PHYSICAL DATA

UNIT SIZE --- SERIES

018---A

024---A

030---A

036---A

042---A

048---A

060---A

Operating Weight (lb)

159

160

208

211

233

269

295

Shipping Weight (lb)

184

185

240

242

262

300

327

Compressor Type

Scroll

REFRIGERANT

Freon

®

(R---22)

Control

TXV (R---22 Hard Shutoff)

Charge (lb)

5.5

6

7.5

8

10

14

15.5

COND FAN

Propeller Type, Direct Drive

Air Discharge

Vertical

Air Qty. (CFM)

2233

2614

2614

3334

3334

4046

4046

Motor HP

1/12

1/10

1/10

1/8

1/8

1/5

1/5

Motor RPM

800

1100

1100

800

800

800

800

COND COIL

Face Area (Sq. ft.)

15.09

15.09

25.87

22.63

17.6

22.63

25.15

Fins per In.

20

20

20

20

20

20

20

Rows

1

1

1

1

2

2

2

Circuits

5

6

6

6

7

8

9

VALVE CONNECT. (In. ID)

Vapor

5/8”

5/8”

3/4”

3/4”

7/8”

7/8”

7/8”

Liquid

3/8”

REFRIGERANT TUBES* (In. OD)

Vapor (0---80 Ft. Tube Length)

5/8”

5/8”

3/4”

3/4”

7/8”

7/8”

1---1/8”

Liquid (0---80 Ft. Tube Length)

3/8”

* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.

Note

: See unit Installation Instruction for proper installation.

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

1--STAGE HEAT PUMP APPLICATIONS

LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80

ft. or when there is more than 20 Ft. vertical separation between
indoor and outdoor units. These applications require additional

accessories and system modifications for reliable system

operation. The maximum allowable total equivalent length is 250
ft. The maximum vertical separation is 200 ft. when outdoor unit

is above indoor unit, and 60 ft. when the outdoor unit is below
the indoor unit. Refer to Accessory Usage Guideline below for

required accessories. See Long--Line Application Guideline for
required piping and system modifications. Also, refer to the table

below for the acceptable vapor tube diameters based on the total

length to minimize the cooling capacity loss.

Unit Nominal Size (Btuh)

Acceptable Vapor

Line Diameter OD

(in.)

Cooling Capacity Loss (%)

Total Equivalent Line Length (ft.)

Standard Application

Long Line Application

Requires Accessories

25

50

80

80+

100

125

150

175

200

225

250

18000

R---22 HP

5/8

0

1

1

1

2

3

3

4

5

5

6

3/4

0

0

0

0

0

1

1

1

1

2

2

24000

R---22 HP

5/8

0

1

3

3

3

5

6

7

8

9

10

3/4

0

0

0

0

1

1

1

2

2

3

3

30000

R---22 HP

3/4

0

1

1

1

2

3

3

4

5

5

6

7/8

0

0

0

0

1

1

1

2

2

2

3

36000

R---22 HP

3/4

0

1

2

2

3

4

5

6

7

8

9

7/8

0

0

1

1

1

2

2

3

3

4

4

42000

R---22 HP

7/8

0

1

1

1

2

2

3

4

4

5

5

48000

R---22 HP

7/8

0

1

2

2

2

3

4

5

5

6

7

60000

R---22 HP

7/8

1

2

3

3

4

5

7

8

9

10

11

1 1/8

0

0

1

1

1

1

2

2

2

3

3

Standard Length = 80 ft. or less total equivalent length

Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines

Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See

Long Line Application Guidelines

213R

Содержание LEGACY 213R

Страница 1: ...sor S Filter drier S Loss of charge pressure switch S Balanced refrigeration system for maximum reliability Durability DuraGuardt protection package S Solid Durable sheet metal construction S Wire coi...

Страница 2: ...ling Systems has determined that this product meets the ENERGY STAR guidelines for energy efficiency Refer to the combination ratings in Product Data for system combinations that meet Energy Star guid...

Страница 3: ...ations for reliable system operation The maximum allowable total equivalent length is 250 ft The maximum vertical separation is 200 ft when outdoor unit is above indoor unit and 60 ft when the outdoor...

Страница 4: ...sion kit is a 24 vac accessory that can turn a 4 wire thermostat application into a 5 wire application This kit can also be used to replace a broken thermostat wire or add an extra wire when needed Th...

Страница 5: ...applications 5 Cycle Protector The cycle protector is designed to prevent compressor short cycling This control provides an approximate 5 minute delay after power to the compressor has been interrupte...

Страница 6: ...low the second stage set point Usage Guideline Outdoor thermostat applications where electric heater is capable of 3 stage operation 14 Sound Hood Wraparound sound reducing cover for the compressor Re...

Страница 7: ...10 AWG or smaller stranded wire for larger than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for vo...

Страница 8: ...8 DIMENSIONS NOTE Optional G dense coil guard shown 213R...

Страница 9: ...BUILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH 0 0 2 9 5 9 8 8 11 7 14 6 17 6 20 5 23 4 kW 213RN A G 024A FA4CNF024 213RN A G 030A FA4CNF030 213RN A G 036A FC4DNF036 A05007 213RN A G 042A...

Страница 10: ...A 17 300 TDR TXV 14 00 12 00 15 600 3 84 9 900 2 52 8 5 355AAV042060 CNRH 2417A 17 400 TDR TXV 14 00 12 00 15 600 3 82 9 900 2 52 8 5 355AAV042080 CNRH 2417A 17 400 TDR TXV 14 00 12 00 15 600 3 84 9 9...

Страница 11: ...V 14 00 11 70 20 600 3 60 13 700 2 52 8 4 355AAV060100 CNRH 3017A 22 800 TDR TXV 14 00 11 70 20 600 3 60 13 700 2 50 8 2 355AAV060120 CNRH 3017A 22 800 TDR TXV 14 00 11 70 20 600 3 60 13 700 2 50 8 2...

Страница 12: ...J AV036070 CNRV 3017A 28 600 TXV 13 00 10 50 29 600 3 44 18 900 2 44 8 1 CNRV 3017A 28 400 TDR TXV 14 00 11 50 29 200 3 52 18 000 2 50 8 2 355AAV042060 CNRV 3017A 28 400 TDR TXV 14 00 11 50 29 200 3 5...

Страница 13: ...4 355AAV060120 CSRH 3612A 28 600 TDR TXV 14 00 11 50 28 800 3 62 18 100 2 54 8 4 315 A J AV036070 CSRH 3612A 28 600 TDR TXV 14 00 11 70 28 800 3 64 18 000 2 56 8 5 315 A J AV048090 CSRH 3612A 28 600 T...

Страница 14: ...20 11 00 35 000 3 50 21 000 2 46 8 2 355AAV042040 CSRH 3612A 33 400 TDR TXV 13 50 11 20 34 800 3 52 20 800 2 48 8 2 355AAV042060 CSRH 3612A 33 400 TDR TXV 13 20 11 00 35 000 3 48 21 000 2 44 8 1 355A...

Страница 15: ...4 00 11 50 41 000 3 64 25 400 2 58 8 1 315 A J AV060110 CNRV 4824A 42 000 TXV 13 00 10 80 42 500 3 58 26 400 2 48 7 9 CNRV 4824A 41 500 TDR TXV 13 50 11 20 41 500 3 56 25 600 2 52 7 9 355AAV042040 CNR...

Страница 16: ...00 3 30 29 400 2 52 8 2 FK4DNB006 47 000 TDR TXV 14 00 11 50 47 500 3 42 29 400 2 58 8 4 CAR 4817A 43 500 TDR TXV 13 00 10 80 46 500 3 24 29 800 2 46 8 1 315 A J AV048090 CAR 4821A 44 500 TDR TXV 13 0...

Страница 17: ...5AAV060100 CSRH 6012A 46 000 TDR TXV 13 50 11 20 47 500 3 26 29 600 2 50 8 1 355AAV060120 CSRH 6012A 46 000 TDR TXV 13 50 11 20 47 500 3 28 29 600 2 50 8 2 315 A J AV048090 CSRH 6012A 46 000 TDR TXV 1...

Страница 18: ...4 1 67 14 42 14 42 1 86 13 76 13 76 2 06 675 72 20 63 11 24 1 25 19 87 10 95 1 39 19 07 10 66 1 54 18 23 10 35 1 71 17 35 10 04 1 90 16 43 9 70 2 11 67 18 77 14 41 1 25 18 05 14 11 1 38 17 28 13 79 1...

Страница 19: ...0 94 FK4DNF002 1 03 0 95 FK4DNF003 1 03 0 95 CAR 2414A 1 01 1 01 CAR 2417A 1 01 1 01 CAR 3014A 1 01 1 01 CAR 3017A 1 01 1 01 CNRF 2418A 1 01 1 01 CNRH 2417A 1 01 1 01 CNRH 3017A 1 01 1 01 CNRV 2414A 1...

Страница 20: ...1 01 1 04 CAR 3621A 1 01 1 04 CNRF 3618A 1 01 1 04 CNRH 3017A 1 01 1 04 CNRH 3617A 1 01 1 04 CNRV 3014A 1 01 1 04 CNRV 3017A 1 01 1 04 CNRV 3617A 1 01 1 04 CNRV 3621A 1 01 1 04 CSRH 3012A 1 01 1 04 CS...

Страница 21: ...AV036070 CNRH 4221A 0 99 0 99 315 A J AV036070 CSRH 3612A 0 98 0 98 315 A J AV036070 CSRH 4212A 0 98 0 98 315 A J AV036070 CAR 3617A 0 98 0 98 315 A J AV048090 CNRH 3617A 0 98 0 98 315 A J AV048090 C...

Страница 22: ...315 A J AV036070 CSRH 4212A 0 98 0 96 315 A J AV036070 CSRH 4812A 1 00 0 98 315 A J AV036070 CAR 4817A 1 00 0 98 315 A J AV048090 CNRH 4221A 0 98 0 96 315 A J AV048090 CNRH 4821A 1 00 0 98 315 A J AV0...

Страница 23: ...8 46 38 46 5 60 57 46 72 46 72 3 34 45 23 45 23 3 71 43 67 43 67 4 12 42 02 42 02 4 57 40 29 40 29 5 06 38 47 38 47 5 60 Cooling Indoor Model Capacity Power Furnace Model FC4DN F B 048 1 00 1 00 FC4DN...

Страница 24: ...5 5 53 63 10 35 87 6 05 60 01 34 75 6 61 56 79 33 60 7 21 67 65 44 49 83 4 58 62 86 48 76 5 00 60 20 47 66 5 46 57 46 46 53 5 97 54 61 45 35 6 52 51 65 44 13 7 13 63 60 91 48 02 4 53 58 49 46 94 4 95...

Страница 25: ...17 40 17 40 1 50 16 62 16 62 1 48 15 45 15 45 1 45 75 525 9 19 8 45 1 37 11 68 10 73 1 44 14 53 13 25 1 51 17 67 15 70 1 60 19 47 17 72 1 65 19 53 19 53 1 65 19 14 19 14 1 63 18 57 18 57 1 61 600 9 3...

Страница 26: ...7A 0 87 0 93 CNRF 2418A 1 00 0 96 CNRH 2417A 1 00 0 96 CNRH 3017A 0 87 0 93 CNRV 2414A 1 00 0 96 CNRV 2417A 1 00 0 96 CNRV 3014A 0 87 0 93 CNRV 3017A 0 87 0 93 CSRH 2412A 0 97 0 96 CSRH 3012A 0 85 0 9...

Страница 27: ...98 0 98 CNRV 3017A 0 98 0 98 CNRV 3617A 0 97 0 97 CNRV 3621A 0 97 0 97 CSRH 3012A 0 98 0 98 CSRH 3612A 0 96 0 95 CAR 3014A 0 97 0 95 315 A J AV036070 CAR 3614A 0 97 0 94 315 A J AV036070 CNRH 3017A 0...

Страница 28: ...97 315 A J AV036070 CAR 3617A 1 00 1 01 315 A J AV048090 CNRH 3617A 1 00 1 02 315 A J AV048090 CNRH 4221A 0 99 0 98 315 A J AV048090 CNRV 3617A 1 00 1 02 315 A J AV048090 CSRH 3612A 0 99 0 97 315 A J...

Страница 29: ...A 0 99 0 99 315 A J AV048090 CNRH 4221A 0 96 0 99 315 A J AV048090 CNRH 4821A 0 98 0 98 315 A J AV048090 CSRH 4212A 0 98 0 98 315 A J AV048090 CSRH 4812A 0 99 0 99 315 A J AV048090 CAR 4221A 0 98 1 01...

Страница 30: ...43 63 79 63 79 4 64 Heating Indoor Model Capacity Power Furnace Model FC4DN F B 048 1 00 1 00 FC4DN F B 048 1 01 1 01 FC4DN F B 060 1 01 0 99 FK4DNB006 0 99 0 98 FK4DNF005 0 99 1 02 CAR 4817A 0 97 1...

Страница 31: ...0 5 07 2250 25 67 23 62 4 22 31 26 28 73 4 35 37 37 34 07 4 51 44 05 39 12 4 67 51 64 46 99 4 83 58 08 58 08 4 98 60 16 60 16 5 02 57 77 57 77 4 95 75 1750 24 36 22 41 4 27 30 00 27 57 4 45 36 07 32 8...

Страница 32: ...n resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with steel wire safety guards Compressor Compressor will be hermetically sealed Compressor wi...