Boss Direct / Indirect Installation Guide
43
Fault
Possible Cause
Solution
Water escaping from the
case unit.
Compression fitting on hot -
draw off not sealing.
Check / remake joint sealing paste.
Cold water at hot tops.
Immersion heater not switched
on or cutout has triggered.
Check / reset.
Indirect - Boiler not working.
Check boiler - consult boiler manufactures’
instructions.
Indirect - motorized valve fault.
Check plumbing / wiring motorized valve.
Indirect - cutout in dual stat has
operated.
Check for faults in the thermostat or high limit
stat and reset.
Water discharges from
expansion relief valve
If continual - pressure reducing
valve (part of inlet control set )
may not be operating correctly.
Check outlet pressure from inlet control set is
3 bar.
If continual - expansion relief
valve seat may be damaged.
Remove cartridge - check seat and renew if
necessary.
If intermittent - expansion vessel
charge may have reduced / blad-
der perished.
Check pressure in expansion vessel. Recharge
to 3 bar if necessary. If bladder perished
replace vessel.
Unit is being back pressurized.
With cylinder cold check pressure in cylinder. If
this is the same as the incoming mains pressure
then you are getting backfeed. Install a balanced
cold supply.
Water discharges from
temperature & pressure
relief valve
Unit has overheated - thermal
controls have failed.
Switched off power to boiler and immersion
heaters. Leave water supply on. Wait until dis-
charge stops. Isolate water supply and replace
if faulty.
Milky / cloudy water
Oxygenated Water.
Water from any pressurized system will release
oxygen bubbles when flowing. The bubbles will
settle out.
No hot water flow
Cold main off.
Check and open stopcock.
Strainer blocked in pressure
reducing valve.
Isolate water supply and clean.
Inlet control set may be fitted
incorrectly.
Check and refit if required.
Noise during hot water
draw o - typically worse
in the morning
Loose airing cupboard pipework. Install extra clips.
Hot or warm water from
cold tap
If tap runs cold after a minute or
so the pipe is picking up heat
from heating pipework.
Insulate/re-route.
Содержание BOSS 100
Страница 4: ...www bssindustrial co uk 4 ...
Страница 31: ...Boss Direct Indirect Installation Guide 31 Cylinder Schematic Electrical Diagram S Plan ...
Страница 33: ...Boss Direct Indirect Installation Guide 33 Cylinder Schematic Electrical Diagram Y Plan ...
Страница 44: ...www bssindustrial co uk 44 48 Direct Indirect Mains Pressure Benchmark Checklist ...
Страница 45: ...Boss Direct Indirect Installation Guide 45 49 Water Storage System Commisioning ...
Страница 47: ...Boss Direct Indirect Installation Guide 47 Notes ...