Field  power  wires  are  connected  to  the  unit  at  line-side

pressure lugs at the main terminal block (TB1) or at factory-

installed option non-fused disconnect switch. See Fig. 21. Max

wire size is no. 2 AWG (copper only). See Fig. 22.

  

Fig. 21 — Disconnect Switch and Unit

Fig. 22 — Power Wiring Connections

TEST LEADS - Unit may be equipped with short leads (pig

-

tails) on the field line connection points off the optional dis

-

connect switch. These leads are for factory run-test purposes

only; remove and discard before connecting field power wires

to unit connection points. Make field power connections direct

-

ly to line connection pressure lugs only.
FIELD WIRING
All  field  wiring  must  comply  with  the  NEC  and  local

requirements.

All units except 208/230-v units are factory wired for the volt

-

age  shown  on  the  nameplate.  If  the  208/230-v  unit  is  to  be

connected  to  a  208-v  power  supply,  the  control  transformer

must be rewired by moving the black wire with the 1/4 in. fe

-

male spade connector from the 230-v connection and moving it

to the 200-v 1/4 in. male terminal on the primary side of the

transformer. Refer to unit label diagram for additional informa

-

tion.

Size wire based on MCA (Minimum Circuit Amps) on the unit

informative plate. See Fig. 22 and the unit label diagram for

power  wiring  connections  to  the  unit  power  terminal  blocks

and  equipment  ground.  Maximum  wire  size  is  2/0 AWG  per

pole.

Provide a ground-fault and short-circuit over-current protection

device (fuse or breaker) per NEC Article 440 (or local codes).

Refer  to  unit  informative  data  plate  for  MOCP  (Maximum

Overcurrent Protection) device size.

Voltage  to  compressor  terminals  during  operation  must  be

within voltage range indicated on unit nameplate. On 3

-

phase

units,  voltages  between  phases  must  be  balanced  within  2%

and the current within 10%. Use the following formula to de

-

termine the percent of voltage imbalance.

Example: Supply voltage is 230-3-60

Determine maximum deviation from average voltage.

(AB) 227-224 = 3 v

(BC) 231-227 = 4 v

(AC) 227-226 = 1 v

Maximum deviation is 4 v.

Determine percent of voltage imbalance.

This  amount  of  phase  imbalance  is  satisfactory  as  it  is  below  the

maximum allowable 2%.

UNITS WITH FACTORY-INSTALLED NON-FUSED 

DISCONNECT
The  factory-installed  optional  non-fused  disconnect  (NFD)

switch is located in a weatherproof enclosure located under the

main  control  box.  The  manual  switch  handle  and  shaft  are

shipped  in  the  disconnect  enclosure. Assemble  the  shaft  and

handle to the switch at this point. Discard the factory test leads

(see Fig. 23).

Connect field power supply conductors to LINE side terminals

when  the  switch  enclosure  cover  is  removed  to  attach  the

handle.

WARNING

FIRE HAZARD

Failure  to  follow  this  warning  could  result  in  personal

injury, death, or property damage.

Do not connect aluminum wire between disconnect switch

and unit. Use only copper wire.

Copper

Wire Only

Electric

Disconnect

Switch

Aluminum

Wire

Units Without Disconnect Option

Units With Disconnect Option

2

4

6

1

3

5

L1

L2

L3

Optional

Disconnect

Switch

Disconnect factory test leads; discard.

Factory

Wiring

11

12

13

L1

L2

L3

TB1

208/230-3-60

460-3-60
575-3-60

Disconnect

per

NEC

% Voltage 

Imbalance = 100 x

max voltage deviation from average voltage

average voltage

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

=

227

3

3

% Voltage Imbalance = 100x

4

= 1.78%

227

IMPORTANT: If the supply voltage phase imbalance is more than 2%,

contact your local electric utility company immediately.

CAUTION

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment

damage.

Operation on improper line voltage or excessive phase im

-

balance constitutes abuse and may cause damage to electri

-

cal components. Such operation would invalidate any ap

-

plicable Bryant warranty.

MOTOR

Содержание Legacy 547K 14

Страница 1: ...UT FUSES LOW VOLTAGE CONTROL CONNECTIONS CONTROL AND POWER WIRING DIAGRAMS EconoMi er X Factory Installed Option 24 PRODUCT DESCRIPTION SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL EC...

Страница 2: ...nt DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit...

Страница 3: ...Coil Options Round Tube Plate Fin Condenser Evaporator Hail Guard A Al Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louver...

Страница 4: ...4 Fig 2 547K 14 Unit Dimensional Drawing...

Страница 5: ...5 Fig 2 547K 14 Unit Dimensional Drawing cont...

Страница 6: ...ounting system that provides adequate height to allow for removal and disposal of frost and ice that will form during the heating defrost mode as well as allow installation of condensate trap per requ...

Страница 7: ...ter flashing as shown Ductwork must be attached to curb and not to the unit SLAB MOUNT HORIZONTAL UNITS ONLY Provide a level concrete slab that extends a minimum of 6 in 150 mm beyond unit cabinet Ins...

Страница 8: ...8 Fig 5 547K 14 Roof Curb Details...

Страница 9: ...ssary Fig 7 Retrofit Installation Dimensions If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb the hole in the curb must be moved...

Страница 10: ...filter access opening and assemble per the steps out lined in Economizer and Two Position Hood Setup on page 10 Fig 9 Typical Access Panel Locations Fig 10 Economizer Hood Package Location ECONOMIZER...

Страница 11: ...t 25 mm in 3 m of run Do not use a pipe size smaller than the unit connection 3 4 in Step 10 Make Electrical Connections NOTE Check all factory and field electrical connections for tight ness Field su...

Страница 12: ...how the wire routings If the field disconnect is larger than 100 A it must be attached to the unit using accessory CRDISBKT001A00 disconnect switch bracket see Fig 19 Follow the instructions provided...

Страница 13: ...ithin 2 and the current within 10 Use the following formula to de termine the percent of voltage imbalance Example Supply voltage is 230 3 60 Determine maximum deviation from average voltage AB 227 22...

Страница 14: ...hex screws on the NFD enclosure 12 Re install the unit front panel Fig 23 Location of Non Fused Disconnect Enclosure Fig 24 Handle and Shaft Assembly for NFD UNITS WITHOUT FACTORY INSTALLED NON FUSED...

Страница 15: ...x and mounted on a bracket behind the convenience outlet access is through the unit s control box access panel See Fig 25 The primary leads to the convenience outlet transformer are not factory connec...

Страница 16: ...ghtness of connector lock nuts before connecting elec trical conduits Field supplied and field installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan Pu...

Страница 17: ...33 Defrost Control Board Arrangement Reversing Valve Control The DFB has 2 outputs for unit reversing valve control Opera tion of the reversing valves is based on internal logic this application does...

Страница 18: ...s SW1 and SW2 see Fig 35 and Table 4 The de fault run period is 60 minutes Fig 35 DIP Switch Settings Defrost Board Table 3 547K Defrost Board I O and Jumper Configurations POINT NAME TYPE OF I O CONN...

Страница 19: ...rough ceramic insulators line break limit switches and a control contactor Heater modules are installed in the compartment below the in door supply fan outlet Access is through the electric heat acces...

Страница 20: ...60 A fuse regardless of actual heater ampacity so only 60 A fuses are necessary SINGLE POINT BOXES WITHOUT FUSES Unit heater applications not requiring supplemental fuses re quire a special single po...

Страница 21: ...21 Fig 41 Typical Control Wiring Diagram Electromechanical with W7220 Controller...

Страница 22: ...22 Fig 42 Typical Power Wiring Diagram 208 230 460 3 60 Unit Shown...

Страница 23: ...23 Fig 43 Typical Power Wiring Diagram 575 3 60 Unit Shown...

Страница 24: ...le includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor En thalpy and other options are available with bus sensors User Interface Provides status for normal operation setu...

Страница 25: ...24 Part 6 Table 5 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity Insensitive Connection OAT OA...

Страница 26: ...g 48 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings To use the keypad when working with menus Press the Up arrow button to mov...

Страница 27: ...rs MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the control sensor locat ed after the cooling coil in the fan section where it is desi...

Страница 28: ...ture Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature...

Страница 29: ...TILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with...

Страница 30: ...e NOTE If using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode g In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump on heat...

Страница 31: ...just for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay for t...

Страница 32: ...TUATOR STALLED Actuator stopped before achieving commanded position NOTE S a Table 9 illustrates the complete hierarchy Your menu parameters may be different depending on your configuration For exampl...

Страница 33: ...Economizer Operation FAN TYPE 2SPEED INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE W HEAT ON COOL Y1 IN COOL Y2 IN COOL Y1 OUT COOL Y2 OUT FAN SPEED reference only DAM...

Страница 34: ...en all of the OA conditions are above the selected bound ary the conditions are not good to economize and the mode is set to NO Figure 49 shows the 5 current boundaries There is also a high limit boun...

Страница 35: ...e to the Alarms menu at any time Clearing Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared from the display To clear an ala...

Страница 36: ...l and Medium Rooftop Units 2 to 25 Tons for discussions on additional control features of these smoke detectors including multiple unit coordination Fig 50 Return Air Smoke Detector Shipping Position...

Страница 37: ...ries Step 13 Fan Speed Set Up NOTE The Indoor Fan motor is equipped with an internal protec tion relay that is designed to disable unit operation if it detects a problem See Typical Wiring Diagram Fig...

Страница 38: ...4 6 1 6 4 6 8 7 2 7 6 8 0 8 4 8 8 9 2 0 4 0 6 6 5 6 8 7 2 7 5 7 9 8 3 8 7 9 1 0 4 0 8 6 9 7 2 7 6 7 9 8 2 8 6 9 0 0 4 1 0 7 3 7 6 7 9 8 2 8 6 0 4 1 2 7 6 7 9 8 2 8 6 0 4 1 4 8 0 8 3 8 6 0 4 1 6 1 8 2...

Страница 39: ...ing Valve Energized Check Valve A Closed Check Valve B Open Check Valve C Open Check Valve D Open Check Valve E Open Check Valve F Closed Check Valve G Closed Table 14 547K 14 Heating Mode COMPONENT S...

Страница 40: ...l installation of the unit Refer to the unit s Service Manual for detailed Pre Start and Start Up instructions Download the latest versions from HVAC Partners www hvacpartners com LPS LOC HPS Indoor C...

Страница 41: ......

Страница 42: ...reserves the right to change at any time specifications and designs without notice and without obligations Replaces New 2022 Carrier Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No I...

Страница 43: ...N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y N _____ Verify that unit is level Y N _____ Verify that fan assembly is free...

Страница 44: ...r Cat No 04 53547013 01 Edition Date 6 22 Printed in U S A Form No II547K 14 01 PRESSURES Refrigerant Suction ____________ PSIG Refrigerant Discharge ____________ PSIG Verify Refrigerant Charge using...

Отзывы: