24
DETAILED COOLING CAPACITIES -- CONTINUED
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75
85
95
105
115
125
CFM
EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
213RNA060---A Outdoor Section With FC4DNF060 Indoor Section
1750
72
69.61 35.82
4.46
67.00 34.80
4.88
64.31 33.76
5.34
61.53 32.71
5.85
58.62 31.62
6.41
55.59 30.48
7.02
67
63.45 44.44
4.39
61.04 43.40
4.81
58.55 42.34
5.27
55.98 41.25
5.78
53.30 40.13
6.33
50.49 38.96
6.93
63
58.99 42.98
4.34
56.74 41.94
4.76
54.40 40.87
5.21
51.98 39.77
5.72
49.46 38.64
6.27
46.83 37.46
6.87
62
57.89 52.98
4.33
55.72 51.90
4.74
53.47 50.76
5.20
51.16 49.56
5.71
48.78 48.25
6.26
46.47 46.47
6.87
57
56.07 56.07
4.31
54.33 54.33
4.73
52.50 52.50
5.19
50.59 50.59
5.70
48.58 48.58
6.26
46.47 46.47
6.87
2000
72
70.84 37.47
4.56
68.11 36.44
4.98
65.32 35.40
5.44
62.44 34.33
5.95
59.43 33.22
6.51
56.30 32.08
7.12
67
64.59 47.19
4.49
62.08 46.14
4.91
59.50 45.06
5.36
56.84 43.96
5.87
54.05 42.81
6.43
51.16 41.61
7.03
63
60.09 45.56
4.44
57.75 44.51
4.85
55.31 43.42
5.31
52.80 42.30
5.82
50.19 41.14
6.37
47.48 39.94
6.97
62
59.16 56.66
4.43
56.93 55.47
4.84
54.66 54.15
5.30
52.43 52.43
5.81
50.30 50.30
6.37
48.06 48.06
6.98
57
58.28 58.28
4.42
56.43 56.43
4.84
54.48 54.48
5.30
52.44 52.44
5.81
50.31 50.31
6.37
48.06 48.06
6.98
2250
72
71.75 39.04
4.66
68.93 38.00
5.07
66.06 36.95
5.53
63.10 35.87
6.05
60.01 34.75
6.61
56.79 33.60
7.21
67
65.44 49.83
4.58
62.86 48.76
5.00
60.20 47.66
5.46
57.46 46.53
5.97
54.61 45.35
6.52
51.65 44.13
7.13
63
60.91 48.02
4.53
58.49 46.94
4.95
55.99 45.83
5.40
53.41 44.69
5.91
50.74 43.50
6.46
47.96 42.27
7.06
62
60.29 59.79
4.53
58.14 58.14
4.94
56.08 56.08
5.41
53.95 53.95
5.92
51.71 51.71
6.48
49.36 49.36
7.09
57
60.11 60.11
4.53
58.14 58.14
4.94
56.09 56.09
5.41
53.95 53.95
5.92
51.72 51.72
6.48
49.36 49.36
7.09
Cooling Indoor Model
Capacity
Power
Furnace Model
*FC4DN(F,B)060
1.00
1.00
FK4DNB006
0.98
0.97
CAR**6024A**
0.97
0.97
315(A,J)AV066135
CSRH*6012A**
0.97
0.97
315(A,J)AV066135
CAR**6024A**
0.97
0.97
315(A,J)AV066155
CNRH*6024A**
0.97
0.97
315(A,J)AV066155
CNRV*6024A**
0.97
0.97
315(A,J)AV066155
CSRH*6012A**
0.97
0.97
315(A,J)AV066155
NOTE
: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
{
Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}
Sensible capacities shown are based on 80
_
F (27
_
C) entering air at the indoor coil. For sensible capacities at other than 80
_
F (27
_
C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80
_
F (27
_
C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80
_
F (27
_
C).
** System kw is total of indoor and outdoor unit kilowatts.
{{
At TVA rating indoor condition (75
_
F edb/63
_
F ewb). All other indoor air temperatures are at 80
_
F edb.
EWB
— Entering Wet Bulb
213R