Technical data
General data and operating conditions
4
>
23
300−I−9052003−EN−04/07.2021
4
Technical data
4.1
General data and operating conditions
Conformity and approval
Approval
ECE
R10 Rev. 5
ß
10R − 05 7105
(see nameplate)
MOBILE DCU
MOBILE PSU
MOBILE DCU PSU
ß
10R − 05 8467
(see nameplate)
MOBILE DCU S
Protection of persons and device protection
Degree of protection
ISO 20653
IP 6K9K
l
Plug mounted
l
Cover sheet mounted
IP 6K7
l
Plug mounted
l
Without cover sheet
Insulation test
EN 61800−5−1
Final test with 2.6kVDC between HV on−board supply
system/LV on−board supply system and HV on−board supply
system/PE
Insulation of control
circuits
EN 61800−5−1
IEC 60664−1
Safe isolation by double/reinforced insulation to the HV
on−board supply system
Short−circuit strength
l
Motor connection: When connecting a 3−phase electric
motor, the DCU motor output is short−circuit proof. The
controller is locked, error acknowledgement is required.
l
Control terminal: permanently short−circuit−proof
Protective measures
against
l
Short circuit
l
Overvoltage
l
Motor Connection Test
l
Device overtemperature
l
Motor overtemperature
(PTC or thermal contact, I
2
t monitoring)
Leakage current
EN 61800−5−1
I
AC
>3.5 mA
I
DC
>10 mA
Observe regulations and safety
instructions!
On/off switching
MOBILE devices are suitable for frequent on/off switching,
e.g. in the setting−up operation.