2
Product information
P120.5 | P200.5 | P300.5 – 6 720 819 267 (2018/08)
23
2
Product information
2.1
Correct use
Buffer cylinders may only be filled with heating water.
Only use buffer cylinders in sealed heating systems.
Operate the buffer cylinders P120.5, P200.5, P300.5 preferably in
combination with heat pumps.
Any other use is considered incorrect. Any damage that may result is
excluded from liability.
2.2
Scope of Delivery
• Buffer cylinder
• Installation and servicing instructions
2.3
Technical data
• Dimensions and specifications (
2.4
Product description
2.5
Data plate
The data plate is located at the top of the rear of the buffer cylinder and
includes the following details:
2.6
Product datasheet on energy consumption
The following product data complies with the requirements of EU Regulations 811/2013 and 812/2013 as supplement to the Directive 2010/30/EU.
Unit
P120.5
A
P200.5
A
Available capacity (total)
l
120
203
Standby heat loss
1)
1) EN 12897; Excluding distribution losses outside the buffer cylinder.
kWh/24h
0,8
1,03
Maximum heating water
temperature
°C
90
90
Maximum heating water operating
pressure
bar
(positive)
3
3
Table 2 Technical data (A)
Unit
P120.5
B
P200.5
B
P300.5
B
Available capacity (total)
l
120
203
300
Standby heat loss
1)
1) EN 12897; Excluding distribution losses outside the buffer cylinder.
kWh/24h
1,3
1,4
1,94
Maximum heating water
temperature
°C
90
90
90
Maximum heating water
operating pressure
bar
(positive)
3
3
3
Table 3 Technical data (B)
Item
Description
1
Heating system flow
2
Casing, painted sheet metal with rigid polyurethane foam
insulation
3
Heating system return
4
Return to heat pump
5
Sensor well for return temperature sensor (GT1)
(Test point)
6
Drain tap
7
Storage cylinder, steel
8
Flow from heat pump
9
Plug with sensor well for flow temperature sensor (T1)
10
Air vent valve
11
PS casing lid
Table 4 Product description (
Item
Description
1
Type
2
Serial number
3
Available capacity (total)
4
Standby heat loss
6
Year of manufacture
9
Max. heating water flow temperature
17
Max. heating water operating pressure
Table 5 Data plate
Product number
Product typ
Storage volume (V)
Standing loss (S)
Water heating energy efficiency class
8 732 910 192
P120.5 S
120,0 l
35,2 W
A
7 735 500 667
8 718 542 920
P120.5
P120/5W
120,0 l
52,0 W
B
8 732 910 194
P200.5 S
203,0 l
42,7 W
A
7 735 500 668
8 718 543 041
P200.5
P200/5W
203,0 l
56,6 W
B
7 735 500 684
8 718 542 847
P300.5
P300/5W
300,0 l
59,0 W
B
Table 6 Product datasheet on energy consumption