3
Regulations
Logalux – 6721814238 (2020/03)
42
2.5
Technical Data
Table 50 Technical Data
2.6
Product data for energy consumption
The following product data satisfy the requirements of the EU
Regulations No. 811/2013 and No. 812/2013 supplementing EU
Regulation 2017/1369.
Manufacturers who implement these guidelines and state the ErP values
are permitted to use the "CE" mark.
Table 51 Product data for energy consumption
3
Regulations
Observe the following guidelines and standards:
• Local regulations
•
EnEG (Building Regulations)
(in Germany)
•
EnEV
(in Germany)
Installation of, and equipment for, heating and water heating systems:
•
DIN
and
EN
standards
–
DIN 4753-1
– Water heaters ...; requirements, identification,
equipment and testing
–
DIN 4753-3
– Water heaters ...; corrosion protection on the
water side with glass lining; requirements and testing
(product standard)
–
DIN 4753-7
– Water heaters, containers with a volume up to
1000 l, manufacturing, thermal insulation and corrosion
protection requirements
–
DIN EN 12897
– Water supply - regulation for ... DHW cylinders
(product standard)
–
DIN 1988-100
– Technical rules for potable water installations
–
DIN EN 1717
– Protection of potable water against pollution ...
–
DIN EN 806-5
– Technical rules for potable water installations
–
DIN 4708
– Central water heating systems
–
EN 12975
– Thermal solar systems and their components
(collectors)
•
DVGW
– Code of Practise W 551 – domestic hot water heating systems
and pipework; technical measures to inhibit the growth of
legionella bacteria in new systems; ...
– Code of Practise W 553 – Sizing DHW circulation systems ...
Product data for energy consumption
•
EU Regulation
and
Directives
–
EU Regulation 2017/1369
–
EU Regulation 811/2013
and
812/2013
Unit
SM400.5 E
Dimensions and specifications
-
page 56
Pressure drop diagram
-
page 57
General description
Tilt height
mm
1955
Minimum room height for anode replacement
mm
2100
Connection size, DHW
DN
R1"
Connection size, cold water
DN
R1"
Connection size, circulation
DN
R¾ "
Inside diameter of test point, solar cylinder
temperature sensor
mm
19.5
Inner diameter, test point, cylinder
temperature sensor
mm
19.5
Inside diameter of handhole cover
mm
120
Cylinder capacity
Useful capacity (overall)
l
367
Useful capacity (excl. solar thermal heating)
l
155
Usable DHW volume
1)
with DHW outlet
temperature
2)
:
45 °C
l
221
40 °C
l
258
Standby heat loss (24 h) in accordance with
DIN 4753 Part 8
3)
kWh/
24 h
1.8
Maximum flow rate at cold water inlet
l/min
37
Maximum DHW temperature
°C
95
Maximum operating pressure, potable water
bar
(positive)
10
Maximum DHW test pressure
bar
(positive)
10
Upper heat exchanger
Content
l
6.9
Surface area
m
2
1
Rating code N
L
according to DIN 4708
4)
N
L
2.8
Continuous output (at 80 °C flow
temperature, 45 °C DHW outlet temperature
and 10 °C cold water temperature)
kW
l/min
27
11.1
Heating water volumetric flow rate
l/h
2600
Heat-up time at rated output
min
34
Maximum heat input
5)
KW
27
Maximum heating water temperature
°C
160
Maximum operating pressure of heating water
bar
(positive)
16
Connection size, heating water
DN
R1”
Lower heat exchanger
Content
l
12.0
Surface area
m
2
1.8
Maximum heating water temperature
°C
160
Maximum operating pressure of heating water
bar
(positive)
16
Connection size, solar
DN
R1”
1) Without solar thermal heating or recharging; set cylinder temperature 60 °C.
2) Mixed water at draw-off point (at 10 °C cold water temperature).
3) Distribution losses outside the DHW cylinder are not taken into account.
4) The rating code N
L
=1 according to DIN 4708 for 3.5 persons, standard bath tub
and kitchen sink. Temperatures: cylinder 60 °C, DHW outlet temperature 45 °C
and cold water 10 °C. Measured at max. heat output. If the heat output is
reduced, N
L
becomes smaller.
5) In the case of heat sources with a higher heat output, limit to the stated value.
Product
number
Product
type
Cylinder
volume (V)
Heat
retention
loss (S)
Energy
efficiency class
for DHW
treatment
8732929427 SM400.5 E
S-B
367,0 l
73,8 W
B
Unit
SM400.5 E
Содержание 8732929427
Страница 15: ...6 Logalux 6721814238 2020 03 15 6 6 1 10 bar 6 2 6 2 60 C 17 17 7 19 20 61 21 62 22 62 8 Bosch Bosch...
Страница 55: ...Logalux 6721814238 2020 03 55 1 1 10 11 12 13 14 15 16 17 4 7 8 9 2 3 5 6 0010032800 001...
Страница 58: ...Logalux 6721814238 2020 03 58 7 8 0010032870 001 0010032872 001 9 10 0010032874 001 1 2 0010002859 001 1 2 3...
Страница 59: ...Logalux 6721814238 2020 03 59 11 12 0010032883 001 0010032881 001 13...
Страница 62: ...Logalux 6721814238 2020 03 62 21 22 1 2 1 2 0010032890 001 0010032892 001 23 24...
Страница 63: ...Logalux 6721814238 2020 03 63 25 26 27 28 0010032894 001 1 2 3...
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ...Bosch Thermotechnik GmbH Sophienstrasse 30 32 D 35576 Wetzlar www bosch thermotechnology com...