2
ST-00000220-
24/04/2019
K4659
EN
Settings
Sensor parameters
Default value
Adjustable parameters
Configuration remote control
BMSO4001
BMSO4003
Time delay
15 mn
3,5,10,15,20 mn
−
30s - 255 h 59 mn 59s
−
Sensitivity
PIR (very high)
Low, medium, high, very high
Brightness threshold
300 lux
20, 100, 300, 500, 1000 lux
−
0 - 1275 lux
−
Oper
ating
mode
Auto
Not active
ON/OFF
Walkthrough
ON
ON/OFF
Eco
Not active
ON/OFF
Det
ec
tion
mode
Initial
PIR
Cannot be modified
−
Holding
PIR
Cannot be modified
−
Retrigger
PIR
PIR/OFF
−
Alarm
Not active
ON/OFF
−
Adv
anc
ed
mode
Calibration
−
0 - 99995 lux
−
Adjustment
Not active
ON/OFF
−
Contribution of light
Automatic
Automatic - 1275 lux
−
Time delay
The period of time after which the load is switched off if no movement is detected.
The time restarts whenever the sensor detects a movement.
Sensitivity
Adjustment of the sensitivity of the detection technology used.
Brightness threshold
Lighting level below which the sensor activates the load and above which it
switches it off.
Operating mode:
Auto
The load is automatically switched on:
- upon detection of a movement if the level of natural light is insufficient.
The load is automatically switched off:
- if no movement is detected at the end of the set time delay + standby time.
- or if the level of natural light is insufficient (adjustment on).
Each new detection causes automatic switching on if the light is insufficient.
Walkthrough
If a movement is detected for a time of less than 20 s, the sensor will decrease
the set time delay to 3 minutes. If the set delay time set is already less than three
minutes, it will remain as such.
Eco
The load is switched on manually while switching off is automatic:
- if no movement is detected at the end of the set delay time.
After switching off the load, if any movement is detected within 30 s, the load is
automatically switched back on (retrigger function on). At the end of this time
interval, the load must be switched back on manually.
Detection mode
Set of technologies used for detection.
Initial:
set of technologies used for the first detection.
Holding:
set of technologies used after the first detection.
Retrigger:
set of technologies used for the Retrigger function.
After switching off, any new detection within 30 seconds will cause the load to switch
back on automatically. After 30 seconds, the load must be switched back on manually.
Available only in Eco mode.
Alarm:
before switching off the load the sensor emits an audible warning signal.
Intervals: 1 minute, 30 seconds, and 10 seconds.
Advanced mode:
Calibration
To calibrate the sensor, it is necessary to measure the lighting level present using
a lux meter and send the value to the sensor using a configuration remote control
(BMSO4001).
Calibration procedure:
Step 1: with only artificial light.
Switch the load on at maximum intensity and close the shutters (if you cannot do
this then wait for sunset).
Measure the level of lighting and send it to the sensor via the remote control.
Step 2: with only natural light.
Turn off the load and open the shutters.
Adjustment
This function allows the sensor to switch off the load 10 minutes (plus a safety
threshold to avoid inappropriate switching off) after the lighting level exceeds the
brightness threshold, even though movement has been detected.
Contribution of light:
amount of supplementary light supplied by switching on the
load.
When the contribution of light parameter is set to “auto” the sensor automatically
calculates the contribution of light.