WARNING:

The unit cabinet must have an uninter-

rupted or unbroken ground to minimize personal injury if
an electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in
accordance with existing electrical codes. Failure to
follow this warning can result in an electric shock, fire, or
death.

B.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 9.

C.

Connect Control Wiring

Route 24v control wires through control wiring grommet and
connect leads to control wiring. (See Fig. 11.)

Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If
thermostat is located more than 100 ft from unit, as measured
along the control voltage wires, use No. 16 AWG color-coded wire
to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from
incoming power leads.

Use furnace transformer, fan coil transformer, or accessory trans-
former for control power, 24v/40va minimum.

NOTE:

Use of available 24v accessories may exceed the mini-

mum 40va power requirement. Determine total transformer load-
ing and increase the transformer capacity or split the load with an
accessory transformer as required.

IMPORTANT:

Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

IX.

COMPRESSOR CRANKCASE HEATER

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to
outdoor unit.

A crankcase heater is required if refrigerant tubing is longer than
50 ft. Refer to Application Guideline and Service Manual—Air
Conditioners and Heat Pumps Using Puron® Refrigerant.

X.

INSTALL ELECTRICAL ACCESSORIES

Refer to the individual instructions packaged with kits or acces-
sories when installing.

XI.

START-UP

CAUTION:

To prevent compressor damage or personal

injury, observe the following:
•Do not overcharge system with refrigerant.
•Do not operate unit in a vacuum or at negative pressure.
•Do not vent refrigerant to atmosphere. Recover during
system repair or final unit disposal.
•Do not disable low-pressure switch.
In scroll-compressor applications:
•Dome temperatures may be hot.

Fig. 6—Liquid-Line Filter Drier

A99331

CONNECTOR

TUBE

LIQUID-LINE
FILTER-DRYER

Fig. 7—Deep Vacuum Graph

A95424

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN
SYSTEM

VACUUM TIGHT
TOO WET

TIGHT
DRY SYSTEM

2000

MICRONS

2500

3000

3500

4000

4500

5000

A95424

Fig. 8—Triple Evacuation Method

A95425

CHECK FOR TIGHT, DRY SYSTEM 

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHARGE SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

—5—

Содержание PURON 533A

Страница 1: ...ipment or components on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit...

Страница 2: ...and the maximum outdoor operating ambient in cooling mode is 125 F V CHECK INDOOR CHECK FLO RATER PISTON AND INSTALL PISTON RING 533A STANDARD If unit is to be installed with a piston metering device...

Страница 3: ...to tubing or valve to attach TXV to distributor 9 Reinstall TXV support clamp removed in item 3 10 Attach TXV bulb to vapor tube inside cabinet in same location as original was when removed using sup...

Страница 4: ...icrons and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the most positive way of assuring a system is free of air and liquid water See Fig 7 TRIPLE EVACUAT...

Страница 5: ...ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc IX COMPRESSOR CRANKCASE HEATER When equipped with a crankcase heater furnish...

Страница 6: ...ONS AND RECOMMENDED LIQUID LINE AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter...

Страница 7: ...6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line tempera ture is higher than indicated or reclaim refrigerant if temperature is lower Allo...

Страница 8: ...and covers 2 Tighten service valve stem caps to 1 12 turn past finger tight 3 Leave User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill o...

Страница 9: ...55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 6...

Страница 10: ...IR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C BRYANT NON PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FAN COIL AIR CONDITIO...

Страница 11: ...THERMOSTAT FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 Y1 C SEE NOTE 2 G O J1 JUMPER J2 JUMPER A97365 Fig 11 Typical 24v Circuit Connections Cont 24 VAC HOT R G W W1 Y Y2 O W2...

Страница 12: ...actory approved liquid line filter drier is required on every unit Do not use an R 22 TXV If indoor unit is equipped with an R 22 TXV it must be changed to a Puron TXV Never open system to atmosphere...

Отзывы: