WIRING DIAGRAM NOTES

1. The AC model thermostat can only control 1-stage cool and 1-stage heat. Dip Switch-C on has no controlling function and can either be

ON or OFF.

2. HP and 2S model thermostat MUST have Dip Switch-C ON when installed in air conditioner applications. If required, second-stage heat

is controlled by O/W2. Refer to indoor equipment Installation Instructions for proper setup.

3. HP and 2S model thermostat MUST have Dip Switch-C OFF when installed in heat pump applications. The reversing valve is controlled

by O/W2.

4. Intelligent Heat Staging Option: 2S model thermostat with Dip Switch-C OFF and Switch-D ON. This provides single-stage heat pump

operation Y/Y2, with three-stage auxiliary heat via W/W1 and Y1/W2. Refer to variable-speed fan coil Installation Instructions. Proper
’intelligent heat capable’ electric heater package must be used.

5. As an option, lock the furnace into low-fire operation and let O/W2 control high-fire operation. Refer to indoor equipment Installation

Instructions for proper setup.

6. Furnace must control its own second-stage heat operation via furnace control algorithm. Refer to indoor equipment Installation Instructions

for proper setup.

7. Terminals marked with * may not be present on equipment.

8. Refer to fan coil Installation Instructions for proper wiring.

9. Select the "ZONE" position on the 2-speed heat pump control board.

10. Omit red and pink wires from diagram with wiring a 564A or 664A with 2-stage heaters.

11. Refer to outdoor equipment Installation Instructions for proper setup.

12. Program thermostat to bring on G (fan) with any W (heat) selection. See section under "set thermostat configuration."

—13—

Содержание TSTAT

Страница 1: ... during a power interruption the internal memory stores programs for an unlimited time and the clock continues to run for at least 72 hrs INSTALLATION CONSIDERATIONS POWER Note that all TSTAT models require no batteries and are not power stealing They do require 24VAC R and C terminals to be connected for proper operation Thermostat will not operate without these 2 connections MODELS There are 3 d...

Страница 2: ...an Y for first stage heat TO SET OFF for HP applications Extra relay controls reversing valve This is factory default ON for AC applications Extra output can be used for 2 stage heat SWITCH D INTELLIGENT HEAT STAGING SELECT ACTIVE ON 2S MODELS ONLY This switch converts a 2 speed heat pump thermostat with 1 stage of auxiliary heat into a 1 speed heat pump thermostat with 3 stages of auxiliary heat ...

Страница 3: ...ty and slow cycle rate Lower numbers increase sensitivity and cycle rate However a limiting feature will not allow more than 4 cycles per hr regardless of setting Anticipator values can range from 1 to 9 Factory default is 3 This default setting will provide optimum performance in nearly all installations Try it first Do not change setting unless there is evidence of the need to do so Unlike conve...

Страница 4: ...en shipped from the factory so this adjustment will provide the best accuracy when set to 0 TO SELECT 1 Enter configuration mode if not already there See above Use up and down buttons to make small now flashing display indicate 13 2 Press SET TIME TEMP button once to flash large display 3 Use up or down buttons to move between 5 4 3 2 1 0 1 2 3 4 or 5 on large display Factory default is 0 4 Press ...

Страница 5: ...t stage With more than 2 stages available let the timer advance one stage every 15 minutes TO TEST EMERGENCY HEAT heat pump systems only To test press MODE button until EHEAT icon turns on This will allow operation of auxiliary heat only Raising set point above room temperature will turn on the first stage of auxiliary heating W W1 Raising set point more than 5 above room temperature will advance ...

Страница 6: ... N A Y Y2 N A N A HP01 B HP OFF EITHER R C G Y Y2 W W1 N A N A Y Y2 N A O W2 HP01 B AC ON EITHER R C G W W1 O W2 N A N A Y Y2 N A N A 2S01 B 2 Speed AC ON EITHER R C G W W1 O W2 N A N A Y1 W2 Y Y2 N A 2S01 B 2 Speed HP OFF OFF R C G Y1 W2 Y Y2 W W1 N A Y1 W2 Y Y2 O W2 2S01 B 1 Speed HP OFF ON R C G Y Y2 W W1 Y1 W2 W W1 Y1 W2 Y Y2 N A O W2 Y1 W2 is on without W W1 AC Air conditioner HP Heat pump 2S...

Страница 7: ...OL STAGE 1 N A N A R G W W1 Y Y2 O W2 Y1 W2 R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y C MODEL AC THERMOSTAT TWO STAGE OR VARIABLE SPEED FURNACE SINGLE SPEED AIR CONDITIONER See notes 1 and 6 W W1 Y Y2 HUM W2 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF Fig 4 Single Speed Air Conditioner with 2 Stage or Variable Speed Furnace Model HP Thermostat A98487 24 VAC HOT FAN H...

Страница 8: ...R CONDITIONER See notes 1 7 and 8 Y W2 W3 E SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF Fig 8 Two Speed Air Conditioner with Single Stage Furnace Model 2S Thermostat A98491 COOL STAGE 1 FAN HEAT STAGE 1 COOL STAGE 2 N A 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C MODEL 2S THERMOSTAT SINGLE STAGE FURNACE TWO SPEED AIR CONDITIONER See n...

Страница 9: ...es 2 5 and 7 R Y1 R G W W1 HUM Y Y2 W2 Y1 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF ON OFF Fig 12 Two Speed Heat Pump with 2 Stage or Variable Speed Furnace Model 2S Thermostat A98495 COOL HEAT STAGE 1 RVS COOLING HEAT STAGE 3 COOL HEAT STAGE 2 FAN 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C W2 MODEL 2S THERMOSTAT TWO STAGE OR VARIABLE SPEE...

Страница 10: ...ETTINGS ON A B C D OFF OFF OFF OFF Fig 16 Single Speed Air Conditioner with Variable Speed Fan Coil FK FV Model HP Thermostat A98499 24 VAC HOT FAN HEAT STAGE 1 HEAT STAGE 2 COOL STAGE 1 N A R G R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C C MODEL HP THERMOSTAT EASY SELECT TERMINAL BOARD J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING SINGLE SPEED AIR CONDITIONER See notes 2 and 8 DH O Y1...

Страница 11: ...W2 W1 Y Y2 Y2 Y Y2 O W2 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF ON OFF Fig 20 Single Speed Packaged Air Conditioner with Single Stage Electric Heat 555A 557A 564A A98503 N A FAN HEAT STAGE 1 COOL STAGE 1 N A 24 VAC HOT R G W W1 Y Y2 O W2 B S1 S2 MODEL AC THERMOSTAT SPLICE BOX GRN WHT BRN WHT BRN See notes 1 11 and 12 C Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION HEATER CONTROL BOX RED...

Страница 12: ... Y2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION HEATER CONTROL BOX RED RED VIO PNK SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF ON OFF Fig 24 Single Speed Packaged Heat Pump with Single Stage Gas Furnace 658A A98507 R G W W1 Y Y2 B S1 S2 MODEL HP THERMOSTAT SPLICE BOX YEL ORN BRN See notes 3 11 and 12 C O W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION WHT GRN RED COOL HEAT STAGE 1 HEAT STAGE...

Страница 13: ...Y1 W2 Refer to variable speed fan coil Installation Instructions Proper intelligent heat capable electric heater package must be used 5 As an option lock the furnace into low fire operation and let O W2 control high fire operation Refer to indoor equipment Installation Instructions for proper setup 6 Furnace must control its own second stage heat operation via furnace control algorithm Refer to in...

Страница 14: ... to prevent operation of the equipment if the thermostat has failed E2 If the AC line voltage drops below a minimum brownout level all outputs are turned off and the display indicates E2 This condition will remain for 15 seconds after proper line voltage is restored If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temp...

Страница 15: ...n or Off Mode Off Heat Cool Auto Eheat Heating Set Point Value Cooling Set Point Value Fan Auto or On 1 Anticipator 1 9 factory default 3 2 Clean Filter Timer Off or 1 9 factory default 2 3 Fahrenheit or Celsius F or C factory default F 4 Fan On with W Off or On factory default Off 5 7 N A 8 9 12 13 14 N A 15 Enable Auto Mode Off or On factory default On Mon Tue Wed Thu Fri Sat Sun TIME HEAT COOL ...

Страница 16: ...ased formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 962 9212 Packaged Service Training Classroom Service Training A94328 1998 B...

Отзывы: