background image

NOTE:

If subcooling charging conditions are not favorable,

charge must be weighed in accordance with unit rating plate ± 0.6
oz/ft of 3/8-in. liquid line above or below 15 ft respectively.
EXAMPLE: To calculate additional charge required for a 25 ft line
set: 25 ft - 15 ft = 10 ft x 0.6 oz/ft = 6 oz of additional charge.

XII.

SYSTEM FUNCTIONS AND SEQUENCE OF OPERA-

TION

The outdoor unit control system has special functions. The
following is an overview of the two-speed control functions:

A.

COOLING OPERATION

This product utilizes a 2-stage cooling indoor thermostat. With a
call for first stage cooling (Yl), the outdoor fan and low capacity
compressor are energized. If low capacity cannot satisfy cooling
demand, high capacity is energized (Yl and Y2 or Y2 only) by the
second stage of indoor thermostat. After second stage is satisfied,
the unit returns to low-speed operation until first stage is satisfied
or until second stage is required again. When both one stage and
two stage cooling are satisfied, the compressor will shut off.

NOTE:

If unit has not operated within the past 12 hours or

following a unit power-up, upon the next thermostat high- or
low-speed demand, unit operates for a minimum of 5 minutes in
high speed.

NOTE:

When two-speed unit is operating at low speed, system

vapor (suction) pressure will be higher than a standard single-
speed system or high-speed operation. This normal operation is
due to the reduced capacity operating with typically larger indoor
and outdoor coils.

NOTE:

Outdoor fan motor will continue to operate for one

minute after compressor shuts off, when outdoor ambient is greater
than or equal to 100°F.

B.

STATUS FUNCTION LIGHTS

A system control STATUS function light is located on the outdoor
unit control board (see Fig. 12). The STATUS light provides
signals for several system operations. See Table 5 for codes and
definitions. Table 5 also provides the order of signal importance.

NOTE:

Only one code will be displayed on the outdoor unit

control board (the most recent with the highest priority).

C.

FACTORY DEFAULTS

Factory defaults have been provided in the event of failure of
outdoor air thermistor, coil thermistor, and/or furnace interface
jumper.

D.

ONE MINUTE SPEED CHANGE TIME DELAY

When compressor changes speeds from high to low or low to high,
there is a 1 minute time delay before compressor restarts. The
outdoor fan motor remains running.

E.

COMPRESSOR OPERATION

When the compressor operates in high capacity operation, the
motor rotates clockwise. Both the lower and upper pistons are
eccentric with the rotating crankshaft and both compress refriger-
ant. When the compressor operates in low capacity the motor
reverses direction (rotates counterclockwise). The lower piston
becomes idle and the upper piston compresses refrigerant. The
start and run windings are reversed.

F.

CRANKCASE HEATER OPERATION

The two-speed control energizes crankcase heater during unit off
cycle.

G.

OUTDOOR FAN MOTOR OPERATION

The outdoor unit control energizes outdoor fan any time compres-
sor is operating. The outdoor fan remains energized during the 1
minute speed change time delay and if a pressure switch or
compressor overload should trip. Outdoor fan motor will continue
to operate for one minute after the compressor shuts off when the
outdoor ambient is greater than or equal to 100°F.

H.

COMPRESSOR VOLTAGE FAILURE (6 FLASHES)

The control senses the voltage of the compressor run winding. If
compressor voltage (Vc) is less than 90v when control board is
calling for compressor operation, control shuts compressor off for
15 minutes with outdoor fan running. After 15 minutes (provided
there is a call for Y1 or Y2), control attempts to start compressor.
During this time, a code of 6 flashes appears at control board. If Vc
trip occurs 3 consecutive times during a Y1 request, then low
capacity operation is locked out and control responds to Y2
requests until a reset occurs. If 3 consecutive trips occur in a
combination of Yl and Y2 or all Y2 requests, then both low and
high capacity operation will be locked out. The compressor voltage
failure (6 flashes) can be caused by:

compressor internal overload trip (refer to Table 6 for correct
winding resistance).

no 240 volt power supply to outdoor unit.

failed compressor contactor(s).

failure of start relay to pick up properly.

improper wiring.

TABLE 4—SUBCOOLING TEMPERATURES

UNIT

TXV TYPE EXPANSION DEVICE

HIGH CAPACITY ONLY

SUBCOOLING AT SERVICE VALVE

024

14°F

036

15°F

048

12°F

060

16°F

TABLE 5—CONTROL FUNCTION LED CODE

CODE

DEFINITION

SIGNAL

IMPORTANCE*

Constant flash

No pause

No demand

Stand by

10

1 flash

w/pause

Low-speed operation

9

2 flashes

w/pause

High-speed operation

8

3 flashes

w/pause

Outdoor thermistor failure

7

4 flashes

w/pause

Outdoor coil thermistor failure

6

3 flashes

pause

4 flashes

Thermistor out of range

5

5 flashes

pause

1 flash

Low pressure switch trip

4

5 flashes

pause

2 flashes

High pressure switch trip

3

6 flashes

w/pause

Compressor V

C

/V

H

trip

2

Constant light

No pause

No flash

Board failure

1

*Function light signal order of importance in case of multiple signal request; 1
is most important.

TABLE 6—DUAL CAPACITY COMPRESSOR

(WINDING RESISTANCE AT 70° ± 20°)

WINDING

024

036

048

060

Start (S-C)

2.280

1.850

1.457

0.740

Run (R-C)

0.770

0.745

0.552

0.356

—12—

Содержание PURON PLUS 598B

Страница 1: ...an cause personal injury or death CAUTION Puron R 410A systems operate at higher pressures than standard R 22 systems Be certain that service equipment is rated for Puron Some R 22 service equipment may not be acceptable Check with your distributor INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Lo...

Страница 2: ...1 side of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit IV OPERATING AMBIENTS The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F V INSTALL TXV Puron fan coils and furnace coils come factory ...

Страница 3: ...barrier as necessary to prevent damage to drain pan IMPORTANT Route the equalizer tube of approved Puron TXV through suction line connection opening in fitting panel prior to replacing fitting panel around tubing 8 Install TXV with 3 8 in copper tubing through small hole in service panel See Fig 5A To avoid damage to tubing or valve use wrench and backup wrench to attach TXV to distributor 9 Reins...

Страница 4: ...ctions using industry accepted methods and materials Do not use soft solder materials which melt below 800 F Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all field and factory joints IMPORTANT Check factory tubing on both indoor and outdoor unit to ensure tubes are not rubbing against each other or any sheet metal Pay c...

Страница 5: ...it cabinet must have as uninter rupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes Failure to follow this warning can result in an electric shock fire or death B CONNECT GROUND AND POWER WIRES Connect ground wire to ground connection in contr...

Страница 6: ...ed the system operates on high speed compressor and low speed airflow until humidistat closes Fig 11 shows the wiring with a Bryant Thermidistat which controls temperature and hu midity level without the need for an additional humidistat and relay IX MAKE AIRFLOW SELECTIONS A AIRFLOW SELECTION FOR 315AAV 355MAV FUR NACES The 315AAV 355MAV Non Condensing Variable Speed Fur naces provide high and lo...

Страница 7: ...SOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 1 2 3 6 and 8 A01497 O W2 W W1 Y1 W2 G R THERMIDISTAT CONTROL MODEL RH TWO STAGE FURNACE WITH PSC BLOWER MOTOR TWO SPEED AIR CONDITIONER W W1 G Y Y2 C Y2 R Y1 C DHUM HUM B S1 S2 W2 R C HEAT STAGE 1 COOL STAGE 1 COOL STAGE 2 HEAT STAGE 2 FAN 24 VAC HOT 24 VAC COMM N A HUMIDIFY N A OUTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR...

Страница 8: ... 10 A01503 O W2 W W1 Y1 W2 G R NON PROGRAMMABLE THERMOSTAT MODEL 2S FURNACE BOARD AFS BOARD TWO SPEED AIR CONDITIONER VARIABLE SPEED 80 NON CONDENSING FURNACE W W1 G Y Y2 C Y2 Y1 C B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 1 COOL STAGE 2 COOL STAGE 1 HEAT STAGE 2 FAN 24 VAC HOT 24 VAC COM N A OUTDOOR SENSOR CONNECTIONS Y Y2 See note 1 2 3 4 and 10 A01504 O W2 W W1 Y1 W2 G R PROGRAMMABLE ...

Страница 9: ... W W1 G Y Y2 C Y2 R Y1 C B S1 S2 W2 R C HEAT STAGE 1 COOL STAGE 1 COOL STAGE 2 HEAT STAGE 2 FAN 24 VAC HOT 24 VAC COMM N A OUTDOOR SENSOR CONNECTION Y Y2 HUM DEHUM DE JUMPER See notes 1 2 3 and 5 A01507 Fig 11 Typical 24V Wiring Diagram Cont O W2 W W1 Y1 W2 G R W2 W1 THERMIDISTAT CONTROL MODEL RH FK4C FV4A OR 40FK FAN COIL TWO SPEED AIR CONDITIONER Y1 G C Y2 R Y1 C DHUM HUM B S1 S2 Y Y2 R O C DH H...

Страница 10: ... THERMIDISTAT DIP SWITCH NO 2 SHOULD BE SET IN THE ON POSITION FOR DUAL CAPACITY COMPRESSOR OPERATION 9 TO ACTIVATE DEHUMIDIFY FUNCTION ON FK4 OR FV4 REMOVE J1 JUMPER AT FAN COIL CONTROL BOARD 10 AS AN OPTION LOCK FURNACE INTO LOW FIRE OPERATION AND LET O W2 CONTROL HIGH FIRE OPERATION REFER TO FURNACE INSTALLATION INSTRUCTIONS FOR PROPER SETUP 11 TO ACTIVATE DEHUMIDIFY FEATURE ON CURRENT STYLE VA...

Страница 11: ... minimum of 5 minutes in high speed XI CHECK CHARGE WARNING Service valve gage ports are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses and gloves when handling refrigerant A COOLING ONLY PROCEDURE 1 Operate unit a minimum of 15 minutes before checking ...

Страница 12: ...ntric with the rotating crankshaft and both compress refriger ant When the compressor operates in low capacity the motor reverses direction rotates counterclockwise The lower piston becomes idle and the upper piston compresses refrigerant The start and run windings are reversed F CRANKCASE HEATER OPERATION The two speed control energizes crankcase heater during unit off cycle G OUTDOOR FAN MOTOR O...

Страница 13: ... attached to motor windings COMPRESSOR CONTROL CONTACTORS Low and high capacity contactor coils are 24 volts The electronic control board controls the operation of the low speed C L and the high speed C H contactors K TEMPERATURE THERMISTORS Thermistors are electronic devices which sense temperature As the temperature increases the resistance decreases Thermistors are used to sense outdoor ambient...

Страница 14: ... tion and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing high performance and to minimize possible equip ment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as coastal applications Fig 14 View from Top...

Страница 15: ... YEL BLK BLK BLK CL 11 21 H C START COMP RELAY BRN CAP L2 L1 EQUIP GND DUAL CAPACITY A B C D BLU BRN BRN BLK YEL BRN BLK C O W Y2 Y1 R 1 RVS SEV HP AC C C VH L 2 ODF CCH VC 1 2 3 4 5 PL1 1 2 PL2 PL5 1 2 3 1 2 1 2 4 5 YEL BLU BLU BRN BRN 1 2 YEL 5 BRN BLU START CAP NOTE 11 208 230 1 60 POWERSUPPLY COMM STATUS FORCED DEFROST TIME MIN DEFROST BLK PL4 PL3 YEL RED LPS HPS OAT OCT COMP YEL R S C BLU BLU...

Страница 16: ... C D BLU BRN BLK YEL BRN BLK C O W Y2 Y1 R 1 RVS SE V HP AC C C VH L 2 ODF CCH VC 1 2 3 4 5 PL1 1 2 PL2 1 2 3 1 2 1 2 4 5 YEL BLU BLK BRN BRN 1 2 YEL 5 BRN BLU START CAP CL 11 21 208 230 1 60 POWERSUPPLY COMM STATUS FORCED DEFROST TIME MIN DEFROST PL5 PL4 PL3 BLU YEL BRN YEL RED BLK BLK LPS HPS OAT OCT COMP YEL R S C NOTE 11 BLU BLU BL U 2003 Bryant Heating Cooling Systems 7310 W Morris St Indiana...

Отзывы: