Table 9 – Troubleshooting Chart -- Cooling

SYMPTOM

CAUSE

REMEDY

Compressor and outdoor fan

will not start

Power failure

Call power company

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Defective contactor, transformer, control relay, or high--

pressure, loss--of--charge or low--pressure switch

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

UI setting too low/too high

Reset UI setting

DO NOT bypass this compressor time

delay–wait for 5 minutes until time--delay

relay is de--energized

Units have a 5--minute time delay

Compressor will not start but condenser fan

runs

Faulty wiring or circuit

Loose connections in compressor

Check wiring and repair or replace

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

Defective run capacitor, overload, or PTC (positive

temperature coefficient) thermistor

Determine cause and replace

Low input voltage (20 percent low)

Determine cause and correct

Compressor cycles (other than normally sat-

isfying) cooling/heating calls

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

charge to capacities shown on rating plate

Defective compressor

Replace and determine cause

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

Defective run/start capacitor, overload or start relay

Determine cause and replace

Faulty outdoor fan motor or capacitor

Replace

Restriction in refrigerant system

Locate restriction and remove

Compressor operates continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size

UI temperature set too low

Reset UI setting

Low refrigerant charge

Locate leak, repair, and recharge

Air in system

Recover refrigerant, evacuate system, and re-

charge

Outdoor coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty indoor or outdoor coil

Clean coil

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

charge

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

Excessive suction pressure

High heat load

Check for source and eliminate

Reversing valve hung up or leaking internally

Replace valve

Refrigerant overcharged

Recover excess refrigerant

Suction pressure too low

Dirty air filter

Replace filter

Low refrigerant charge

Check for leaks, repair and recharge

Metering device or low side restricted

Remove source of restriction

Insufficient coil airflow

Check filter–replace if necessary

Temperature too low in conditioned area

Reset UI setting

Outdoor ambient below 55

°

F (13

°

C)

Verify low--ambient cooling enabled in UI

Filter drier restricted

Replace

IFM does not run

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft

Insufficient voltage at motor

Determine cause and correct

Power connectors not properly sealed

Connectors should snap easily; do not force

IFM operation is intermittent

Water dripping into motor

Verify proper drip loops in connector wires

Connectors not firmly sealed

Gently pull wires individually to be sure they are

crimped into the housing

577D

--

--

A

Содержание EVOLUTION 577D----A

Страница 1: ...2 High Voltage Connections 12 Routing Power Leads Into Unit 12 Connecting Ground Lead to Ground Screw 12 Routing Control Power Wires 13 Accessory Installation 13 Special Procedures for 208 v Operation...

Страница 2: ...rooftop or on cement slab See Fig 4 for roof curb dimensions Standard units can be converted to downflow vertical discharge configurations for rooftop applications Models with an N in the thirteenth...

Страница 3: ...in 1219 mm above the unit top The maximum horizontal extension of a partial overhang must not exceed 48 in 1219 mm IMPORTANT Do not restrict outdoor airflow An air restriction at either the outdoor ai...

Страница 4: ...sepan units G H C B A F D E G H A09414 UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 27...

Страница 5: ...5 A09556 Fig 5 577D A24 30 Unit Dimensions 577D A...

Страница 6: ...6 A09557 Fig 6 577D A36 60 Unit Dimensions 577D A...

Страница 7: ...Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variable based on Comfort Roll back see User Interface instructions for...

Страница 8: ...1750 Max 1600 1600 1600 2000 2000 2000 Furnace gas ht airflow Low Stage 815 1215 1255 845 1215 1255 Furnace gas ht airflow High Stage 1385 1885 1875 1300 1910 1920 Size in mm 11x10 279x254 11x10 279x...

Страница 9: ...shackles clevis pins and straps to the base rails of the unit Be sure materials are rated to hold the weight of the unit See Fig 7 3 Attach a clevis of sufficient strength in the middle of the straps...

Страница 10: ...unit from factory Insure openings are air and watertight The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence type air c...

Страница 11: ...1 2 in FPT gas inlet on the unit gas valve For natural gas applications the gas pressure at unit gas connection must not be less than 4 0 IN W C or greater than 13 IN W C while the unit is operating F...

Страница 12: ...or within sight from the unit Refer to the unit rating plate NEC and local codes for maximum fuse circuit breaker size and minimum circuit amps ampacity for wire sizing The field supplied disconnect...

Страница 13: ...door Air Temperature Sensor OAT EQUIPMENT OPERATION HAZARD The installation of an outdoor air temperature sensor OAT using the Evolution control board OAT terminals is required Many Evolution features...

Страница 14: ...GROUND SCREW IN SPLICE BOX YEL BLK GROUND LEAD SINGLE PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC National Electrical Code Field Wiring Splice Connections NOTE Use copper wire only L1 L2 A06299...

Страница 15: ...15 FURNACE BOARD HP AC BOARD A09108 Fig 13 Control Plate A06357 Fig 14 Control Voltage Wiring Connections 577D A...

Страница 16: ...llow 5 minutes to elapse then light unit b Make sure that condenser fan blade is correctly positioned in fan orifice Top 1 3 of condenser fan blade should be within fan orifice venturi c Ensure fan hu...

Страница 17: ...laced 4 Passing all of the tests motor control module alone can be replaced MOTOR TURNS SLOWLY 1 Low static pressure loading of blower while access panel is removed will cause blower to run slowly Par...

Страница 18: ...18 A10217C Fig 16 Connection Wiring Schematic 577D A Single Phase Gas Inputs 040 060 090 kBtu hr 577D A...

Страница 19: ...19 A10217L Fig 16 Cont Ladder Wiring Schematic 577D A Single Phase Gas Inputs 040 060 090 kBtu hr 577D A...

Страница 20: ...20 A10219C Fig 17 Connection Wiring Schematic 577D A Single Phase Gas Inputs 115 130 kBtu hr 577D A...

Страница 21: ...21 A10219L Fig 17 Cont Ladder Wiring Schematic 577D A Single Phase Gas Inputs 115 130 kBtu hr 577D A...

Страница 22: ...onger than 3 minutes code changes to lockout 13 If open less than 3 minutes status code 33 continues to flash until blower shuts off Check for loose blower wheel restricted vent excessive wind dirty f...

Страница 23: ...EQUENCE OF OPERATION COOLING OPERATION With a call for first stage cooling the outdoor fan and low stage compressor are energized If low stage cannot satisfy cooling demand high stage cooling is energ...

Страница 24: ...d has failed Control board needs to be replaced Brown Out 230 v 46 Line voltage 187v for at least 4 seconds Compressor and fan operation not allowed until voltage 190v Verify line voltage No 230v at U...

Страница 25: ...ils to remain closed the inducer will remain running After the pressure switch re closes the Evolution ignition control will begin a 15 second pre purge period 2 Trial For Ignition Sequence The spark...

Страница 26: ...d local codes or contact your distributor to determine the required orifice size 2 Adjust manifold pressure to obtain low stage input rate See Fig 19 a Turn off gas supply to unit b Remove pipe plug o...

Страница 27: ...result of step f by Btu heating value of the gas to obtain total measured input shown in Table 6 Consult the local gas supplier if the heating value of gas is not known EXAMPLE Assume a 90 000 high s...

Страница 28: ...m problem in the case of a gas component failure To initiate the component test procedure ensure that there are no UI inputs to the control the ABCD connector can be removed from the Evolution control...

Страница 29: ...the Refrigeration Service Techniques Manual Refrigerants Section NO CHARGE Check for leak Use standard evacuating techniques After evacuating system weigh in the specified amount of refrigerant refer...

Страница 30: ...30 A06360 Fig 22 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 23 Cooling Charging Table Subcooling 577D A...

Страница 31: ...ructions Air Filter IMPORTANT Never operate the unit without a suitable air filter in the return air duct system Always replace the filter with the same dimensional size and type as originally install...

Страница 32: ...ergent and water solution Rinse coils with clear water using a garden hose Be careful not to splash water on motors insulation wiring or air filter s For best results spray condenser coil fins from in...

Страница 33: ...switches are attached to refrigeration system under pressure it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists If switch must be re...

Страница 34: ...ols the following functions Indoor blower operation Gas valve Inducer motor Remote sparker module Pressure switch monitoring gas SYSTEMS COMMUNICATION FAILURE If communication with the Evolution Contr...

Страница 35: ...insure thermistor is mounted properly Outdoor air thermistor OAT is field mounted and connected Verify that the OAT has been properly installed 0 10 20 30 40 50 60 70 80 90 0 20 40 60 80 100 120 TEMPE...

Страница 36: ...erformance and to minimize possible equipment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as coastal applica...

Страница 37: ...550 psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE...

Страница 38: ...operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low Reset UI setting Low refrigerant charge Locate leak repair...

Страница 39: ...t 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace filter...

Страница 40: ...UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR PRES...

Отзывы: