Table 16 – CO

2

Sensor Standard Settings

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(CFM/

PERSON)

ANALOG

OUTPUT

CO

2

CONTROL

RANGE

(PPM)

OPTIONAL

RELAY

SETPOINT

(PPM)

RELAY

HYSTERESIS

(PPM)

1

Proportional

Any

0---10V

4---20mA

0---2000

1000

50

2

Interface w/Standard Building

Control System

Proportional

Any

2---10V

7---20mA

0---2000

1000

50

3

Exponential

Any

0---10V

4---20mA

0---2000

1100

50

4

Proportional

15

0---10V

4---20mA

0---1100

1100

50

5

Economizer

Proportional

20

0---10V

4---20mA

0---900

900

50

6

Exponential

15

0---10V

4---20mA

1---1100

1100

50

7

Exponential

20

0---10V

4---20mA

0---900

900

50

8

Health & Safety

Proportional

---

0---10V

4---20mA

0---9999

5000

500

9

Parking/Air Intakes/Loading Docks

Proportional

---

0---10V

4---20mA

0---2000

700

50

Table 17 – CO

2

Sensor Standard Settings Economizer Input/Output Logic

INPUTS

OUTPUTS

DEMAND

CONTROL

VENTILATION

(DCV)

ENTHALPY

Y1

Y2

COMPRESSOR

N TERMINAL

OUTDOOR

RETURN

STAGE

1

STAGE

2

OCCUPIED

UNOCCUPIED

DAMPER

Below set (DCV

LED Off)

High (Free Cooling

LED off)

Low

On

On

On

On

Minimum position

Closed

On

Off

On

Off

Off

Off

Off

Off

Low (Free Cooling

LED on)

High

On

On

On

Off

Modulating** (between min.

position and full---open)

Modulating** (between closed

and full---open)

On

Off

Off

Off

Off

Off

Off

Off

Minimum position

Closed

Above set (DCV

LED On)

High (Free Cooling

LED off)

Low

On

On

On

On

Modulating

{{

(between

min. position and DCV

maximum)

Modulating

{{

(between closed

and DCV maximum)

On

Off

On

Off

Off

Off

Off

Off

Low (Free Cooling

LED on)

High

On

On

On

Off

Modulating***

Modulating

{{{

On

Off

Off

Off

Off

Off

Off

Off

* For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.

{

Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), now power (Unoccupied).

**Modulating is based on the supply--- air sensor signal.

{{

Modulation is based on the DCV signal.

***Modulation is based on the greater of DCV and supply--- air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply--- air signal).

{{{

Modulating is based on the greater of DCV and supply--- air sensor signals, between closed and wither maximum position (DCV) or fully open (supply--- air signal).

OPERATION

Sequence of Operation—

When free cooling is not available, the

compressor will be controlled by the thermostat. When free cooling
is available, the outdoor--air damper is modulated by the Economizer
control to provide a 50

_

to 55

_

F (10

_

to 12.8

_

C) supply--air

temperature into the zone. As the supply--air temperature fluctuates
above 55

_

(12.8

_

C) or below 50

_

F (10

_

C), the dampers will be

modulated (open or close) to bring the supply--air temperature back
within the set points. For Economizer operation, there must be a
thermostat call for the fan (G). This will move the damper to its
minimum position during the occupied mode.

NOTE

: The DCV Max potentiometer must be closed (CCW)

when not using CO

2

sensor.

Above 50

_

F (10

_

C) supply--air temperature, the dampers will

modulate from 100% open to the minimum open position. From

50

_

F to 45

_

F (10

_

to 7.2

_

C) supply--air temperature, the dampers

will maintain at the minimum open position. Below 45

_

F (7.2

_

C),

the dampers will be completely shut. As the supply--air temperature

rises, the dampers will come back open to the minimum open
position once the supply--air temperature rises to 48

_

F (8.9

_

C). If

power exhaust is installed, as the outdoor--air damper opens and
closes, the power exhaust fans will be energized and deenergized.

If field--installed accessory CO

2

sensors are connected to the

Economizer control, a demand controlled ventilation strategy will

begin to operate. As the CO

2

level in the zone increases above the

CO

2

set point, the minimum position of the damper will be

increased proportionally. As the CO

2

level decreases because of the

increase in fresh air, the outdoor--air damper will be proportionally
closed. Damper position will follow the higher demand condition

from DCV mode or free cooling mode. Damper movement from

full closed to full open (or vice versa) will take between 1 1/2 and
2 1/2 minutes. If free cooling can be used as determined from the

appropriate changeover command (dry bulb, enthalpy curve, or
differential enthalpy), a call for cooling (Y1 closes at the

thermostat) will cause the control to modulate the dampers open to

maintain the supply air temperature set point at 50

_

to 55

_

F (10

_

to 12.8

_

C). As the supply air temperature drops below the set point

range of 50

_

to 55

_

F (10

_

to 12.8

_

C), the control will modulate

the outdoor--air dampers closed to maintain the proper supply--air

temperature.

704D

--

--

A

Содержание Legacy 704D--A

Страница 1: ...allation and servicing of this equipment can be hazardous due to mechanical and electrical components Only trained and qualified personnel should install repair or service this equipment Untrained per...

Страница 2: ...gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in 6 35 mm See Fig 6 This is necessary for unit drain to function properly Refer to accessory roof...

Страница 3: ...3 A09467 Fig 2 704D A24 36 Unit Dimensions 704D A...

Страница 4: ...4 A09468 Fig 3 704D A42 60 Unit Dimensions 704D A...

Страница 5: ...B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 CPRFCURB011A00 14 356 Large C...

Страница 6: ...ane operators and ground support staff should handle and install this equipment When working with this equipment observe precautions in the literature on tags stickers and labels attached to the equip...

Страница 7: ...7 Install Duct Connections The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non residence type air conditioning and ventilating...

Страница 8: ...ll ductwork for maximum required airflow either heating or cooling for unit being installed Avoid abrupt duct size increases or decreases or performance may be affected 6 Adequately insulate and weath...

Страница 9: ...d connection 3 Locate the black and yellow wires connected to the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor POWER SUPPLY FIELD SUPPLIED F...

Страница 10: ...174 406 184 COMPRESSORS Quantity Scroll 1 REFRIGERANT R 410A Quantity lb Quantity kg 4 8 2 2 6 2 2 8 6 4 2 9 6 1 2 7 6 4 2 9 10 0 4 5 REFRIGERANT METERING DEVICE TXV OUTDOOR COIL Rows Fins in Face Are...

Страница 11: ...cover refrigerant from system and evacuate to 500 microns if no additional leaks are found 5 Charge unit with Puron R 410A refrigerant using an accurate scale Refer to unit rating plate for required c...

Страница 12: ...ure not used To change cooling speed 1 Remove the vinyl cap off of the desired speed tap wire Refer to Table 3 for color coding Add the wet coil pressure drop in Table 5 to the system static to determ...

Страница 13: ...ower speed WARNING CONTINUOUS FAN OPERATION When the DEHUM feature is not used the continuous fan speed will be the same as cooling fan speed When the DEHUM feature is used the continuous fan will ope...

Страница 14: ...ssure available for ducting Shaded areas indicate airflows that are not recommended for dehumidification control Table 5 704D A Wet Coil Pressure Drop IN W C UNIT SIZE STANDARD CFM S C F M 600 700 800...

Страница 15: ...INSTRUCTIONS TO DETERMINE CORRECT SPEED TAP SETTING 6 DO NOT DISCONNECT PLUG UNDER LOAD 7 THIS FUSE IS MANUFACTURED BY LITTELFUSE P N 257003 8 UNIT FACTORY SHIPPED IN STD MODE ACCESSSORY ELECTRIC HEA...

Страница 16: ...P1 4 P1 3 P1 2 P1 1 P2 4 P2 3 P2 2 P2 1 C C1 C2 HR1 HR4 HR2 HR3 BRN BRN BRN BRN WHT VIO PNK GRY 2 5 4 3 1 BLU PNK RED BLK G Y HIGH C P4 4 P4 3 P4 2 P4 1 P4 5 IFB RED 24VAC IF USED ACCESSORY ELECTRIC...

Страница 17: ...17 A10202C Fig 13 Connection Wiring Diagram 208 230 3 60 704D A...

Страница 18: ...18 A10202L Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 704D A...

Страница 19: ...SES ARE MANUFACTURED BY COOPER BUSSMAN P N FNQ R 5 9 DEHUM FEATURE CANNOT BE USED WHEN ECONOMIZER IS INSTALLED UNIT FACTORY SHIPPED IN STD MODE ACCESSSORY ELECTRIC HEAT HR1 5 KW HR1 2 10 KW HR1 2 3 15...

Страница 20: ...HT VIO PNK GRY 2 5 4 3 1 BLU PNK RED BLK G Y HIGH C P4 4 P4 3 P4 2 P4 1 P4 5 IFB RED 24VAC IF USED ACCESSORY ELECTRIC HEAT G Y RED BRN WHT VIO PNK GRY R C Y1 G W2 W3 50VL500271 YEL L2 ORN SEE NOTE 4 D...

Страница 21: ...21 A08490 Fig 15 Cooling Charging Chart 704D A...

Страница 22: ...with the same dimensional size and type as originally installed See Table 11 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean cleanable ty...

Страница 23: ...lush all dirt and debris from the unit base Inspect the drain pan and condensate drain line when inspecting the coils Clean the drain pan and condensate drain by removing all foreign matter from the p...

Страница 24: ...ure drop at about 20 psig 957 Pa If system pressure is above this switch should be closed To check switch 1 Turn off all power to unit 2 Disconnect leads on switch 3 Apply ohmmeter leads across switch...

Страница 25: ...an impermeable polyethylene plastic drip cloth or tarp Cover an approximate 10 x 10 ft 3 x 3 m area 2 Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant s...

Страница 26: ...ith minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove mo...

Страница 27: ...compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Det...

Страница 28: ...INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL...

Страница 29: ...V Control Using a Duct Mounted CO2 Sensor 33ZCSENC02 or CGCDXSEN004A00 and 33ZCASPCO2 or CGCDXASP00100 or CRCBDIOX005A00 CRENTDIF004A00 accessory is used on many different base units As such these kit...

Страница 30: ...ber Table 13 Filter Part Number DESCRIPTION PART NUMBER Indoor Coil Air Filter 12 x 20 x 1 304 8 x 508 x 25 4 mm KH01AA312 NOTE The economizer control settings and the filters are accessible through t...

Страница 31: ...Duct Cover Panel Hood Divider Removed A09691 Fig 20 Horizontal Return Duct Cover Panel Removal Filter Angle Bracket Right Hood Side Panel Left Hood Side Panel Filter Angle Bracket A09692 Fig 21 Filter...

Страница 32: ...nel Hood Top Panel Left Hood Side Panel Hood Divider A09693 Fig 22 Economizer Hood Assembly A09694 Fig 23 Economizer Hood Installation Filter Clips Aluminum Filter A09695 Fig 24 Filter Installation Se...

Страница 33: ...eturn duct cover panel Screw in place ensuring all seams are air and watertight 6 Open economizer hood package found on the top skid Mount OAT sensor to its assigned bracket by screwing together with...

Страница 34: ...698 Fig 27 OAT Bracket Installation Filter Angle Bracket Right Hood Side Panel Filter Angle Bracket Left Hood Side Panel Right Hood Side Left Hood Side A09699 Fig 28 Filter Angle Bracket Installation...

Страница 35: ...mm KH01AA316 18 x 24 x 1 457 2 x 609 5 x 25 4 mm KH01AA318 13 Economizer controls are set to a standard factory setting Nevertheless you can adjust these settings through the filter access door Review...

Страница 36: ...points The temperature changeover is set using 3 dip switches on the sensor The ABCD potentiometer on the controller should be set to the D position See Fig 35 SUPPLY AIR TEMPERATURE SAT SENSOR The su...

Страница 37: ...adjust the outdoor air dampers to minimum position If the outdoor air temperature is below the set point the position of the outdoor air dampers will be controlled to provide free cooling using outdoo...

Страница 38: ...en the outdoor air has a lower enthalpy than the return air and is below the set point the Economizeropenstobringinoutdoorairfor freecooling Replacethe standard outside air dry bulb temperature sensor...

Страница 39: ...e is 75_F 23 9_C 60 x 10 75 x 90 73 5_F 23 1_C 2 Disconnect the supply air sensor from terminals T and T1 3 Ensure that the factory installed jumper is in place across terminals P and P1 If remote dam...

Страница 40: ...CAL ECONOMIZER THE ECONOMIZER MOTOR CONNECTIONS ARE AS SHOWN FOR HORIZONTAL ECONOMIZER THE ECONOMIZER MOTOR IS ATTACHED TO THE ECONOMIZER IV BOARD THE WIRES SHOWN ARE NOT UTILIZED BLK WHT RED 5 WHEN N...

Страница 41: ...41 A10201 Fig 41 Connection Wiring Diagram 230 3 704D A...

Страница 42: ...42 A10201 Fig 41 Cont Ladder Wiring Diagram 230 3 704D A...

Страница 43: ...43 A10203 Fig 42 Connection Wiring Diagram 460 3 704D A...

Страница 44: ...44 A10203 Fig 42 Cont Ladder Wiring Diagram 460 3 704D A...

Страница 45: ...meter to the correct position The same equation can be used to determine the occupied or maximum ventilation rate to the building For example an output of 3 6 volts to the actuator provides a base ven...

Страница 46: ...ree cooling is not available the compressor will be controlled by the thermostat When free cooling is available the outdoor air damper is modulated by the Economizer control to provide a 50_ to 55_F 1...

Страница 47: ...remain in position 5 Turn the DCV set point potentiometer CW until the DCV LED turns off The DCV LED should turn off when the potentiometer is approximately 9 v The actuator should drive fully closed...

Страница 48: ...48 REQUIRED CLEARANCES TO COMBUSTIBLE MATL NEC REQUIRED CLEARANCES REQUIRED CLEARANCE FOR OPERATION AND SERVICING A10230 Fig 43 704D A 30 36 3 Phase with Economizer 704D A...

Страница 49: ...49 REQUIRED CLEARANCES TO COMBUSTIBLE MATL NEC REQUIRED CLEARANCES REQUIRED CLEARANCE FOR OPERATION AND SERVICING A10231 Fig 44 704D A 42 60 3 Phase with Economizer 704D A...

Страница 50: ...nue or change at any time specifications or designs without notice and without incurring obligations E2010 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 04 10...

Отзывы: