Operating Instructions
3
Operating instructions for Buderus 600 - 11R / 19R / 24R • Edition 08/2003
Boulter Buderus Ltd. • http://www.boulter-boilers.com
Subject to modifications resulting from technical improvements!
5
Electricity supply
This boiler must be earthed.
A mains supply of 230 V - 50Hz is required.
Connection must be made in a way that allows complete
isolation of the electrical supply such as a double pole
switch, having a 3 mm 1/8") contact seperation in both
poles, serving only the boiler and system controls.
Alternatively, a 3-pin unswitched socket may be used.
The means of isolation must be accessible to the user
after installation.
6
Functions of the system and operating
instructions
The installer should familiarize the user with the
functions and operation of the heating system and
ensure that a complete set of technical documentation is
supplied.
7
Maintenance
The appliance should be serviced at least once a year
by a CORGI registered installer.
8
Cleaning
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains, wipe with a damp
cloth and finish off with a dry cloth.
DO NOT use abrasive cleaning materials.
9
Initial start-up
9.1
Operation of the boiler
9.1.1 Access to the control unit
z
Press the window to open the access panel of the
control unit see fig 1.
Fig. 1
Open the window of control unit
9.1.2 Lighting and shutting down the boiler.
z
Press the mains switch (see fig 2, item 1) on the
control unit to "
I
" to light the boiler.
z
Press the mains switch to "
0
" to shut down the boiler.
9.1.3 Frost hazard
In the event of any risk of the heating system freezing
up, you must keep the pump switched on.
Fig. 2
Control panel
9.1.4 Temperature-setting adjustments
z
Set flow temperature at the control unit (fig. 2, item 2)
(see table 1).
z
Adjust room temperature to maximum setting at the
control unit.
z
Push the mains power switch (fig. 2, item 1) to “
I
”.
The boiler runs through the start-up programme and
the burner is ignited after approx. 30 seconds.
z
Adjust room temperature to desired setting at the
control unit.
I
NOTE
Knob pos. 3 in fig. 2 is used for service purposes
only.
*
Basic setting: Have the specific system settings of the Buderus control system and burner-control unit control panel adjusted by
a specialist heating system company.
Table 1
Flow temperature
I
0
1
10
1
10
2
1
3
Control unit
Range of application
Controller position / boiler flow temperature
230 V temperature
controller
Floor heating
Radiator heating
1
3
(48 °C, max. factory-adjusted setting for floor heating)
1
7
(67 °C, min. factory-adjusted setting for radiator heating)
ON/OFF temperature
controller, 24 V
Radiator heating
1
5
(58 °C, new building) up to
10
(80 °C, old building)*