background image

16

ALL UNITS
Test the GFCI receptacle by pressing the TEST button on the

face of the receptacle to trip and open the receptacle. Check for

proper grounding wires and power line phasing if the GFCI re

-

ceptacle does not trip as required. Press the RESET button to

clear the tripped condition. 

Unit-Mounted Convenience Outlets

Outlets will often require that 2  disconnects  be opened to de-

energize  all  power  to  the  unit.  Treat  all  units  as  electrically

energized until the convenience outlet power is also checked and

de-energization is confirmed. Observe National Electrical Code

Article 210, Branch Circuits, for use of convenience outlets.

Fuse on Power Type

The  factory  fuse  is  a  Bussman  “Fusetron”

1

  T-15,  non-

renewable screw-in (Edison base) type plug fuse. See Fig. 28

for maximum continuous use amp limitations.

Fig. 28 — Convenience Outlet Utilization Notice Label

FACTORY-OPTION THRU-BASE CONNECTIONS 

(ELECTRICAL CONNECTIONS)
This service connection kit consists of a 1/2

 

in. electrical bulk

-

head connector and a 1-1/2 in. electrical bulkhead connector,

connected  to  an  “L”  bracket  covering  the  embossed  (raised)

section  of  the  unit  basepan  in  the  condenser  section.  See

Fig. 29.  The  1/2  in.  bulkhead  connector  enables  the  low-

voltage control wires to pass through the basepan. The 1-1/2 in.

electrical  bulkhead  connector  allows  the  high-voltage  power

wires to pass through the basepan.

Fig. 29 — Thru-the-Base Option, Shipping Position

1. Remove the “L” bracket assembly from the unit.

2. Remove  connector  plate  assembly  from  the  “L”  bracket

and  discard  the  “L”  bracket,  but  retain  the  washer  head

screws  and  the  gasket  (located  between  the  “L”  bracket

and the connector plate assembly).

NOTE: Take care not to damage the gasket, as it is reused in the

following step.

3. Place the gasket over the embossed area in the basepan,

aligning the holes in the gasket to the holes in the basepan.

See Fig. 30.

4. Install the connector plate assembly to the basepan using

8 of the washer head screws.

NOTE: If electrical connections are not going to occur at this time,

tape or otherwise cover the fittings so that moisture does not get

into the building or conduit in the interim.

Fig. 30 — Completing Installation of Thru-the-Base Option

Check tightness of connector lock nuts before connecting elec

-

trical conduits.

Field-supplied and field-installed liquid tight conduit connectors

and conduit may be attached to the connectors on the basepan.

Pull correctly rated high voltage through appropriate conduits.

Connect the power conduit to the internal disconnect (if unit is

so equipped) or to the external disconnect (through unit side pan

-

el). A hole must be field cut in the main control box bottom on

the left side so the 24-v control connections can be made.

Connect the control power conduit to the unit control box at

this hole.

Units Without Thru-Base Connections

1. Install power wiring conduit through side panel openings.

Install conduit between disconnect and control box.

2. Install  power  lines  to  terminal  connections  as  shown  in

Fig. 22.

Field Control Wiring

The 547K*14 requires an external temperature control device.

This device can be a thermostat (field-supplied) or a thermostat

emulation  device  provided  as  part  of  a  third-party  Building

Management System.

Thermostat

Install a Bryant-approved accessory 2-stage Cooling/Heating ther

-

mostat  according  to  installation  instructions  included  with  the

accessory. If using an electronic thermostat, configure it for “non-

heat pump” operation. Locate the thermostat accessory on a solid

wall in the conditioned space to sense average temperature in ac

-

cordance with the thermostat installation instructions.

If the thermostat contains a logic circuit requiring 24-v power,

use a thermostat cable or equivalent single leads of different

colors with minimum of 7 leads. If the thermostat does not re

-

quire a 24-v source (no “C” connection required), use a ther

-

mostat  cable  or  equivalent  with  minimum  of  6 leads.  See

Fig. 31. Check the thermostat installation instructions for addi

-

tional  features  which  might  require  additional  conductors  in

the cable. For wire runs up to 50 ft (15 m), use no. 18 AWG

(American Wire Gauge) insulated wire 95°F (35°C minimum).

For 50 to 75 ft (15 to 23 m), use no. 16 AWG insulated wire

(35°C minimum). For over 75 ft (23 m), use no. 14 AWG insu

-

lated  wire  (35°C  minimum).  All  wire  sizes  larger  than

no. 18 AWG  cannot  be  directly  connected  to  the  thermostat

and will require a junction box and splice at the thermostat.

1. Bussman and Fusetron are trademarks of Cooper Technologies 

Company.

0.5” Electrical
Bulkhead
Connector

1.5” Electrical
Bulkhead
Connector

Gasket

Connector
Plate
Assembly

Содержание Legacy 547K 14

Страница 1: ...UT FUSES LOW VOLTAGE CONTROL CONNECTIONS CONTROL AND POWER WIRING DIAGRAMS EconoMi er X Factory Installed Option 24 PRODUCT DESCRIPTION SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL EC...

Страница 2: ...nt DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit...

Страница 3: ...Coil Options Round Tube Plate Fin Condenser Evaporator Hail Guard A Al Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louver...

Страница 4: ...4 Fig 2 547K 14 Unit Dimensional Drawing...

Страница 5: ...5 Fig 2 547K 14 Unit Dimensional Drawing cont...

Страница 6: ...ounting system that provides adequate height to allow for removal and disposal of frost and ice that will form during the heating defrost mode as well as allow installation of condensate trap per requ...

Страница 7: ...ter flashing as shown Ductwork must be attached to curb and not to the unit SLAB MOUNT HORIZONTAL UNITS ONLY Provide a level concrete slab that extends a minimum of 6 in 150 mm beyond unit cabinet Ins...

Страница 8: ...8 Fig 5 547K 14 Roof Curb Details...

Страница 9: ...ssary Fig 7 Retrofit Installation Dimensions If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb the hole in the curb must be moved...

Страница 10: ...filter access opening and assemble per the steps out lined in Economizer and Two Position Hood Setup on page 10 Fig 9 Typical Access Panel Locations Fig 10 Economizer Hood Package Location ECONOMIZER...

Страница 11: ...t 25 mm in 3 m of run Do not use a pipe size smaller than the unit connection 3 4 in Step 10 Make Electrical Connections NOTE Check all factory and field electrical connections for tight ness Field su...

Страница 12: ...how the wire routings If the field disconnect is larger than 100 A it must be attached to the unit using accessory CRDISBKT001A00 disconnect switch bracket see Fig 19 Follow the instructions provided...

Страница 13: ...ithin 2 and the current within 10 Use the following formula to de termine the percent of voltage imbalance Example Supply voltage is 230 3 60 Determine maximum deviation from average voltage AB 227 22...

Страница 14: ...hex screws on the NFD enclosure 12 Re install the unit front panel Fig 23 Location of Non Fused Disconnect Enclosure Fig 24 Handle and Shaft Assembly for NFD UNITS WITHOUT FACTORY INSTALLED NON FUSED...

Страница 15: ...x and mounted on a bracket behind the convenience outlet access is through the unit s control box access panel See Fig 25 The primary leads to the convenience outlet transformer are not factory connec...

Страница 16: ...ghtness of connector lock nuts before connecting elec trical conduits Field supplied and field installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan Pu...

Страница 17: ...33 Defrost Control Board Arrangement Reversing Valve Control The DFB has 2 outputs for unit reversing valve control Opera tion of the reversing valves is based on internal logic this application does...

Страница 18: ...s SW1 and SW2 see Fig 35 and Table 4 The de fault run period is 60 minutes Fig 35 DIP Switch Settings Defrost Board Table 3 547K Defrost Board I O and Jumper Configurations POINT NAME TYPE OF I O CONN...

Страница 19: ...rough ceramic insulators line break limit switches and a control contactor Heater modules are installed in the compartment below the in door supply fan outlet Access is through the electric heat acces...

Страница 20: ...60 A fuse regardless of actual heater ampacity so only 60 A fuses are necessary SINGLE POINT BOXES WITHOUT FUSES Unit heater applications not requiring supplemental fuses re quire a special single po...

Страница 21: ...21 Fig 41 Typical Control Wiring Diagram Electromechanical with W7220 Controller...

Страница 22: ...22 Fig 42 Typical Power Wiring Diagram 208 230 460 3 60 Unit Shown...

Страница 23: ...23 Fig 43 Typical Power Wiring Diagram 575 3 60 Unit Shown...

Страница 24: ...le includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor En thalpy and other options are available with bus sensors User Interface Provides status for normal operation setu...

Страница 25: ...24 Part 6 Table 5 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity Insensitive Connection OAT OA...

Страница 26: ...g 48 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings To use the keypad when working with menus Press the Up arrow button to mov...

Страница 27: ...rs MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the control sensor locat ed after the cooling coil in the fan section where it is desi...

Страница 28: ...ture Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature...

Страница 29: ...TILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with...

Страница 30: ...e NOTE If using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode g In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump on heat...

Страница 31: ...just for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay for t...

Страница 32: ...TUATOR STALLED Actuator stopped before achieving commanded position NOTE S a Table 9 illustrates the complete hierarchy Your menu parameters may be different depending on your configuration For exampl...

Страница 33: ...Economizer Operation FAN TYPE 2SPEED INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE W HEAT ON COOL Y1 IN COOL Y2 IN COOL Y1 OUT COOL Y2 OUT FAN SPEED reference only DAM...

Страница 34: ...en all of the OA conditions are above the selected bound ary the conditions are not good to economize and the mode is set to NO Figure 49 shows the 5 current boundaries There is also a high limit boun...

Страница 35: ...e to the Alarms menu at any time Clearing Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared from the display To clear an ala...

Страница 36: ...l and Medium Rooftop Units 2 to 25 Tons for discussions on additional control features of these smoke detectors including multiple unit coordination Fig 50 Return Air Smoke Detector Shipping Position...

Страница 37: ...ries Step 13 Fan Speed Set Up NOTE The Indoor Fan motor is equipped with an internal protec tion relay that is designed to disable unit operation if it detects a problem See Typical Wiring Diagram Fig...

Страница 38: ...4 6 1 6 4 6 8 7 2 7 6 8 0 8 4 8 8 9 2 0 4 0 6 6 5 6 8 7 2 7 5 7 9 8 3 8 7 9 1 0 4 0 8 6 9 7 2 7 6 7 9 8 2 8 6 9 0 0 4 1 0 7 3 7 6 7 9 8 2 8 6 0 4 1 2 7 6 7 9 8 2 8 6 0 4 1 4 8 0 8 3 8 6 0 4 1 6 1 8 2...

Страница 39: ...ing Valve Energized Check Valve A Closed Check Valve B Open Check Valve C Open Check Valve D Open Check Valve E Open Check Valve F Closed Check Valve G Closed Table 14 547K 14 Heating Mode COMPONENT S...

Страница 40: ...l installation of the unit Refer to the unit s Service Manual for detailed Pre Start and Start Up instructions Download the latest versions from HVAC Partners www hvacpartners com LPS LOC HPS Indoor C...

Страница 41: ......

Страница 42: ...reserves the right to change at any time specifications and designs without notice and without obligations Replaces New 2022 Carrier Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No I...

Страница 43: ...N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y N _____ Verify that unit is level Y N _____ Verify that fan assembly is free...

Страница 44: ...r Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No II547K 14 01 PRESSURES Refrigerant Suction ____________ PSIG Refrigerant Discharge ____________ PSIG Verify Refrigerant Charge using...

Отзывы: