15
Boiler inspection and maintenance
Logano GC 144 II – 6 720 808 893 (2017/02)
21
Fig. 30 Gas valve
[1]
ON/OFF knob (shown in ON position)
15.5
Cleaning the boiler
The boiler can be cleaned with brushes and/or by wet cleaning. Cleaning
tools are available as accessories.
Inspecting the ignition burner
▶ Observe the ignition burner through the sight glas window
(
Fig. 31 GC 144 II
[1]
Sight glass
▶ The flame must rise over the sensor by ½" to 1-½".
▶ The pilot ignition gas pressure must be adjusted if the flame is too
small or too large.
Fig. 32 Correct ignition flame setting
[1]
Flame rises ½" to 1-½" above sensor
[2]
Ignition flame
▶ Remove the safety screw on the adjustment screw for the igniter
(
figure 24, page 17).Turn the inner adjustment screw clockwise
to reduce the size of the ignition flame, and counterclockwise to
increase it.
▶ After completed adjustment replace the safety screw
(
▶ If the flame is too small, the pilot orifice needs cleaning
(
figure 39, page 23). If the igniter flame is acceptable, start
cleaning.
Fig. 33 Gas valve
[1]
Safety screw on igniter adjustment screw
The adjustment screw is located behind a safety screw
on the gas valve (
1
6 720
8
04 440-3
8
.1T
1
6 720
8
04 440-39.1T
Be careful not to damage the pilot orifice during
installation and cleaning.
2
1
6 720
8
04 440-40.1T
1
6 720
8
04 440-41.1T
Содержание GC144/3