background image

Bulletin Number: TBG-21 | Logamatic R2107 Quick Start Guide

Technical service bulletin

Data subject to change without notice | BTC 463002101 A | 08.2010

Buderus 

 
 

Bosch Thermotechnology Corp.

50 Wentworth Ave

Londonderry, NH 03053

Tel:

  (603) 552-1100

Fax:

 (603) 584-1681

www.buderus.us

 

REF TEMP

 – Will change according to system design. Program to 

the following:

1.  Baseboard – 160 °F

2.  Hydro-Air – 128 °F

3.  Panel Rads – 155 °F

4.  Cast Iron Rads – 150 °F

•  To change REF TEMP:

 While on the 

REF TEMP

 setting, hold 

 and turn 

dial 

 to proper design temperature

REMOTE 1

 - default is OFF, but must be changed to ON when 

using BFU.

•  To change REMOTE 1:

 While on the 

REMOTE 1

 setting, hold 

 and turn 

dial 

 to select ON.

ROOM COMP

 – you only get this setting when you turn on BFU 

and this must be set to 18.

•  To change ROOM COMP:

 While on the 

ROOM COMP

 setting, hold 

 and turn 

dial 

 clockwise to select 18.

OASETBACK

 – This must always be changed! Change to 

  SETBACK when using standard themostats 

(no BFU) and RMSETBACK if using BFU room 

sensor.

•  To change OASETBACK:

 While on the 

OASETBACK

 setting, hold 

 and turn 

dial 

 to select proper setting.

OFFSET

 – Will change according to system design. Program for 

the following:

1.  Baseboard, Panel Rads, and Cast Iron Rads – 0 

(default)

2.  Hydro-Air – Must be changed to 9

3. 

•  To change OFFSET:

 While on the 

OFFSET

 setting, hold 

 and turn 

dial 

 clockwise until 9 is selected.

Use the following under 

CIRCUIT 2

:

REF TEMP

 – Rule of thumb: set 

REF TEMP

 10 °F lower than 

design water temp

Examples: 

1.  Staple up (No Plates) 135 °F

2.  Below sub-floor w/ plates 125 °F

3.  Quick-track (or equal) 115 °F

4.  Slab (nothing over) 90 °F

** All other settings under 

CIRCUIT 2

 will follow same rules as 

CIRCUIT 1

.

Additional Rules

1. Never use a BFU with a hydro-air

2. If you are using the hydro-air settings above and circuit 2 for 

radiant, you must adjust circuit 2 temp down. Raising the day 
temp setting to 86 will also have an effect on circuit 2.

3. All settings listed above are starting points only – the heating 

curve may need to be adjusted further after the system is up 
and running. It is always best to start the curve low and work up 
from there.

Отзывы: