ELECTRICAL DATA
UNIT SIZE ---
VOLTAGE,
SERIES
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MIN
WIRE
SIZE†
MIN WIRE
SIZE†
MAX
LENGTH
ft. (m)‡
MAX
LENGTH
ft. (m)‡
MAX
FUSE**
or CKT
BRK
AMPS
MAX
MIN
LRA
RLA
FLA
60° C
75° C
60° C
75° C
018---B
208/230/1
253
197
48.0
9.0
0.5
11.7
14
14
67 (20.4)
64 (19.5)
20
024---B
58.3
13.5
0.8
17.6
14
14
44 (13.4)
42 (12.8)
30
030---B
73.0
14.1
1.1
18.7
14
14
42 (12.8)
40 (12.2)
30
036---B
79.0
16.7
1.1
21.9
12
12
57 (17.4)
54 (16.5)
35
042---B
109.0
19.9
1.2
26.0
10
10
76 (23.2)
73 (22.3)
40
048---B
117.0
21.8
1.2
28.4
10
10
70 (21.3)
66 (20.1)
40
060---C
134.0
26.3
1.2
34.1
8
10
91 (27.7)
55 (16.8)
50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
If wire is applied at ambient greater than 30
_
C (86
_
F), consult table 310---16 of the NEC---2008 (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed
cable (NM), trade name ROMEX, shall be that of 60
_
C (140
_
F) conditions, per the NEC (ANSI/NFPA 70) Article 334.80. If other than uncoated (no---plated),
60 or 75
_
C (140 or 167
_
F) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable
tables of the NEC (ANSI/NFPA 70).
}
Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2001 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER LEVEL (dBA)
UNIT SIZE ---
VOLTAGE, SERIES
STANDARD RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
018---B
75
50.0
59.0
65.5
69.5
64.5
61.0
55.0
024---B
75
53.0
60.0
68.0
69.5
68.0
63.0
58.5
030---B
77
57.0
66.5
71.0
73.0
69.5
66.5
59.0
036---B
77
55.0
66.5
71.0
70.5
69.0
67.0
63.5
042---B
77
57.0
60.0
66.5
69.0
68.0
64.5
58.0
048---B
80
57.0
60.0
68.0
75.0
69.0
66.5
65.5
060---C
80
59.5
65.0
71.5
72.0
67.0
65.0
62.0
NOTE
: Tested in accordance with AHRI Standard 270---95. (Not listed with AHRI).
A--WEIGHTED SOUND POWER LEVEL (dBA) WITH SOUND SHIELD
UNIT SIZE ---
VOLTAGE, SERIES
STANDARD RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
018---B
73
50.5
60.0
66.0
68.0
64.0
60.5
54.0
024---B
73
53.5
60.0
67.0
68.5
66.5
61.5
56.0
030---B
77
57.5
66.0
71.0
72.5
69.0
65.5
57.5
036---B
76
55.5
66.0
70.0
69.5
68.5
66.0
61.5
042---B
74
57.0
60.5
66.5
67.5
67.0
62.5
56.5
048---B
78
57.0
60.5
67.5
74.0
68.0
64.0
62.5
060---C
77
59.5
65.0
71.0
68.5
66.0
61.5
58.5
NOTE
: Tested in accordance with AHRI Standard 270---95. (Not listed with AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE, SERIES
REQUIRED SUBCOOLING ° F (° C)
018---B
8 (4.4)
024---B
11 (6.1)
030---B
9 (5.0)
036---B
10 (5.6)
042---B
11 (6.1)
048---B
12 (6.7)
060---C
11 (6.1)
113AN