AIR CONDITIONER WITH PURON (R--410A) QUICK REFERENCE GUIDE
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are
designed to operate with Puron. Puron refrigerant cylinders are rose colored.
S
Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright
position.
Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.
S
Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.
S
Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.
S
Manifold sets should be minimum 700 psig high--side and 180 psig low--side with 550 psig low--side retard.
S
Use hoses with minimum 700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC refrigerant.
S
Puron, as with other HFCs, is only compatible with POE oils.
S
Vacuum pumps will not remove moisture from oil.
S
Only use factory specified liquid--line filter driers with rated working pressures no less than 600 psig.
S
Do not install a suction--line filter drier in liquid line.
S
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S
POE oils may cause damage to certain plastics and roofing materials.
S
Wrap all filter driers and service valves with wet cloth when brazing.
S
A Puron liquid--line filter drier is required on every unit.
S
Do not use an R--22 TXV.
S
Never open system to atmosphere while it is under a vacuum.
S
When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
S
Always replace filter drier after opening system for service.
S
Do not vent Puron into the atmosphere.
S
Observe all warnings, cautions, and bold text.
S
Do not leave Puron suction line driers in place for more than 72 hrs.
704D
--
--
A
Содержание Legacy 704D--A
Страница 3: ...3 A09467 Fig 2 704D A24 36 Unit Dimensions 704D A...
Страница 4: ...4 A09468 Fig 3 704D A42 60 Unit Dimensions 704D A...
Страница 17: ...17 A10202C Fig 13 Connection Wiring Diagram 208 230 3 60 704D A...
Страница 18: ...18 A10202L Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 704D A...
Страница 21: ...21 A08490 Fig 15 Cooling Charging Chart 704D A...
Страница 41: ...41 A10201 Fig 41 Connection Wiring Diagram 230 3 704D A...
Страница 42: ...42 A10201 Fig 41 Cont Ladder Wiring Diagram 230 3 704D A...
Страница 43: ...43 A10203 Fig 42 Connection Wiring Diagram 460 3 704D A...
Страница 44: ...44 A10203 Fig 42 Cont Ladder Wiring Diagram 460 3 704D A...