temperature sensor
mm
19
19
19
Internal diameter, test port, cylinder temperature sensor
mm
19
19
19
Weight (dry, excl. packaging)
kg
115
118
135
Total weight when filled
kg
405
408
515
Cylinder capacity
Available capacity (total)
l
290
290
380
Available capacity (excl. solar heating)
l
120
125
155
Available amount of DHW
1)
DHW outlet temperature
2)
:
1) Without solar heating or reheating; selected cylinder temperature 60 °C
2) Mixed water at the draw-off point (at 10 °C cold water temperature)
45 °C
l
171
179
221
40 °C
l
200
208
258
Standby heat loss to DIN 4753 part 8
3)
3) Distribution losses outside the buffer cylinder are not taken into account.
kWh/24h
2.1
2
2.2
Maximum throughput, cold water inlet
l/min
29
29
38
Maximum DHW temperature
°C
95
95
95
Max. operating pressure, DHW
bar (positive)
10
10
10
Highest design pressure (cold water)
bar (positive)
7.8
7.8
7.8
Maximum DHW test pressure
bar (positive)
10
10
10
Upper indirect coil
Contents
l
5.7
6.2
7.0
Surface area
m
2
0.84
0.9
1
Performance factor N
L
to DIN 4708
4)
4) The performance factor NL=1 to DIN 4708 for 3.5 occupants, standard bath tub and kitchen sink. Temperatures: cylinder 60 °C, outlet 45 °C and cold water 10 °C. Measured
at max. heat input. The N
L
drops with reduced heat input.
NL
1.8
2
3
Continuous output (at 80 °C flow temperature, 45 °C DHW outlet temperature and 10 °C cold
water temperature)
kW
l/min
23
9.4
28.5
11.7
36
14.7
Heat-up time at rated output
min
16
18
18
Maximum heat input
5)
5) Limit to the stated value for heat sources with higher heat input.
kW
31.5
28.5
36
Maximum heating water temperature
°C
160
160
160
Max. heating water operating pressure
bar (positive)
16
16
16
Connection size, heating water
DN
R1"
R1"
R1"
Pressure loss diagram
Lower indirect coil
Contents
l
5.8
8.8
12.1
Surface area
m
2
1.3
1.3
1.8
Maximum heating water temperature
°C
160
160
160
Max. heating water operating pressure
bar (positive)
16
16
16
Connection size, solar
DN
R1"
R1"
R1"
Pressure loss diagram
Table 32 Dimensions and specification (
Fig. 1, page 110 and Fig. 3, page 111)