background image

11

FINAL CHECKS

IMPORTANT

: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub--through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and

covers.

3. Tighten service valve stem caps to 1/12--turn past finger

tight.

4. Leave Owner’s Manual with owner. Explain system opera-

tion and periodic maintenance requirements outlined in

manual.

5. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible
equipment failure, periodic maintenance must be performed on this

equipment.
Frequency of maintenance may vary depending upon geographic

areas, such as coastal applications. See Users Manual for

information.

213B

/215B

Содержание Legacy 213B

Страница 1: ...nnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and...

Страница 2: ...PAN Dimension in mm TIEDOWN KNOCKOUT LOCATIONS in mm A B C 26 X 26 660 X 660 9 1 8 231 8 4 7 16 112 7 21 1 4 539 8 31 1 2 X 31 1 2 800 X 800 9 1 8 231 8 6 9 16 166 7 24 11 16 627 1 35 X 35 889 X 889 9...

Страница 3: ...rigerant tubing to fittings on outdoor unit vapor and liquid service valves Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth tubing set can be...

Страница 4: ...r any sheet metal Pay close attention to feeder tubes makings sure wire ties on feeder tubes are secure and tight Be sure field wiring complies with local and national fire safety and electrical codes...

Страница 5: ...stalling Start Up CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury Wear safety glasses protective clothing and gloves when handling refrigerant and observe t...

Страница 6: ...imer starts only when the defrost thermostat is closed and the contactor is energized Defrost mode is identical to cooling mode except that outdoor fan motor stops and second stage heat is turned on t...

Страница 7: ...rating plate for required subcooling temperat ure 5 Refer to Table 7 Find the point where required subcooling temperature intersects measured liquid service valve pres sure 6 To obtain required subcoo...

Страница 8: ...7A 5 3 CSPH 3012A 3 3 FB4CNF030 TXV 3 FF1ENP030 3 FF1ENP031 3 FX4DN B F 031 5 5 CAP 36 A 5 3 CNP 36 A 3 CNPV 3717A 5 3 CSPH 3612A 5 3 FB4CNF036 TXV FV4C FE4A N B F 003 5 5 3 FF1ENP036 5 3 FF1ENP037 5...

Страница 9: ...AP 30 A CNP 30 A CNP 3117A CSPH 3012A FB4CNF030 TXV FF1ENP030 FF1ENP031 FX4DN B F 031 3 CAP 36 A CNP 36 A CNPV 3717A CSPH 3612A FB4CNF036 TXV FV4C FE4A N B F 003 FF1ENP036 FF1ENP037 FX4DN B F 037 5 CA...

Страница 10: ...21 22 23 23 23 23 65 3 7 12 18 19 21 21 22 22 70 7 14 16 18 20 20 20 75 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 1...

Страница 11: ...ce valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Ch...

Страница 12: ...ll a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter...

Отзывы: