Reset
11
25
Reset
1. Press and hold down the Time, Insert and
Cancel buttons simultaneously until “RESET”
appears in the display.
2. Keep all three buttons depressed until all
characters have disappeared from the display.
This resets all key settings back to the factory
settings, language to “AMERICAN”, and unit
of temperature to Fahrenheit.
The heating program, time and day of the week
remain the same.
RESET
88 88
88 8
I N S
O
24
The Ecomatic HS 2102 reports the following service messages as part of its self-diagnostic capability.
Message (ERR)
Meaning
Action
BURNER
Burner lock-out
Check burner and press burner reset.
BOIL SENS
Defective FK sensor
Check resistance of FK sensor and
verify with curve.
OA SENSOR
Defective outside air sensor
Check resistance of OA sensor and
verify with curve.
DHW SENS
Defective DHW sensor
Check resistance of BF sensor and
verify with curve.
HEATING
Heating system stays cold.
Turn control OFF/ON.
Continued pump logic operation.
Check boiler operation.
DHW
DHW stays cold for 2 hours.
Check tank pump operation.
BFC
BFC does not respond
Check wiring to BFC.
INTERNAL
Internal error
Turn control OFF/ON. Electronic
module may need to be replaced.
Contact Buderus Hydronic Systems.
These messages are very helpful in troubleshooting the Ecomatic HS 2102. Consult the sensor curves
to verify proper sensor operation. In case of sensor failure, the HS 2102 continues burner and circulator
operation to prevent possible freeze-up of the heating system.