—24—
DETAILED COOLING CAPACITIES* Continued
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed.
** Unit kw is total of indoor and outdoor unit kilowatts.
EWB—Entering Wet Bulb
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75
85
95
105
115
125
CFM
EWB
Capacity
MBtuh†
Total
Sys
KW**
Capacity
MBtuh†
Total
Sys
KW**
Capacity
MBtuh†
Total
Sys
KW**
Capacity
MBtuh†
Total
Sys
KW**
Capacity
MBtuh†
Total
Sys
KW**
Capacity
MBtuh†
Total
Sys
KW**
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
561C060-A, B, E Outdoor Section With CC5A/CD5AW060 Indoor Section
1750
72
66.3
32.0
5.14
63.7
31.0
5.64
61.0
30.0
6.20
58.1
28.9
6.82
55.0
27.8
7.50
51.7
26.6
8.24
67
60.6
40.0
4.96
58.1
38.9
5.46
55.6
37.9
6.01
52.9
36.7
6.63
50.0
35.6
7.30
47.1
34.4
8.02
62
55.2
47.8
4.81
52.9
46.7
5.30
50.6
45.5
5.85
48.1
44.3
6.46
45.4
42.9
7.12
42.8
41.5
7.80
57
51.8
51.8
4.72
50.0
50.0
5.22
48.2
48.2
5.78
46.3
46.3
6.40
44.2
44.2
7.07
42.1
42.1
7.77
1800
72
66.6
32.3
5.17
64.0
31.3
5.67
61.2
30.3
6.23
58.3
29.2
6.85
55.2
28.1
7.53
51.9
26.9
8.27
67
60.8
40.4
4.99
58.4
39.4
5.48
55.8
38.3
6.04
53.1
37.2
6.65
50.2
36.0
7.33
47.2
34.8
8.05
62
55.5
48.4
4.83
53.2
47.3
5.33
50.8
46.1
5.88
48.2
44.8
6.49
45.6
43.5
7.14
42.9
42.0
7.83
57
52.2
52.2
4.75
50.4
50.4
5.25
48.6
48.6
5.81
46.6
46.6
6.43
44.5
44.5
7.11
42.4
42.4
7.81
2100
72
68.1
33.9
5.34
65.3
32.9
5.83
62.4
31.8
6.39
59.4
30.7
7.01
56.1
29.6
7.69
52.8
28.4
8.43
67
62.2
43.1
5.14
59.7
42.1
5.64
57.0
41.0
6.20
54.2
39.8
6.81
51.2
38.6
7.48
48.0
37.4
8.21
62
56.7
52.0
4.98
54.4
50.8
5.48
51.9
49.5
6.03
49.3
48.0
6.64
46.6
46.3
7.30
44.1
44.1
8.01
57
54.6
54.6
4.93
52.7
52.7
5.43
50.7
50.7
5.99
48.6
48.6
6.62
46.4
46.4
7.29
44.1
44.1
8.01
2250
72
68.7
34.6
5.41
65.9
33.6
5.91
62.9
32.6
6.47
59.8
31.4
7.09
56.5
30.3
7.77
53.1
29.1
8.51
67
62.8
44.4
5.22
60.2
43.4
5.71
57.5
42.3
6.27
54.6
41.1
6.89
51.5
39.9
7.56
48.3
38.6
8.28
62
57.3
53.7
5.05
54.9
52.4
5.55
52.4
51.0
6.10
49.8
49.3
6.71
47.2
47.2
7.38
44.8
44.8
8.11
57
55.6
55.6
5.01
53.7
53.7
5.51
51.6
51.6
6.08
49.5
49.5
6.70
47.2
47.2
7.38
44.8
44.8
8.11
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Unit
Size
Cooling
Indoor
Section
Unit
Size
Cooling
Capacity
Power
Capacity
Power
CC5A/CD5AW
060
1.00
1.00
FG3AAA
060
0.99
1.00
CC5A/CD5AA
060
0.96
0.97
FK4CNB
006
1.02
1.00
CE3AA
060
1.01
0.99
COILS + 333(B,J)AV060100 VARIABLE-SPEED FURNACE
CK3BA
060
0.96
1.00
CK3BA
060
0.96
0.95
CK5A/CK5BA
060
0.96
0.97
CK5A/CK5BA
060
0.96
0.95
CK5A/CK5BN
060
0.96
0.98
CK5A/CK5BX
060
1.00
0.95
CK5A/CK5BX
060
1.00
1.00
COILS + 333(B,J)AV060120 VARIABLE-SPEED FURNACE
F(A,B)4AN(F,B)
060
1.01
1.05
CK3BA
060
0.96
0.96
FB4ANB
070
1.02
1.03
CK5A/CK5BA
060
0.96
0.96
FC4BN(F,B)
060
1.00
1.04
CK5A/CK5BX
060
0.96
0.96
FC4BNB
070
1.02
1.02
—
—
—