background image

38

ENTHALPY SETTINGS
When the OA temperature, enthalpy and dew point are below

the respective setpoints, the Outdoor Air can be used for econ

-

omizing. Figure 50 shows the new single enthalpy boundaries

in the W7220. There are 5 boundaries (setpoints ES1 through

ES5), which are defined by dry bulb temperature, enthalpy and

dew point.

Refer to Table 22 for ENTH CURVE setpoint values.

The W7220  calculates  the enthalpy and  dew  point using  the

OA temperature and humidity input from the OA enthalpy sen

-

sor.  When  the  OA  temperature,  OA  humidity  and  OA  dew

point are all below the selected boundary, the economizer sets

the economizing mode to YES, economizing is available.

When all of the OA conditions are above the selected bound

-

ary, the conditions are not good to economize and the mode is

set to NO.

Figure 50 shows the 5 current boundaries. There is also a high

limit boundary for differential enthalpy. The high limit bound

-

ary is ES1 when there are no stages of mechanical cooling en

-

ergized  and  HL  (high  limit)  when  a  compressor  stage  is

energized.
TWO-SPEED FAN OPERATION
The W7220 controller has the capability to work with a system

using a 2-speed supply fan. The W7220 does not control the

supply directly but uses the following input status to determine

the speed of the supply fan and controls the OA damper to the

required position.

The W (heating mode) is not controlled by the W7220 but it re

-

quires the status to know where to position the OA damper for

minimum position for the fan speed.

The  2-speed  fan  delay  is  available  when  the  system  is  pro

-

grammed  for  2-speed  fan  (in  the  System  Setup  menu  item).

The  2-speed  fan  delay  is  defaulted  to  5  minutes  and  can  be

changed in the Advanced Setup menu item. When the unit has

a call for Y1 In and in the free cooling mode and there is a call

for Y2 In, the 2-speed fan delay starts and the OA damper will

modulate  100%  open,  the  supply  fan  should  be  set  to  high

speed by the unit controller.

After the delay one of two actions will happen:

• The Y2  In  call  will  be  satisfied  with  the  damper  100%

open and fan on high speed and the call will turn off

OR

• If the call for additional cooling in the space has not been

satisfied then the first stage of mechanical cooling will be

enabled through Y1 Out or Y2 Out.

CHECKOUT
Inspect all wiring connections at the economizer module’s ter

-

minals, and verify compliance with the installation wiring dia

-

grams. For checkout, review the Status of each configured pa

-

rameter and perform the Checkout tests.

For information about menu navigation and use of the keypad

see Interface Overview on page 29.

Power Up

After the W7220 module is mounted and wired, apply power.

Initial Menu Display

On  initial  start  up,  Honeywell  displays  on  the  first  line  and

economizer W7220 on the second line. After a brief pause, the

revision of the software appears on the first line and the second

line is blank.

Power Loss (Outage or Brownout)

All setpoints and advanced settings are restored after any pow

-

er loss or interruption.

NOTE: All settings are stored in non-volatile flash memory.

Status

Use the Status menu (see Table 12) to check the parameter val

-

ues for the various devices and sensors configured.

NOTE:  For  information  about  menu  navigation  and  use  of the

keypad, see Interface Overview on page 29.

Checkout Tests

Use the Checkout menu (see page 33) to test the damper opera

-

tion and any configured outputs. Only items that are config

-

ured are shown in the Checkout menu.

NOTE:  For  information  about  menu  navigation  and  use  of the

keypad see Interface Overview on page 29.

To perform a Checkout test:

1. Scroll to the desired test in the Checkout menu using the

▲ and ▼ buttons. 

2. Press  the 

  (Enter)  button  to  select  the  item.  RUN?

appears. 

3. Press  the 

  (Enter)  button  to  start  the  test.  The  unit

pauses and then displays IN PROGRESS. When the test is

complete, DONE appears. 

4. When all desired parameters have been tested, press the 

(Menu Up/Exit) button to end the test.

The Checkout tests can all be performed at the time of installa

-

tion or at any time during the operation of the system as a test

that the system is operable.

STATE

FAN SPEED

OCC

Low

Y1

Low

Y2

High

W

High

WARNING

ELECTRIC SHOCK HAZARD

Failure to follow this warning could result in personal inju

-

ry, property damage, or death. 

Before  performing  service  or  maintenance  operations  on

unit, always turn off main power switch to unit and install

lock(s) and lockout tag(s). Unit may have more than one

power  switch.  Ensure  electrical  service  to  rooftop  unit

agrees with voltage and amperage listed on the unit rating

plate.

If any wiring changes are required, first be sure to remove

power from the economizer module before starting work.

Pay particular attention to verifying the power connection

(24 vac).

CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment dam

-

age.

Be sure to allow enough time for compressor start-up and

shutdown between checkout tests so that you do not short-

cycle the compressors.

Содержание Legacy 549J 12 Series

Страница 1: ...NG DIAGRAMS EconoMi er X Factory Option 27 SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL ECONOMIZER MODULE WIRING DETAILS S BUS SENSOR WIRING CO2 SENSOR WIRING INTERFACE OVERVIEW SETUP...

Страница 2: ...wer switch to unit and install lock s and lockout tag s Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate Unit may have more than one power swi...

Страница 3: ...Indoor Hail Guard A Al Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louvered Hail Guard N Precoat Al Cu Al Cu Louvered Hail...

Страница 4: ...4 Fig 2 Unit Dimensional Drawing Size 12 Units...

Страница 5: ...5 Fig 2 Unit Dimensional Drawing Size 12 Units cont...

Страница 6: ...ITION A 48 in 1219 mm 18 in 457 mm 18 in 457 mm 12 in 305 mm Unit disconnect is mounted on panel No disconnect convenience outlet option Recommended service clearance Minimum clearance B 42 in 1067 mm...

Страница 7: ...om O ring Install the fitting body and torque to 96 10 in lb 10 9 1 Nm Do not exceed 106 in lb 11 9 Nm when tightening INSTALLATION Jobsite Survey Complete the following checks before installation 1 C...

Страница 8: ...ME MOUNTED INSTALLATION Frame mounted applications generally follow the sequence for a curb installation Adapt the sequence as required to suit spe cific installation plan Step 3 Inspect Unit Inspect...

Страница 9: ...9 Fig 6 Roof Curb Details REV 50TM500827...

Страница 10: ...al information Lifting holes are provided in base rails as shown in Fig 8 Re fer to rigging instructions on unit Before setting the unit onto the curb recheck gasketing on curb Rigging materials under...

Страница 11: ...iguration using accessory CRDUCTCV001A00 To convert to horizontal configuration remove screws from side duct opening covers see Fig 10 and remove covers Discard the supply duct cov er Install accessor...

Страница 12: ...to the basepan and remove In order to remove the screws it may be nec essary to remove the panel underneath the two position damper Locate and cut the 2 plastic tie wraps securing the assembly to the...

Страница 13: ...rflow configuration does not deter mine which drain connection to use Either drain connection can be used with vertical or horizontal applications When using the standard side drain connection ensure...

Страница 14: ...disconnects be sure to use 1 2 in screws to mount the disconnect directly to the end panel following the instruc tions on the Field Disconnect Warning label see Fig 25 In either case set the disconnec...

Страница 15: ...2 0 AWG copper only per pole Provide a ground fault and short circuit over current protection device fuse or breaker per NEC Article 440 or local codes Refer to unit informative data plate for MOCP Ma...

Страница 16: ...he pointer to be 3 75 to 3 88 in 95 to 99 mm for 80A and 100A NFD and 3 43 to 3 56 in 87 to 90 mm for 200A NFD 7 Tighten the locking screw to secure the shaft to the NFD 8 Turn the handle to the OFF p...

Страница 17: ...t side of the disconnect Be sure to create a drip loop at least 6 in long Fig 31 Powered Convenience Outlet Wiring Duty Cycle The unit powered convenience outlet has a duty cycle limita tion The trans...

Страница 18: ...duit between disconnect and control box 2 Install power lines to terminal connections as shown in Fig 26 FIELD CONTROL WIRING The 549J unit requires an external temperature control device This device...

Страница 19: ...ycle de mand is received Once de energized at the start of a Heating cy cle the reversing valves will remain de energized until the next cooling stage is initiated Compressor control The DFB receives...

Страница 20: ...see Fig 37 and Table 7 The de fault run period is 60 minutes for size 12 units Table 6 549J Defrost Board I O and Jumper Configurations POINT NAME TYPE OF I O CONNECTION PIN NUMBER UNIT CONNECTION NOT...

Страница 21: ...tie to ensure that the thermostat wire is tight and will not be damaged by contact with the condenser coil See Fig 38 NOTE If thru the bottom connections accessory is used refer to the accessory insta...

Страница 22: ...t Use the wiring procedure listed below for each heater as determined by the number of stages in the heater Single Stage Heaters Single stage heaters will have an orange and a brown control wire Conne...

Страница 23: ...ory Electric Heater Control Connections NOTE Optional Outdoor Temperature Control at One Heater Stage Move either heater wire to this terminal and connect outdoor temperature switch between second and...

Страница 24: ...24 Fig 42 Typical 549J Control Wiring Diagram...

Страница 25: ...25 Fig 43 Typical 549J Power Wiring Diagram 208 230 3 60 unit shown...

Страница 26: ...26 Fig 44 RTU Open Controller System Wiring Diagram...

Страница 27: ...are available with bus sensors User Interface The interface provides status for normal operation setup pa rameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display...

Страница 28: ...ft Terminal Block IAQ 2 10 2 10 VDC Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 VAC Air Quality Sensor 24 VAC Source ACT 2 10 2 10 VDC Damper Actuator Outp...

Страница 29: ...the list of menus Fig 49 W7220 Controller Navigation Buttons To use the keypad when working with Setpoints System and Advanced Settings Checkout tests and Alarms 1 Navigate to the desired menu 2 Press...

Страница 30: ...L HEAT HEAT PUMP MODE Displays COOL or HEAT when system is set to heat pump Non conventional COOL Y1 IN OFF ON OFF FIRST STAGE COOLING DEMAND Y1 IN Y1 I signal from space thermostat or unitary control...

Страница 31: ...F 43 C to 27 C increment by 1 F COMPRESSOR LOW TEMPERATURE LOCKOUT Set point determines outdoor temperature when the mechanical cooling cannot be turned on Commonly referred to as the Compressor locko...

Страница 32: ...e capacity of the RTU The value is found on the nameplate label for the specific unit AUX1 OUT NONE NONE ERV EXH2 SYS Select OUTPUT for AUX1 O relay NONE not configured output is not used ERV Energy R...

Страница 33: ...n damper to the full open position Exhaust fan contacts enable during the DAMPER OPEN test Make sure to pause in the mode to allow exhaust contacts to energize due to the delay in the system DAMPER CL...

Страница 34: ...ce actuator if damper is movable and supply voltage is between 21 6 V and 26 4 V Check actuator count on STATUS menu FREEZE ALARM N A N A Check if outdoor temperature is below the LOW Temp Lockout on...

Страница 35: ...2 Sensor 1 Speed Fan DCV OUTSIDE AIR GOOD TO ECONOMIZE Y1 I Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 Set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMI...

Страница 36: ...On Off High 0 v Off 0 v Off VENTMIN to Full Open Closed to Full Open On On High 24 v On 0 v Off VENTMIN to Full Open Closed to Full Open Above Set No Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX C...

Страница 37: ...ll Open Closed to Full Open On On High DELAY 24 v On 0 v Off MIN POS H to Full Open Closed to Full Open Table 21 Enthalpy Operation with Demand Controlled Ventilation DCV CO2 Sensor 2 Speed Fan DCV OU...

Страница 38: ...ation wiring dia grams For checkout review the Status of each configured pa rameter and perform the Checkout tests For information about menu navigation and use of the keypad see Interface Overview on...

Страница 39: ...n air smoke detectors are ar ranged for vertical return configurations only All components necessary for operation are factory provided and mounted The unit is factory configured for immediate smoke d...

Страница 40: ...ols Connec tions Board at terminals marked Smoke Shutdown Cut jumper JMP 3 when ready to energize unit ECONOMI ER IV OCCUPANCY SWITCH See Fig 53 for general EconoMi er IV wiring External occu pancy co...

Страница 41: ...the fan to increase ten sion Ensure the blower shaft and motor shaft are parallel to each other pulleys aligned Tighten all bolts securely when finished BELT TENSION METHOD Requires belt tension gage...

Страница 42: ...rves the right to change at any time specifications and designs without notice and without obligations Replaces II549J 12 02 2020 Carrier Cat No 04 53549013 01 Edition Date 6 2020 Printed in U S A For...

Страница 43: ...N _____ Verify that unit is level Y N _____ Check fan wheels and propeller for location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are prop...

Страница 44: ..._ L3 _____________ Supply Fan Amps L1 _____________ L2 _____________ L3 _____________ TEMPERATURES Outdoor air Temperature _____________ F DB Dry Bulb Return air Temperature _____________ F DB _______...

Отзывы: