PURON® (R-410A) QUICK REFERENCE GUIDE

• Puron® refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and

replacement components are designed to operate with Puron®.

• Puron® refrigerant cylinders are rose colored.

• Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.

• Puron® systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when

charging into suction line with compressor operating.

• Manifold sets should be at least 700 psig high side and 180 psig low side with 550 psig low-side retard.

• Use hoses with 700 psig service pressure rating.

• Leak detectors should be designed to detect HFC refrigerant.

• Puron®, as with other HFCs, is only compatible with POE oils.

• Vacuum pumps will not remove moisture from oil.

• Do not leave Puron® suction line filter driers in line longer than 72 hrs.

• Do not use liquid-line filter driers with rated working pressures less than 600 psig.

• Do not install a suction-line filter drier in liquid line.

• POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

• Poe oils may cause damage to certain plastics and roofing materials.

• Wrap all filter driers and service valves with wet cloth when brazing.

• A factory-approved liquid-line filter drier is required on every unit.

• Do not use an R-22 TXV.

• If indoor unit is equipped with an R-22 TXV, it must be changed to a Puron TXV.

• Never open system to atmosphere while it is under a vacuum.

• When system must be opened for service, recover refrigerant, break vacuum with dry nitrogen prior to opening to atmosphere.

Evacuate to 500 microns prior to recharging.

• Always replace filter drier after opening system for service.

• Do not vent Puron® into the atmosphere.

• Do not use capillary tube coils.

• Observe all warnings, cautions, and bold text.

NOTES:

1. BRYANT THERMOSTAT WIRING DIAGRAMS ARE ONLY ACCURATE FOR MODEL NUMBERS BEGIN-

NING WITH TSTAT _ _ _ _ _ _ _.

2. WIRING MUST CONFORM TO NEC LOCAL CODES.

3. SOME UNITS ARE EQUIPPED WITH PRESSURE SWITCH(ES), TEMPERATURE SWITCH, OR 5-MINUTE

COMPRESSOR CYCLE PROTECTION. CONNECT 24V FIELD WIRING TO FACTORY-PROVIDED STRIPPED
LEADS.

4. A LIQUID-LINE SOLENOID VALVE IS REQUIRED ON SOME UNITS. SEE SPECIFIC UNIT INSTRUCTIONS.

5. THERMOSTATS ARE FACTORY CONFIGURED WITH 5-MINUTE COMPRESSOR CYCLE PROTECTION

AND 4 CYCLES PER HOUR LIMIT. SEE THERMOSTAT INSTALLATION INSTRUCTIONS FOR DETAILS.

6. TO STAGE ELECTRIC RESISTANCE HEAT, CONSULT OUTDOOR THERMOSTAT INSTALLATION IN-

STRUCTIONS.

A97368

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

CONTACTOR

C

© 2002 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231

—12—

Printed in U.S.A.

ii533a186

Catalog No. 5353-308

Содержание PURON 533A

Страница 1: ...ipment or components on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit...

Страница 2: ...and the maximum outdoor operating ambient in cooling mode is 125 F V CHECK INDOOR CHECK FLO RATER PISTON AND INSTALL PISTON RING 533A STANDARD If unit is to be installed with a piston metering device...

Страница 3: ...to tubing or valve to attach TXV to distributor 9 Reinstall TXV support clamp removed in item 3 10 Attach TXV bulb to vapor tube inside cabinet in same location as original was when removed using sup...

Страница 4: ...icrons and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the most positive way of assuring a system is free of air and liquid water See Fig 7 TRIPLE EVACUAT...

Страница 5: ...ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc IX COMPRESSOR CRANKCASE HEATER When equipped with a crankcase heater furnish...

Страница 6: ...ONS AND RECOMMENDED LIQUID LINE AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter...

Страница 7: ...6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line tempera ture is higher than indicated or reclaim refrigerant if temperature is lower Allo...

Страница 8: ...and covers 2 Tighten service valve stem caps to 1 12 turn past finger tight 3 Leave User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill o...

Страница 9: ...55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 6...

Страница 10: ...IR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C BRYANT NON PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FAN COIL AIR CONDITIO...

Страница 11: ...THERMOSTAT FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 Y1 C SEE NOTE 2 G O J1 JUMPER J2 JUMPER A97365 Fig 11 Typical 24v Circuit Connections Cont 24 VAC HOT R G W W1 Y Y2 O W2...

Страница 12: ...actory approved liquid line filter drier is required on every unit Do not use an R 22 TXV If indoor unit is equipped with an R 22 TXV it must be changed to a Puron TXV Never open system to atmosphere...