is available for that device. Both indoor and outdoor units must have
energy tracking capability for this feature to function fully.
This menu item allows the installer to view the energy usage of each
piece of equipment connected to the system. To return to the previous
screen, touch
BACK
. To exit the Service menus, touch
DONE
.
A14231
6.6. Refrigerant Charging: Greenspeed®
Intelligence, 18VS™, 19VS™ Systems
For variable capacity and multi-stage heat pumps and AC units, a
refrigerant charging menu is available to aid in the proper charging of the
system. Enter the menu from the service screens by touching
REFRIGERANT CHARGING
.
The option for
HTG CHECK CHARGE
is only available for heat pump
units, and not available in AC units.
NOTE:
See the outdoor equipment Installation Instructions for
information on what conditions
CHARGING COOLING
and
HTG
CHECK CHARGE
are available.
6.6.1. Charging
Within the
CHARGING COOLING
or
HTG CHECK
screens, the
installer will have the ability to enter the
LINESET
length and the
VAPOR LINE
diameter. After the selections are made, touch
NEXT
.