3
PHYSICAL DATA
UNIT SIZE --- SERIES
018---A
024---A
030---A
036---A
042---A
048---A
060---A
Operating Weight (lb)
159
160
208
211
233
269
295
Shipping Weight (lb)
184
185
240
242
262
300
327
Compressor Type
Scroll
REFRIGERANT
Freon
®
(R---22)
Control
TXV (R---22 Hard Shutoff)
Charge (lb)
5.5
6
7.5
8
10
14
15.5
COND FAN
Propeller Type, Direct Drive
Air Discharge
Vertical
Air Qty. (CFM)
2233
2614
2614
3334
3334
4046
4046
Motor HP
1/12
1/10
1/10
1/8
1/8
1/5
1/5
Motor RPM
800
1100
1100
800
800
800
800
COND COIL
Face Area (Sq. ft.)
15.09
15.09
25.87
22.63
17.6
22.63
25.15
Fins per In.
20
20
20
20
20
20
20
Rows
1
1
1
1
2
2
2
Circuits
5
6
6
6
7
8
9
VALVE CONNECT. (In. ID)
Vapor
5/8”
5/8”
3/4”
3/4”
7/8”
7/8”
7/8”
Liquid
3/8”
REFRIGERANT TUBES* (In. OD)
Vapor (0---80 Ft. Tube Length)
5/8”
5/8”
3/4”
3/4”
7/8”
7/8”
1---1/8”
Liquid (0---80 Ft. Tube Length)
3/8”
* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.
Note
: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
1--STAGE HEAT PUMP APPLICATIONS
LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80
ft. or when there is more than 20 Ft. vertical separation between
indoor and outdoor units. These applications require additional
accessories and system modifications for reliable system
operation. The maximum allowable total equivalent length is 250
ft. The maximum vertical separation is 200 ft. when outdoor unit
is above indoor unit, and 60 ft. when the outdoor unit is below
the indoor unit. Refer to Accessory Usage Guideline below for
required accessories. See Long--Line Application Guideline for
required piping and system modifications. Also, refer to the table
below for the acceptable vapor tube diameters based on the total
length to minimize the cooling capacity loss.
Unit Nominal Size (Btuh)
Acceptable Vapor
Line Diameter OD
(in.)
Cooling Capacity Loss (%)
Total Equivalent Line Length (ft.)
Standard Application
Long Line Application
Requires Accessories
25
50
80
80+
100
125
150
175
200
225
250
18000
R---22 HP
5/8
0
1
1
1
2
3
3
4
5
5
6
3/4
0
0
0
0
0
1
1
1
1
2
2
24000
R---22 HP
5/8
0
1
3
3
3
5
6
7
8
9
10
3/4
0
0
0
0
1
1
1
2
2
3
3
30000
R---22 HP
3/4
0
1
1
1
2
3
3
4
5
5
6
7/8
0
0
0
0
1
1
1
2
2
2
3
36000
R---22 HP
3/4
0
1
2
2
3
4
5
6
7
8
9
7/8
0
0
1
1
1
2
2
3
3
4
4
42000
R---22 HP
7/8
0
1
1
1
2
2
3
4
4
5
5
48000
R---22 HP
7/8
0
1
2
2
2
3
4
5
5
6
7
60000
R---22 HP
7/8
1
2
3
3
4
5
7
8
9
10
11
1 1/8
0
0
1
1
1
1
2
2
2
3
3
Standard Length = 80 ft. or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See
Long Line Application Guidelines
213R