10
INDOOR
THERMOSTAT
DISCONNECT
PER NEC*
FROM
POWER
SOURCE
RETURN
AIR
TOP COVER
*NEC
- NATIONAL ELECTRICAL CODE
POWER ENTRY
CONTROL ENTRY
A09238
Fig. 10 -- Typical Installation
TRAP
OUTLET
1-in. (25 mm) min.
2-in. (51 mm) min.
A09052
Fig. 11 -- Condensate Trap
Table 1 – Physical Data -- Unit 607----A
607----A24
607----A30
607----A36
607----A42
607----A48
607----A60
Unit Size
2
2.5
3
3.5
4
5
Shipping Weight (lb)
(kg)
354
161
346
157
426
193
472
214
460
209
506
230
Compressor Quantity
1
Type
Scroll
Refrigerant
R-410A
Refrigerant Quantity (lb)
Quantity (kg)
11.1
5.0
10.3
4.7
9.9
4.5
11.3
5.1
12.5
5.7
15.2
6.9
Refrigerant Metering Device
Indoor TXV, Outdoor Dual Accuraters
Orifice OD (in)
(mm)
0.032 (2)
0.81 (2)
0.037 (2)
0.94 (2)
0.038 (2)
0.97 (2)
0.040 (2)
1.02 (2)
0.040 (2)
1.02 (2)
0.049 (2)
1.24 (2)
Outdoor Coil
Rows...Fins/in,
face area (sq. ft.)
2...21
13.6
2...21
13.6
2...21
13.6
2...21
17.5
2...21
17.5
2...21
23.3
Outdoor Fan
Nominal Airflow (cfm)
Diameter (in.)
Diameter (mm)
Motor hp (rpm)
2500
24
610
1/10 (810)
2700
24
610
1/5 (810)
3100
26
660
1/5 (810)
3100
26
660
1/5 (810)
3100
26
660
1/5 (810)
3500
26
660
1/4 (810)
Indoor Coil
Rows...Fins/in,
face area (sq. ft.)
3...17
3.7
3...17
3.7
3...17
4.7
3...17
4.7
3...17
5.6
3...17
5.6
Indoor Blower
Nominal Airflow (cfm)
Size (in.)
Size (mm)
Motor hp (rpm)
800
10 x 10
254 x 254
1/2
1000
10 x 10
254 x 254
1/2
1200
11 x 10
279 x 254
3/4
1400
11 x 10
279 x 254
3/4
1600
11 x 10
279 x 254
1
1750
11 x 10
279 x 254
1
High Pressure Switch (psig)
Cutout
Reset (Auto)
650 +/- 15
420 +/- 25
Loss-of-Charge/Low Pressure Switch (psig)
Cutout
Reset (Auto)
20 +/- 5
45 +/- 10
Return Air Filters
disposable (in)
(mm)
20x20x1
508x508x25
20x24x1
508x610x25
24x30x1
610x762x25
24x36x1
610x914x25
*Required filter sizes shown are based on the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow
velocity of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN.
W.C.
{
If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity.
}
For 460 volt units, add 14 lb (6.4 kg) to the weight.
Table 2 – Minimum Airflow for Reliable Electric Heater Operation (CFM)
SIZE
607-- --A24
607-- --A30
607-- --A36
607-- --A42
607-- --A48
607-- --A60
AIRFLOW (CFM)
800
1025
1250
1400
1710
1800
607C
--
--
A
Содержание PREFERRED 607C--A Series
Страница 3: ...3 A09426 Fig 2 607 A24 30 Unit Dimensions 607C A ...
Страница 4: ...4 A09427 Fig 3 607 A36 60 Unit Dimensions 607C A ...
Страница 11: ...11 A10197 Fig 12 Connection Wiring Schematics 208 230 1 60 607C A ...
Страница 12: ...12 A10197 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 607C A ...
Страница 13: ...13 A10194 Fig 13 Connection Wiring Schematics 208 230 3 60 607C A ...
Страница 14: ...14 A10194 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 607C A ...
Страница 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 607C A ...
Страница 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 607C A ...
Страница 41: ...41 A10059 Fig 45 Economizer Wiring Diagram 607C A ...
Страница 43: ...43 A10200 Fig 45 Cont Ladder Wiring Diagram 230 3 607C A ...
Страница 44: ...44 A10199 Fig 47 Connection Wiring Diagram 460 3 607C A ...
Страница 45: ...45 A10199 Fig 46 Cont Ladder Wiring Diagram 460 3 607C A ...