Technical data
Rated data of the devices for HV on−board supply system 800 V
DC/AC inverter
>
29
300−I−9052003−EN−04/07.2021
4.2.2
DC/AC inverter
DC/AC inverter
7.5 kW
11 kW
15 kW
22 kW
30 kW
60 kW
Input voltage − HV on−board supply system
Rated voltage
V DC
800
Voltage range
V DC
100...848
Output voltage
3 AC 0V...510V
Output frequency f
out
Hz
−599...+599
Switch−off at short−circuit current
A
peak
24
36.1
48.1
72.1
96.2
192.3
Efficiency
typical
%
98.5
Valid for operating point
DC 600 V, AC 400 V, 58 A, 8 kHz, 40 kW, cos phi 1.0
Continuous operation
Current consumption − HV
on−board supply system
A
9.8
13.5
18.4
26.3
39.2
71
Output power
kW
5
7.3
10
14.7
20
40
Output current at
f
out
<5Hz
2 kHz,
permanent
A
8
11
15
21.5
32
58
4 kHz,
permanent
A
6.4
8.8
12
17.2
25.6
46.4
8 kHz,
permanent
A
4.8
6.6
9
12.9
19.2
34.8
16 kHz,
permanent
A
2.4
3.3
4.5
6.5
9.6
17.4
4 kHz auto
A
8
11
15
21.5
32
58
8 kHz auto
A
7.2
9.9
13.5
19.4
28.8
52.2
16 kHz auto
A
4.4
6.1
8.3
11.8
17.6
31.9
Output current at
f
out
>5Hz
2 kHz,
permanent
A
12.8
17.6
24
34.4
51.2
72.5*
4 kHz,
permanent
A
10
13.8
18.8
26.9
40
72.5*
8 kHz,
permanent
A
7.2
9.9
13.5
19.4
28.8
52.2
16 kHz,
permanent
A
4
5.5
7.5
10.8
16
29
4 kHz auto
A
10
13.8
18.8
26.9
40
72.5*
8 kHz auto
A
8
11
15
21.5
32
58
16 kHz auto
A
4.8
6.6
9
12.9
19.2
34.8
Output current for "socket" application (VAC)
f
out
<10Hz, VAC
16 kHz,
permanent
A
2.8
3.9
5.3
7.5
10.6
18.6
f
out
>10Hz, VAC
16 kHz,
permanent
A
5
6.9
9.5
13.5
18.9
34.2
*
From MOBILE firmware version 6.3:
Derating to min. 58 A if the coolant and ambient temperatures are above 60 °C (DCU) or 55 °C (PSU) for more than
60 minutes.