ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued

 

9. High-Pressure Switch

 

Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400  ± 10 
psig and resets at 298 ± 20 psig. Provides protection against compressor damage due to loss of outdoor  airflow.  To prevent rapid compressor recycling, 
Cycle Protector can be used with this switch. 

SUGGESTED USE:  Installations exposed to very ‘‘dirty’’ outdoor air.

Installations where condenser inlet air temperature exceeds 125°F (51.7°C).

 

10. Inlet Grille Kit

 

 

A field-installed enhanced inlet grille to replace the standard inlet grille on residential air conditioners and heat pumps. 

SUGGESTED USE:  For greater protection against inclement weather, incidental damage, and vandalism.

 

11. Liquid-Line Solenoid Valve (LSV)

 

 

An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts 
refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle. 

 

Note:

 

 Compressor Start Assist–Capacitor/Relay Type must also be used. Do not use with hard shutoff TXV. 

SUGGESTED USE:  For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

In certain long-line-applications. Refer to Long-Line Application Guideline.

 

12. Low-Ambient Controller

 

 

Head-pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle 
the outdoor fan motor in order to maintain condensing temperature within normal operating limits (approximately 100°F high and 60°F low).
The control will maintain working head pressure at low-ambient temperatures down to 0°F when properly installed.  

SUGGESTED USE:  Cooling operation at outdoor temperatures below 55°F (12.8°C).

 

13. Low-Pressure Switch

 

 

Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27 
psig. Prevents indoor coil freeze-up due to loss of indoor airflow. Provides protection against compressor damage due to loss of refrigerant charge. To 
prevent rapid compressor recycling, Cycle Protector can be used with this switch. 

SUGGESTED USE:  Where indoor coil is exposed to ‘‘dirty’’ air.

All commercial installations.

 

14. MotorMaster® Control

 

 

A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing 
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F, it maintains condensing temperature at 100°F ± 10°F. 

SUGGESTED USE:  Cooling operation at outdoor temperatures below 55°F.

All commercial installations.

 

15. Outdoor Air Temperature Sensor

 

 

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat 

SUGGESTED USE:  All corporate programmable thermostats.

 

16. Sound Hood

 

 

Wraparound sound attenuation cover for the compressor. Reduces unit sound level by about 2 dBA. 

SUGGESTED USE:  Unit installed closer than 15 ft to quiet areas—bedrooms, etc.

Unit installed between 2 houses less than 10 ft apart.

 

17. Thermostatic Expansion Valve (TXV)

 

 

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the 
evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB valves are available.  Do not use hard shutoff TXV 
with Liquid-Line Solenoid Valve.

SUGGESTED USE:  For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Required for use on all zoning systems.

 

18. Time-Delay Relay

 

 

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. 

SUGGESTED USE:  For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Required for use on all zoning systems.

 

19. Winter Start Control

 

 

An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load 
conditions. 

SUGGESTED USE:  All air conditioners where Low-Ambient Controller has been added.

Содержание ELECTRIC AIR CONDITIONER 561C

Страница 1: ...each unit with a hard smooth finish that will last for many years All screws on cabinet exterior are coated for a long lasting rust resistant quality appearance TOTALLY ENCLOSED FAN MOTOR Means greate...

Страница 2: ...17 3 4 7 7 8 8 3 8 9 3 8 18 X 18 024 A D 18 23 15 16 3 3 16 5 8 3 15 16 5 16 17 3 4 10 3 16 16 1 8 17 3 4 7 7 8 8 3 8 9 1 2 18 X 18 030 A D 22 1 2 21 15 16 3 3 16 3 4 3 11 16 18 1 8 19 3 4 22 1 4 14 3...

Страница 3: ...1 0 66 5 59 5 018 D 80 57 5 64 0 69 5 72 0 71 5 68 0 60 0 024 A 80 59 5 65 0 69 5 74 0 73 0 70 0 62 0 024 D 82 55 5 63 0 68 0 71 0 70 5 67 5 58 5 030 A 80 55 0 62 5 73 5 74 0 71 0 67 5 59 5 030 D 80 5...

Страница 4: ...AL EQUIPMENT Coastal Filter KAACF0601SML KAACF0401MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Low Ambient Controller N A P251 0083 RCD Crankcase Heater KAACH1001AAA Inlet Grille Kit...

Страница 5: ...nd 1125 1100 1125 1 5 and 1125 1 4 and 1125 1 5 and 1125 1 4 and 1125 Volts Hertz Phase 208 230 60 1 460 60 1 208 230 60 1 460 60 1 Condenser Airflow CFM 2500 3400 OPTIONAL EQUIPMENT Coastal Filter KA...

Страница 6: ...Volts Hertz Phase 208 230 60 1 460 60 1 208 230 60 1 460 60 1 Condenser Airflow CFM 3400 OPTIONAL EQUIPMENT Coastal Filter KAACF0501LRG Time Delay Relay KAATD0101TDR Cycle Protector Standard KSACY0101...

Страница 7: ...ations where outdoor design temperature exceeds 105 F 40 6 C Replacement installations with hard shutoff expansion valve on indoor coil Installations where Liquid Line Solenoid Valve has been added 4...

Страница 8: ...nt pressure drops to about 27 psig Prevents indoor coil freeze up due to loss of indoor airflow Provides protection against compressor damage due to loss of refrigerant charge To prevent rapid compres...

Страница 9: ...10 00 9 05 CC5A CD5AW030 22 600 NONE 10 00 10 00 9 10 CE3AA024 22 600 NONE 10 00 10 00 9 10 CE3AA030 23 000 NONE 10 20 10 20 9 20 CF5AA024 22 600 NONE 10 00 10 00 9 10 CK3BA024 22 400 NONE 10 00 10 00...

Страница 10: ...5BT036 29 000 TDR 11 00 11 00 10 05 CK5A CK5BW030 28 000 TDR 10 50 10 50 9 70 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CC5A CD5AW030 28 000 TDR 10 50 10 50 9 80 CD5AW036 29 000 TDR 11 00 11 00 10...

Страница 11: ...R 10 50 10 50 9 80 COILS 333 B J AV060100 VARIABLE SPEED FURNACE CC5A CD5AA042 33 400 TDR 10 80 10 80 10 05 CD5AW036 33 400 TDR 10 50 10 50 10 00 CK5A CK5BA042 33 400 TDR 10 80 10 80 10 10 CK5A CK5BT0...

Страница 12: ...42 40 000 TDR 10 50 10 50 9 45 CC5A CD5AC048 40 000 TDR 10 70 10 70 9 45 CC5A CD5AW042 40 000 TDR 10 50 10 50 9 55 CC5A CD5AW048 40 000 TDR 10 70 10 70 9 45 CD5AA048 40 000 TDR 10 70 10 70 9 45 CE3AA0...

Страница 13: ...0 TDR TXV 11 00 9 55 FC4BNB070 48 500 TDR TXV 11 00 9 50 FG3AA048 46 000 NONE 10 00 10 50 10 50 9 20 FG3AA060 47 000 NONE 10 20 10 50 10 50 9 35 FK4CNF005 48 000 TDR TXV 11 50 9 90 FK4CNF006 49 000 TD...

Страница 14: ...060100 VARIABLE SPEED FURNACE CC5A CD5AA060 46 000 TDR 10 50 10 50 9 15 CC5A CD5AC048 45 500 TDR 10 80 10 80 9 30 CK3BA048 45 500 TDR 10 80 10 80 9 30 CK3BA060 45 500 TDR 11 00 11 00 9 15 CK5A CK5BA04...

Страница 15: ...8 15 8 1 77 14 9 14 9 1 87 14 1 14 1 1 96 13 2 13 2 2 05 12 3 12 3 2 14 675 72 21 9 10 8 1 86 20 7 10 4 1 97 19 4 9 86 2 07 18 0 9 39 2 18 16 7 8 90 2 27 15 3 8 44 2 36 67 19 9 13 7 1 80 18 7 13 2 1 9...

Страница 16: ...91 20 0 11 4 3 00 67 25 8 18 3 2 37 24 3 17 7 2 48 22 7 17 1 2 59 21 2 16 5 2 69 19 6 15 8 2 79 18 0 15 2 2 87 62 23 4 22 0 2 28 22 0 21 3 2 39 20 6 20 4 2 50 19 3 19 3 2 60 18 1 18 1 2 70 16 9 16 9...

Страница 17: ...rmance With Other Indoor Sections Indoor Section Unit Size Cooling Indoor Section Unit Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 04 1 01 COILS 333 B J AV048080 VARIABLE SPEED FURNACE...

Страница 18: ...0 1 00 COILS 333 B J AV060100 VARIABLE SPEED FURNACE 042 1 00 1 00 CC5A CD5AA 042 0 99 0 92 CC5A CD5AW 042 1 00 1 00 CD5AW 036 0 99 0 92 CD5AW 036 1 00 1 00 CK5A CK5BA 042 0 99 0 92 CE3AA 036 0 99 1 0...

Страница 19: ...2 26 6 3 56 34 0 25 7 3 74 31 8 24 8 3 93 29 6 23 9 4 11 27 3 23 1 4 29 62 34 9 33 1 3 24 33 0 32 0 3 42 31 0 30 8 3 61 29 2 29 2 3 80 27 5 27 5 3 99 25 8 25 8 4 19 57 34 1 34 1 3 22 32 5 32 5 3 41 30...

Страница 20: ...Unit Size Cooling Indoor Section Unit Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 1 00 1 00 CD5AA 048 1 00 0 93 CC5A CD5AC 048 0 99 1 00 CE3AA 042 1 00 0 94 CC5A CD5AW 042 1 00 1 00 048...

Страница 21: ...0 4 97 31 8 25 8 5 17 62 41 1 37 5 3 88 38 7 36 3 4 11 36 3 35 0 4 35 34 0 33 6 4 57 31 7 31 7 4 78 29 3 29 3 5 01 57 39 4 39 4 3 82 37 6 37 6 4 07 35 7 35 7 4 31 33 7 33 7 4 55 31 7 31 7 4 78 29 3 2...

Страница 22: ...or Section Unit Size Cooling Capacity Power Capacity Power CD5AA 048 1 00 1 00 CD5AA 048 0 99 1 00 CC5A CD5AA 060 1 00 1 00 CD5AC 048 0 99 1 00 CC5A CD5AC 048 0 98 0 99 CE3AA 048 0 99 1 01 CC5A CD5AW...

Страница 23: ...44 0 40 7 4 55 41 9 39 6 5 05 39 8 38 4 5 60 37 5 37 0 6 18 35 2 35 2 6 79 57 44 1 44 1 4 04 42 5 42 5 4 52 40 8 40 8 5 03 39 1 39 1 5 57 37 2 37 2 6 17 35 2 35 2 6 79 1800 72 56 2 28 4 4 37 53 7 27...

Страница 24: ...5 17 64 0 31 3 5 67 61 2 30 3 6 23 58 3 29 2 6 85 55 2 28 1 7 53 51 9 26 9 8 27 67 60 8 40 4 4 99 58 4 39 4 5 48 55 8 38 3 6 04 53 1 37 2 6 65 50 2 36 0 7 33 47 2 34 8 8 05 62 55 5 48 4 4 83 53 2 47...

Страница 25: ...9 0 139 0 149 0 55 TCG 35 8 33 8 31 8 29 6 27 3 25 1 23 0 20 9 KW 2 13 2 29 2 45 2 60 2 74 2 87 2 98 3 07 SDT 70 9 83 8 97 0 109 0 120 0 131 0 141 0 151 0 561C030 A D 30 TCG 28 0 26 0 24 0 22 0 20 1 1...

Страница 26: ...CG 46 6 44 7 42 7 40 6 38 4 36 1 33 8 31 4 KW 3 28 3 61 3 99 4 41 4 87 5 37 5 89 6 44 SDT 77 7 88 2 98 6 109 0 119 0 129 0 139 0 149 0 40 TCG 50 9 48 8 46 7 44 4 42 1 39 7 37 2 34 7 KW 3 34 3 68 4 06...

Страница 27: ...50 ft indoor coil below 150 ft 6 For interconnecting refrigerant tube lengths between 50 and 175 ft consult Residential Split Systems Long Line Application Guideline available from equipment distribut...

Страница 28: ...cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Ai...

Отзывы: