Bryant EVOLUTION 577D----A Скачать руководство пользователя страница 16

16

PRE--START--UP

FIRE, EXPLOSION, ELECTRICAL SHOCK AND

ENVIRONMENTAL HAZARD

Failure to follow this warning could result in personal

injury or death and/or property damage.

1. Follow recognized safety practices and wear protective

goggles when checking or servicing refrigerant system.

2. Do not operate compressor or provide any electric power

to unit unless compressor terminal cover is in place and
secured.

3. Do not remove compressor terminal cover until all

electrical sources are disconnected and tagged.

4. Relieve and recover all refrigerant from system before

touching or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor

terminals.

5. Never attempt to repair soldered connection while

refrigerant system is under pressure.

6. Do not use torch to remove any component. System

contains oil and refrigerant under pressure.

7. To remove a component, wear protective goggles and

proceed as follows:

a. Shut off gas supply to unit.

b. Shut off electrical power to unit and install

lockout tag.

c. Relieve and reclaim all refrigerant from system

using both high-- and low--pressure ports.

d. Cut component connecting tubing with tubing

cutter and remove component from unit.

e. Carefully unsweat remaining tubing stubs when

necessary. Oil can ignite when exposed to flame.

!

WARNING

Use the Start--Up Checklist supplied at the end of this book and

proceed as follows to inspect and prepare the unit for initial
start--up:

1. Remove all access panels. (See Fig. 24.)
2. Read and follow instructions on all DANGER, WARNING,

CAUTION, and INFORMATION labels attached to, or
shipped with unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages, such as

broken lines, loose parts, disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and

on unit base. Detecting oil generally indicates a

refrigerant leak. Leak test all refrigerant tubing
connections using electronic leak detector, or

liquid--soap solution. If a refrigerant leak is detected, see
following Check for Refrigerant Leaks section.

c. Inspect all field-- and factory--wiring connections. Be

sure that connections are completed and tight.

d. Ensure wires do not touch refrigerant tubing or sharp

sheet metal edges.

e. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure gas line is free of air. Before lighting the unit

for the first time, perform the following tasks with the
gas valve in the OFF position.

NOTE

: If the gas supply pipe was not purged before connecting

the unit, it will be full of air. It is recommended that the ground

joint union be loosened, and the supply line be allowed to purge
until the odor of gas is detected. Never purge gas lines into a
combustion chamber. Immediately upon detection of gas odor,
retighten the union. Allow 5 minutes to elapse, then light unit.

b. Make sure that condenser--fan blade is correctly

positioned in fan orifice. Top 1/3 of condenser fan blade

should be within fan orifice venturi.

c. Ensure fan hub is positioned correctly with respect to

motor housing (See Fig. 27).

d. Make sure that air filter(s) is in place.

e. Make sure that condensate drain trap is filled with water

to ensure proper drainage.

f. Make sure that all tools and miscellaneous loose parts

have been removed.

5. Compressors are internally spring mounted. Do not loosen

or remove compressor holddown bolts.

6. Each unit system has two Schrader--type ports, one

low--side Schrader fitting located on the suction line, and

one high--side Schrader fitting located on the compressor
discharge line. Be sure that caps on the ports are tight.

START--UP

Unit Start--Up and Troubleshooting

NOTE: Always check high-- and low--voltage supply to the unit
components. Check the integrity of the plug receptacle connections

and unit wiring harness prior to assuming a component failure.

A. LED Description

LEDs built into Evolution control boards provide installer or
service person information concerning operation and/or fault

condition of the unit controls and ECM motor. This information is

also available at the system UI in text with basic troubleshooting
instructions. Careful use of information displayed will reduce the

need for extensive manual troubleshooting.
Both the furnace and heat pump (HP)/air conditioner (AC) boards

have an amber LED and a green LED. On the HP/AC board, these
are located near the System Communications connector (ABCD)

(lower right corner of the HP/AC board as installed in the unit).

On the furnace board, these are located at the upper right side,
adjacent to the fuse, above the terminal block. The amber LED is

the System Status LED, labeled STATUS. The green LED, labeled
COMM, is used as an indicator of system communications status

(See Fig. 15 and 18).
Status Codes will be displayed on the STATUS LED using the
following protocol:

1. The number of short flashes indicates first digit of code.
2. The number of long flashes indicates second digit of code.
3. A short flash is 0.25 seconds on. A long flash is 1 second

on.

4. The time between flashes is 0.25 seconds.
5. The time between last short flash and first long flash is 1

second.

6. The LEDs will be off for 2.5 seconds before repeating code.
7. If multiple status codes are active concurrently, the highest

priority status code is displayed.

B. Control

Start--Up

and

System

Communications

Troubleshooting

On power up, green COMM LEDs will be turned off until
successful system communications are established (this should

happen within 10 seconds). Once communications with UI are
successful, both COMM LEDs will be lit and held on. At the same

time, amber STATUS LEDs will be lit and held continuously on

until a request for operating mode is received. The STATUS LED
will be on any time unit is in idle mode.
If, at any time, communications are not successful for a period
exceeding 2 minutes, the Evolution control will only allow

577D

--

--

A

Содержание EVOLUTION 577D----A

Страница 1: ...2 High Voltage Connections 12 Routing Power Leads Into Unit 12 Connecting Ground Lead to Ground Screw 12 Routing Control Power Wires 13 Accessory Installation 13 Special Procedures for 208 v Operation...

Страница 2: ...rooftop or on cement slab See Fig 4 for roof curb dimensions Standard units can be converted to downflow vertical discharge configurations for rooftop applications Models with an N in the thirteenth...

Страница 3: ...in 1219 mm above the unit top The maximum horizontal extension of a partial overhang must not exceed 48 in 1219 mm IMPORTANT Do not restrict outdoor airflow An air restriction at either the outdoor ai...

Страница 4: ...sepan units G H C B A F D E G H A09414 UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 27...

Страница 5: ...5 A09556 Fig 5 577D A24 30 Unit Dimensions 577D A...

Страница 6: ...6 A09557 Fig 6 577D A36 60 Unit Dimensions 577D A...

Страница 7: ...Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variable based on Comfort Roll back see User Interface instructions for...

Страница 8: ...1750 Max 1600 1600 1600 2000 2000 2000 Furnace gas ht airflow Low Stage 815 1215 1255 845 1215 1255 Furnace gas ht airflow High Stage 1385 1885 1875 1300 1910 1920 Size in mm 11x10 279x254 11x10 279x...

Страница 9: ...shackles clevis pins and straps to the base rails of the unit Be sure materials are rated to hold the weight of the unit See Fig 7 3 Attach a clevis of sufficient strength in the middle of the straps...

Страница 10: ...unit from factory Insure openings are air and watertight The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence type air c...

Страница 11: ...1 2 in FPT gas inlet on the unit gas valve For natural gas applications the gas pressure at unit gas connection must not be less than 4 0 IN W C or greater than 13 IN W C while the unit is operating F...

Страница 12: ...or within sight from the unit Refer to the unit rating plate NEC and local codes for maximum fuse circuit breaker size and minimum circuit amps ampacity for wire sizing The field supplied disconnect...

Страница 13: ...door Air Temperature Sensor OAT EQUIPMENT OPERATION HAZARD The installation of an outdoor air temperature sensor OAT using the Evolution control board OAT terminals is required Many Evolution features...

Страница 14: ...GROUND SCREW IN SPLICE BOX YEL BLK GROUND LEAD SINGLE PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC National Electrical Code Field Wiring Splice Connections NOTE Use copper wire only L1 L2 A06299...

Страница 15: ...15 FURNACE BOARD HP AC BOARD A09108 Fig 13 Control Plate A06357 Fig 14 Control Voltage Wiring Connections 577D A...

Страница 16: ...llow 5 minutes to elapse then light unit b Make sure that condenser fan blade is correctly positioned in fan orifice Top 1 3 of condenser fan blade should be within fan orifice venturi c Ensure fan hu...

Страница 17: ...laced 4 Passing all of the tests motor control module alone can be replaced MOTOR TURNS SLOWLY 1 Low static pressure loading of blower while access panel is removed will cause blower to run slowly Par...

Страница 18: ...18 A10217C Fig 16 Connection Wiring Schematic 577D A Single Phase Gas Inputs 040 060 090 kBtu hr 577D A...

Страница 19: ...19 A10217L Fig 16 Cont Ladder Wiring Schematic 577D A Single Phase Gas Inputs 040 060 090 kBtu hr 577D A...

Страница 20: ...20 A10219C Fig 17 Connection Wiring Schematic 577D A Single Phase Gas Inputs 115 130 kBtu hr 577D A...

Страница 21: ...21 A10219L Fig 17 Cont Ladder Wiring Schematic 577D A Single Phase Gas Inputs 115 130 kBtu hr 577D A...

Страница 22: ...onger than 3 minutes code changes to lockout 13 If open less than 3 minutes status code 33 continues to flash until blower shuts off Check for loose blower wheel restricted vent excessive wind dirty f...

Страница 23: ...EQUENCE OF OPERATION COOLING OPERATION With a call for first stage cooling the outdoor fan and low stage compressor are energized If low stage cannot satisfy cooling demand high stage cooling is energ...

Страница 24: ...d has failed Control board needs to be replaced Brown Out 230 v 46 Line voltage 187v for at least 4 seconds Compressor and fan operation not allowed until voltage 190v Verify line voltage No 230v at U...

Страница 25: ...ils to remain closed the inducer will remain running After the pressure switch re closes the Evolution ignition control will begin a 15 second pre purge period 2 Trial For Ignition Sequence The spark...

Страница 26: ...d local codes or contact your distributor to determine the required orifice size 2 Adjust manifold pressure to obtain low stage input rate See Fig 19 a Turn off gas supply to unit b Remove pipe plug o...

Страница 27: ...result of step f by Btu heating value of the gas to obtain total measured input shown in Table 6 Consult the local gas supplier if the heating value of gas is not known EXAMPLE Assume a 90 000 high s...

Страница 28: ...m problem in the case of a gas component failure To initiate the component test procedure ensure that there are no UI inputs to the control the ABCD connector can be removed from the Evolution control...

Страница 29: ...the Refrigeration Service Techniques Manual Refrigerants Section NO CHARGE Check for leak Use standard evacuating techniques After evacuating system weigh in the specified amount of refrigerant refer...

Страница 30: ...30 A06360 Fig 22 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 23 Cooling Charging Table Subcooling 577D A...

Страница 31: ...ructions Air Filter IMPORTANT Never operate the unit without a suitable air filter in the return air duct system Always replace the filter with the same dimensional size and type as originally install...

Страница 32: ...ergent and water solution Rinse coils with clear water using a garden hose Be careful not to splash water on motors insulation wiring or air filter s For best results spray condenser coil fins from in...

Страница 33: ...switches are attached to refrigeration system under pressure it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists If switch must be re...

Страница 34: ...ols the following functions Indoor blower operation Gas valve Inducer motor Remote sparker module Pressure switch monitoring gas SYSTEMS COMMUNICATION FAILURE If communication with the Evolution Contr...

Страница 35: ...insure thermistor is mounted properly Outdoor air thermistor OAT is field mounted and connected Verify that the OAT has been properly installed 0 10 20 30 40 50 60 70 80 90 0 20 40 60 80 100 120 TEMPE...

Страница 36: ...erformance and to minimize possible equipment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as coastal applica...

Страница 37: ...550 psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE...

Страница 38: ...operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low Reset UI setting Low refrigerant charge Locate leak repair...

Страница 39: ...t 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace filter...

Страница 40: ...UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR PRES...

Отзывы: