80
Confirming settings by means of the
button, the following screen appears:
Time delay
Normally open
Normally closed
In particular, it’s possible to select the following time delays:
- 0 (instantaneous changeover)
- ∞ (uninterrupted changeover)
- 1-2-3-5-10-20-30s-1-2-5-10-20-30min (time delay changeover)
Pushing cancel button
all changes done about contact mode and delay won’t be
saved.
On the contrary, pushing the confirmation button
all settings will be applied.
By pushing for about 5 seconds the “test”
button, it’s possible to check the correct
operation of the contact making a changeover test (from normally open to closed or from
normally closed to open).
By pushing for about 5 seconds the “reset”
, it’s possible to reset the contact status
at steady state (function normally used for long delays).